SSW900 soft starter with SSW900-CRS485-W Modbus RTU module Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
Low word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
11
SSW %In (S1.1.6)
Net Id 1. Current in % of the softstarter rated current, 0.0 to 999.9 %, one decimal place.
UInt16%0.1R
21
Motor %In (S1.1.5)
Net Id 2. Current in % of the motor rated current, 0.0 to 999.9 %, one decimal place.
UInt16%0.1R
31
Motor %Vn, main line (S1.2.5)
Net Id 3. Main line voltage in % of the motor rated voltage, 0.0 to 999.9 %.
UInt16%0.1R
41
Main line voltage, average (S1.2.4)
Net Id 4. Average of the three main line voltages, 0.0 to 999.9 V, one decimal place.
UInt16V0.1R
51
SSW %Vn, main line (S1.2.6)
Net Id 5. Main line voltage in % of the softstarter rated voltage, 0.0 to 999.9 %.
UInt16%0.1R
61
Motor %Vn, output voltage (S1.3.2)
Net Id 6. Output voltage in % of the motor rated voltage, 0.0 to 999.9 %.
UInt16%0.1R
71
Output voltage, average (S1.3.1)
Net Id 7. Average output voltage, 0.0 to 999.9 V, one decimal place.
UInt16V0.1R
81
Power factor (S1.5.4)
Net Id 8, an 8-bit value carried in one 16-bit register. Power factor, 0.00 to 1.00, two decimal places.
UInt16-0.01R
91
Motor torque (S1.7.1)
Net Id 9. Motor torque in % of the rated torque, 0.0 to 999.9 %, one decimal place.
UInt16%0.1R
102
Active power (S1.5.1)
Net Id 10. Active power, 32-bit value 0.0 to 11700.0 kW, one decimal place (two registers, low word first on the wire).
UInt32kW0.1R
122
Apparent power (S1.5.2)
Net Id 12. Apparent power, 32-bit value 0.0 to 11700.0 kVA, one decimal place.
UInt32kVA0.1R
142
Reactive power (S1.5.3)
Net Id 14. Reactive power, 32-bit value 0.0 to 11700.0 kVAr, one decimal place.
UInt32kVAr0.1R
171
PLL frequency (S1.6.2)
Net Id 17. Mains frequency measured by the phase-locked loop, 0.0 to 99.9 Hz.
UInt16Hz0.1R
211
SCR blocking voltage R-U (S1.4.1)
Net Id 21. R-U thyristor blocking voltage, 0.0 to 999.9 V.
UInt16V0.1R
221
SCR blocking voltage S-V (S1.4.2)
Net Id 22. S-V thyristor blocking voltage, 0.0 to 999.9 V.
UInt16V0.1R
231
SCR blocking voltage T-W (S1.4.3)
Net Id 23. T-W thyristor blocking voltage, 0.0 to 999.9 V.
UInt16V0.1R
242
Current, average (S1.1.4)
Net Id 24. Current, 32-bit value with one decimal place (0.0 to 14544.0 A), so the two words carry the value times 10.
UInt32A0.1R
262
Current, R phase (S1.1.1)
Net Id 26. Current, 32-bit value with one decimal place (0.0 to 14544.0 A), so the two words carry the value times 10.
UInt32A0.1R
282
Current, S phase (S1.1.2)
Net Id 28. Current, 32-bit value with one decimal place (0.0 to 14544.0 A), so the two words carry the value times 10.
UInt32A0.1R
302
Current, T phase (S1.1.3)
Net Id 30. Current, 32-bit value with one decimal place (0.0 to 14544.0 A), so the two words carry the value times 10.
UInt32A0.1R
331
Main line voltage R-S (S1.2.1)
Net Id 33. R-S line voltage, 0.0 to 999.9 V.
UInt16V0.1R
341
Main line voltage S-T (S1.2.2)
Net Id 34. S-T line voltage, 0.0 to 999.9 V.
UInt16V0.1R
351
Main line voltage T-R (S1.2.3)
Net Id 35. T-R line voltage, 0.0 to 999.9 V.
UInt16V0.1R
501
Thermal class status, of maximum (S4.2.1)
Net Id 50. Thermal class status in % of the maximum, 0.0 to 100.0 %.
UInt16%0.1R
601
SCR temperature (S4.1.1)
Net Id 60. Thyristor (SCR) temperature, -22 to 260 °C, unit 1 °C.
Int16°C1R
631
Motor temperature, channel 1 (S4.3.1)
Net Id 63. Motor temperature channel 1, -20 to 260 °C, unit 1 °C.
Int16°C1R
641
Motor temperature, channel 2 (S4.3.2)
Net Id 64. Motor temperature channel 2, -20 to 260 °C, unit 1 °C.
Int16°C1R
651
Motor temperature, channel 3 (S4.3.3)
Net Id 65. Motor temperature channel 3, -20 to 260 °C, unit 1 °C.
Int16°C1R
661
Motor temperature, channel 4 (S4.3.4)
Net Id 66. Motor temperature channel 4, -20 to 260 °C, unit 1 °C.
Int16°C1R
671
Motor temperature, channel 5 (S4.3.5)
Net Id 67. Motor temperature channel 5, -20 to 260 °C, unit 1 °C.
Int16°C1R
681
Motor temperature, channel 6 (S4.3.6)
Net Id 68. Motor temperature channel 6, -20 to 260 °C, unit 1 °C.
Int16°C1R
2321
Active command source (S3.1.2)
Net Id 232. 0 HMI keys LOC, 1 HMI keys REM, 2 DIx LOC, 3 DIx REM, 4 USB LOC, 5 USB REM, 6 SoftPLC LOC, 7 SoftPLC REM, 8 slot 1 LOC, 9 slot 1 REM, 10 slot 2 LOC, 11 slot 2 REM.
UInt16-1R
2941
SSW model, current (S3.3.1)
Net Id 294. 0 = 10-30 A, 1 = 45-105 A, 2 = 130-200 A, 3 = 255-412 A, 4 = 480-670 A, 5 = 820-950 A, 6 = 1100-1400 A.
UInt16-1R
2961
SSW model, voltage (S3.3.2)
Net Id 296. 0 = 220-575 V, 1 = 380-690 V.
UInt16-1R
2971
SSW model, control voltage (S3.3.3)
Net Id 297. 0 = 110-240 V, 1 = 110-130 V, 2 = 220-240 V, 3 = 24 V.
UInt16-1R
2982
Serial number (S3.3.4)
Net Id 298. Device serial number, 0 to 4294967295, two registers.
UInt32-1R
6731
Analog output, percent (S2.2.1)
Net Id 673. Analog output in %, 0.00 to 100.00 %.
UInt16%0.01R
6741
Analog output, current (S2.2.2)
Net Id 674. Analog output current, 0.000 to 20.000 mA.
UInt16mA0.001R
6751
Analog output, voltage (S2.2.3)
Net Id 675. Analog output voltage, 0.000 to 10.000 V.
UInt16V0.001R
6761
Analog output, 10 bits (S2.2.4)
Net Id 676. Analog output raw value, 0 to 1023.
UInt16-1R
6771
Digital inputs (S2.1.1)
Net Id 677. Bit 0 = DI1, bit 1 = DI2, bit 2 = DI3, bit 3 = DI4, bit 4 = DI5, bit 5 = DI6, bits 6-15 reserved.
Hex-1R
6781
Digital outputs (S2.1.2)
Net Id 678. Bit 0 = DO1, bit 1 = DO2, bit 2 = DO3, bits 3-15 reserved.
Hex-1R
6791
Actual status (S3.1.1)
Net Id 679. 0 ready, 1 initial test, 2 fault, 3 ramp up, 4 full voltage, 5 bypass, 6 reserved, 7 ramp down, 8 braking, 9 FWD/REV, 10 jog, 11 reserved, 12 re-start delay, 13 general disabled, 14 configuration.
UInt16-1R
6801
Status word (S3.1.3.1 / S5.1.1)
Net Id 680. Bits: 0 running, 1 general enabled, 2 jog, 3 initial test, 4 ramp up, 5 full voltage, 6 bypass, 7 ramp down, 8 remote, 9 braking, 10 FWD/REV, 11 reverse, 12 Ton, 13 Toff, 14 alarm, 15 fault.
Hex-1R
6811
Command word, HMI key (S5.2.2)
Net Id 681. Bits: 0 start/stop, 1 general enabled, 2 jog, 3 FWD/REV, 4 LOC/REM, 7 reset, 8-15 reserved.
Hex-1RW
6831
Command word, DIx (S5.2.1)
Net Id 683. Bits: 0 start/stop, 1 general enabled, 2 jog, 3 FWD/REV, 4 LOC/REM, 7 reset, 8 brake, 9 emergency start, 10-15 reserved.
Hex-1RW
6841
Command word, SoftPLC (S5.2.4)
Net Id 684. Bits: 0 start/stop, 1 general enabled, 2 jog, 3 FWD/REV, 4 LOC/REM, 7 reset, 8-15 reserved.
Hex-1RW
6851
Command word slot 1 (S5.2.5)
Net Id 685. Command word written by the communication module in slot 1; same bit layout as the DIx command word.
Hex-1RW
6861
Command word slot 2 (S5.2.6)
Net Id 686. Command word written by the communication module in slot 2; same bit layout as the DIx command word.
Hex-1RW
6921
Configuration mode status (S3.1.4.1)
Net Id 692. Bits: 0 system initialization, 1 firmware download, 2 oriented start-up, 3 incompatible, 4 reset needed, 5 copy HMI, 6 test mode, 7-15 reserved.
Hex-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

The SSW900 reaches Modbus RTU through the SSW900-CRS485-W communication module. All parameters are available as 16-bit holding registers and the data addressing uses offset zero, so the parameter network address (Net Id) is the register address; the status word is register 680, the slot 1 and slot 2 command words are 685 and 686. Factory serial settings are C8.2.1 Serial protocol = 2 (Modbus RTU), C8.2.2 Address = 1, C8.2.3 Baud rate = 1 (19200 bit/s) and C8.2.4 Bytes config = 1 (8 bits, even parity, 1 stop bit). Values are integers without a decimal point; the number of decimal places per parameter is listed in the manual's table 10.2 and is applied as the scale factor here. Every 32-bit parameter occupies two consecutive registers and is written by the master word by word; the low word comes first (word_order LowFirst). Registers 1500-1549 are a read area and 1600-1619 a write area for cyclic data, each containing the values of the parameters whose Net Ids are configured in C8.1.1.5-C8.1.1.54 (read) and C8.1.2.6-C8.1.2.25 (write); they are not listed because their content is a configuration choice. Only the status, measurement, I/O and command words used in practice are listed; the motor and protection parameter groups are reachable through their own Net Ids. Source: WEG 'SSW900-CRS485-W Modbus RTU User's Guide', document 10004628707, revision 06, published 10/2024 for software 1.6X - section 7.2 Memory Map (parameter Net Id = register address; the main parameters S3.1.3.1 status word 680 and S5.2.5/S5.2.6 command words 685/686), section C8.2 RS485 Serial (factory settings) and table 10.2 'Characteristics of the parameters for the communication protocol' (Net Ids and decimal places for every parameter); PDF at https://static.weg.net/medias/downloadcenter/h5a/hb1/WEG-manual-modbus-rtu-10004628707-SSW900-en.pdf.