WEG · Soft starter
SSW900 soft starter with SSW900-CRS485-W Modbus RTU module Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- Low word first
- Baud rate
- 19200
- Parity
- Even
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 1 | 1 | SSW %In (S1.1.6) Net Id 1. Current in % of the softstarter rated current, 0.0 to 999.9 %, one decimal place. | UInt16 | % | 0.1 | R |
| 2 | 1 | Motor %In (S1.1.5) Net Id 2. Current in % of the motor rated current, 0.0 to 999.9 %, one decimal place. | UInt16 | % | 0.1 | R |
| 3 | 1 | Motor %Vn, main line (S1.2.5) Net Id 3. Main line voltage in % of the motor rated voltage, 0.0 to 999.9 %. | UInt16 | % | 0.1 | R |
| 4 | 1 | Main line voltage, average (S1.2.4) Net Id 4. Average of the three main line voltages, 0.0 to 999.9 V, one decimal place. | UInt16 | V | 0.1 | R |
| 5 | 1 | SSW %Vn, main line (S1.2.6) Net Id 5. Main line voltage in % of the softstarter rated voltage, 0.0 to 999.9 %. | UInt16 | % | 0.1 | R |
| 6 | 1 | Motor %Vn, output voltage (S1.3.2) Net Id 6. Output voltage in % of the motor rated voltage, 0.0 to 999.9 %. | UInt16 | % | 0.1 | R |
| 7 | 1 | Output voltage, average (S1.3.1) Net Id 7. Average output voltage, 0.0 to 999.9 V, one decimal place. | UInt16 | V | 0.1 | R |
| 8 | 1 | Power factor (S1.5.4) Net Id 8, an 8-bit value carried in one 16-bit register. Power factor, 0.00 to 1.00, two decimal places. | UInt16 | - | 0.01 | R |
| 9 | 1 | Motor torque (S1.7.1) Net Id 9. Motor torque in % of the rated torque, 0.0 to 999.9 %, one decimal place. | UInt16 | % | 0.1 | R |
| 10 | 2 | Active power (S1.5.1) Net Id 10. Active power, 32-bit value 0.0 to 11700.0 kW, one decimal place (two registers, low word first on the wire). | UInt32 | kW | 0.1 | R |
| 12 | 2 | Apparent power (S1.5.2) Net Id 12. Apparent power, 32-bit value 0.0 to 11700.0 kVA, one decimal place. | UInt32 | kVA | 0.1 | R |
| 14 | 2 | Reactive power (S1.5.3) Net Id 14. Reactive power, 32-bit value 0.0 to 11700.0 kVAr, one decimal place. | UInt32 | kVAr | 0.1 | R |
| 17 | 1 | PLL frequency (S1.6.2) Net Id 17. Mains frequency measured by the phase-locked loop, 0.0 to 99.9 Hz. | UInt16 | Hz | 0.1 | R |
| 21 | 1 | SCR blocking voltage R-U (S1.4.1) Net Id 21. R-U thyristor blocking voltage, 0.0 to 999.9 V. | UInt16 | V | 0.1 | R |
| 22 | 1 | SCR blocking voltage S-V (S1.4.2) Net Id 22. S-V thyristor blocking voltage, 0.0 to 999.9 V. | UInt16 | V | 0.1 | R |
| 23 | 1 | SCR blocking voltage T-W (S1.4.3) Net Id 23. T-W thyristor blocking voltage, 0.0 to 999.9 V. | UInt16 | V | 0.1 | R |
| 24 | 2 | Current, average (S1.1.4) Net Id 24. Current, 32-bit value with one decimal place (0.0 to 14544.0 A), so the two words carry the value times 10. | UInt32 | A | 0.1 | R |
| 26 | 2 | Current, R phase (S1.1.1) Net Id 26. Current, 32-bit value with one decimal place (0.0 to 14544.0 A), so the two words carry the value times 10. | UInt32 | A | 0.1 | R |
| 28 | 2 | Current, S phase (S1.1.2) Net Id 28. Current, 32-bit value with one decimal place (0.0 to 14544.0 A), so the two words carry the value times 10. | UInt32 | A | 0.1 | R |
| 30 | 2 | Current, T phase (S1.1.3) Net Id 30. Current, 32-bit value with one decimal place (0.0 to 14544.0 A), so the two words carry the value times 10. | UInt32 | A | 0.1 | R |
| 33 | 1 | Main line voltage R-S (S1.2.1) Net Id 33. R-S line voltage, 0.0 to 999.9 V. | UInt16 | V | 0.1 | R |
| 34 | 1 | Main line voltage S-T (S1.2.2) Net Id 34. S-T line voltage, 0.0 to 999.9 V. | UInt16 | V | 0.1 | R |
| 35 | 1 | Main line voltage T-R (S1.2.3) Net Id 35. T-R line voltage, 0.0 to 999.9 V. | UInt16 | V | 0.1 | R |
| 50 | 1 | Thermal class status, of maximum (S4.2.1) Net Id 50. Thermal class status in % of the maximum, 0.0 to 100.0 %. | UInt16 | % | 0.1 | R |
| 60 | 1 | SCR temperature (S4.1.1) Net Id 60. Thyristor (SCR) temperature, -22 to 260 °C, unit 1 °C. | Int16 | °C | 1 | R |
| 63 | 1 | Motor temperature, channel 1 (S4.3.1) Net Id 63. Motor temperature channel 1, -20 to 260 °C, unit 1 °C. | Int16 | °C | 1 | R |
| 64 | 1 | Motor temperature, channel 2 (S4.3.2) Net Id 64. Motor temperature channel 2, -20 to 260 °C, unit 1 °C. | Int16 | °C | 1 | R |
| 65 | 1 | Motor temperature, channel 3 (S4.3.3) Net Id 65. Motor temperature channel 3, -20 to 260 °C, unit 1 °C. | Int16 | °C | 1 | R |
| 66 | 1 | Motor temperature, channel 4 (S4.3.4) Net Id 66. Motor temperature channel 4, -20 to 260 °C, unit 1 °C. | Int16 | °C | 1 | R |
| 67 | 1 | Motor temperature, channel 5 (S4.3.5) Net Id 67. Motor temperature channel 5, -20 to 260 °C, unit 1 °C. | Int16 | °C | 1 | R |
| 68 | 1 | Motor temperature, channel 6 (S4.3.6) Net Id 68. Motor temperature channel 6, -20 to 260 °C, unit 1 °C. | Int16 | °C | 1 | R |
| 232 | 1 | Active command source (S3.1.2) Net Id 232. 0 HMI keys LOC, 1 HMI keys REM, 2 DIx LOC, 3 DIx REM, 4 USB LOC, 5 USB REM, 6 SoftPLC LOC, 7 SoftPLC REM, 8 slot 1 LOC, 9 slot 1 REM, 10 slot 2 LOC, 11 slot 2 REM. | UInt16 | - | 1 | R |
| 294 | 1 | SSW model, current (S3.3.1) Net Id 294. 0 = 10-30 A, 1 = 45-105 A, 2 = 130-200 A, 3 = 255-412 A, 4 = 480-670 A, 5 = 820-950 A, 6 = 1100-1400 A. | UInt16 | - | 1 | R |
| 296 | 1 | SSW model, voltage (S3.3.2) Net Id 296. 0 = 220-575 V, 1 = 380-690 V. | UInt16 | - | 1 | R |
| 297 | 1 | SSW model, control voltage (S3.3.3) Net Id 297. 0 = 110-240 V, 1 = 110-130 V, 2 = 220-240 V, 3 = 24 V. | UInt16 | - | 1 | R |
| 298 | 2 | Serial number (S3.3.4) Net Id 298. Device serial number, 0 to 4294967295, two registers. | UInt32 | - | 1 | R |
| 673 | 1 | Analog output, percent (S2.2.1) Net Id 673. Analog output in %, 0.00 to 100.00 %. | UInt16 | % | 0.01 | R |
| 674 | 1 | Analog output, current (S2.2.2) Net Id 674. Analog output current, 0.000 to 20.000 mA. | UInt16 | mA | 0.001 | R |
| 675 | 1 | Analog output, voltage (S2.2.3) Net Id 675. Analog output voltage, 0.000 to 10.000 V. | UInt16 | V | 0.001 | R |
| 676 | 1 | Analog output, 10 bits (S2.2.4) Net Id 676. Analog output raw value, 0 to 1023. | UInt16 | - | 1 | R |
| 677 | 1 | Digital inputs (S2.1.1) Net Id 677. Bit 0 = DI1, bit 1 = DI2, bit 2 = DI3, bit 3 = DI4, bit 4 = DI5, bit 5 = DI6, bits 6-15 reserved. | Hex | - | 1 | R |
| 678 | 1 | Digital outputs (S2.1.2) Net Id 678. Bit 0 = DO1, bit 1 = DO2, bit 2 = DO3, bits 3-15 reserved. | Hex | - | 1 | R |
| 679 | 1 | Actual status (S3.1.1) Net Id 679. 0 ready, 1 initial test, 2 fault, 3 ramp up, 4 full voltage, 5 bypass, 6 reserved, 7 ramp down, 8 braking, 9 FWD/REV, 10 jog, 11 reserved, 12 re-start delay, 13 general disabled, 14 configuration. | UInt16 | - | 1 | R |
| 680 | 1 | Status word (S3.1.3.1 / S5.1.1) Net Id 680. Bits: 0 running, 1 general enabled, 2 jog, 3 initial test, 4 ramp up, 5 full voltage, 6 bypass, 7 ramp down, 8 remote, 9 braking, 10 FWD/REV, 11 reverse, 12 Ton, 13 Toff, 14 alarm, 15 fault. | Hex | - | 1 | R |
| 681 | 1 | Command word, HMI key (S5.2.2) Net Id 681. Bits: 0 start/stop, 1 general enabled, 2 jog, 3 FWD/REV, 4 LOC/REM, 7 reset, 8-15 reserved. | Hex | - | 1 | RW |
| 683 | 1 | Command word, DIx (S5.2.1) Net Id 683. Bits: 0 start/stop, 1 general enabled, 2 jog, 3 FWD/REV, 4 LOC/REM, 7 reset, 8 brake, 9 emergency start, 10-15 reserved. | Hex | - | 1 | RW |
| 684 | 1 | Command word, SoftPLC (S5.2.4) Net Id 684. Bits: 0 start/stop, 1 general enabled, 2 jog, 3 FWD/REV, 4 LOC/REM, 7 reset, 8-15 reserved. | Hex | - | 1 | RW |
| 685 | 1 | Command word slot 1 (S5.2.5) Net Id 685. Command word written by the communication module in slot 1; same bit layout as the DIx command word. | Hex | - | 1 | RW |
| 686 | 1 | Command word slot 2 (S5.2.6) Net Id 686. Command word written by the communication module in slot 2; same bit layout as the DIx command word. | Hex | - | 1 | RW |
| 692 | 1 | Configuration mode status (S3.1.4.1) Net Id 692. Bits: 0 system initialization, 1 firmware download, 2 oriented start-up, 3 incompatible, 4 reset needed, 5 copy HMI, 6 test mode, 7-15 reserved. | Hex | - | 1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
The SSW900 reaches Modbus RTU through the SSW900-CRS485-W communication module. All parameters are available as 16-bit holding registers and the data addressing uses offset zero, so the parameter network address (Net Id) is the register address; the status word is register 680, the slot 1 and slot 2 command words are 685 and 686. Factory serial settings are C8.2.1 Serial protocol = 2 (Modbus RTU), C8.2.2 Address = 1, C8.2.3 Baud rate = 1 (19200 bit/s) and C8.2.4 Bytes config = 1 (8 bits, even parity, 1 stop bit). Values are integers without a decimal point; the number of decimal places per parameter is listed in the manual's table 10.2 and is applied as the scale factor here. Every 32-bit parameter occupies two consecutive registers and is written by the master word by word; the low word comes first (word_order LowFirst). Registers 1500-1549 are a read area and 1600-1619 a write area for cyclic data, each containing the values of the parameters whose Net Ids are configured in C8.1.1.5-C8.1.1.54 (read) and C8.1.2.6-C8.1.2.25 (write); they are not listed because their content is a configuration choice. Only the status, measurement, I/O and command words used in practice are listed; the motor and protection parameter groups are reachable through their own Net Ids. Source: WEG 'SSW900-CRS485-W Modbus RTU User's Guide', document 10004628707, revision 06, published 10/2024 for software 1.6X - section 7.2 Memory Map (parameter Net Id = register address; the main parameters S3.1.3.1 status word 680 and S5.2.5/S5.2.6 command words 685/686), section C8.2 RS485 Serial (factory settings) and table 10.2 'Characteristics of the parameters for the communication protocol' (Net Ids and decimal places for every parameter); PDF at https://static.weg.net/medias/downloadcenter/h5a/hb1/WEG-manual-modbus-rtu-10004628707-SSW900-en.pdf.