  "spec_version": 1,
  "slug": "weg-ssw900",
  "manufacturer": "WEG",
  "model": "SSW900 soft starter with SSW900-CRS485-W Modbus RTU module",
  "category": "Soft starter",
  "supplier_url": "https://www.weg.net/catalog/weg/US/en/Automation/Soft-Starters/Soft-Starter-SSW900/c/GLOBAL_WDC_SOFT_STARTER_SSW900",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "LowFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 19200,
      "parity": "Even",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [],
  "holding_registers": [
    {
      "address": 1,
      "count": 1,
      "name": "SSW %In (S1.1.6)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 1. Current in % of the softstarter rated current, 0.0 to 999.9 %, one decimal place."
    },
    {
      "address": 2,
      "count": 1,
      "name": "Motor %In (S1.1.5)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 2. Current in % of the motor rated current, 0.0 to 999.9 %, one decimal place."
    },
    {
      "address": 3,
      "count": 1,
      "name": "Motor %Vn, main line (S1.2.5)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 3. Main line voltage in % of the motor rated voltage, 0.0 to 999.9 %."
    },
    {
      "address": 4,
      "count": 1,
      "name": "Main line voltage, average (S1.2.4)",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 4. Average of the three main line voltages, 0.0 to 999.9 V, one decimal place."
    },
    {
      "address": 5,
      "count": 1,
      "name": "SSW %Vn, main line (S1.2.6)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 5. Main line voltage in % of the softstarter rated voltage, 0.0 to 999.9 %."
    },
    {
      "address": 6,
      "count": 1,
      "name": "Motor %Vn, output voltage (S1.3.2)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 6. Output voltage in % of the motor rated voltage, 0.0 to 999.9 %."
    },
    {
      "address": 7,
      "count": 1,
      "name": "Output voltage, average (S1.3.1)",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 7. Average output voltage, 0.0 to 999.9 V, one decimal place."
    },
    {
      "address": 8,
      "count": 1,
      "name": "Power factor (S1.5.4)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Net Id 8, an 8-bit value carried in one 16-bit register. Power factor, 0.00 to 1.00, two decimal places."
    },
    {
      "address": 9,
      "count": 1,
      "name": "Motor torque (S1.7.1)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 9. Motor torque in % of the rated torque, 0.0 to 999.9 %, one decimal place."
    },
    {
      "address": 10,
      "count": 2,
      "name": "Active power (S1.5.1)",
      "data_type": "UInt32",
      "units": "kW",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 10. Active power, 32-bit value 0.0 to 11700.0 kW, one decimal place (two registers, low word first on the wire)."
    },
    {
      "address": 12,
      "count": 2,
      "name": "Apparent power (S1.5.2)",
      "data_type": "UInt32",
      "units": "kVA",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 12. Apparent power, 32-bit value 0.0 to 11700.0 kVA, one decimal place."
    },
    {
      "address": 14,
      "count": 2,
      "name": "Reactive power (S1.5.3)",
      "data_type": "UInt32",
      "units": "kVAr",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 14. Reactive power, 32-bit value 0.0 to 11700.0 kVAr, one decimal place."
    },
    {
      "address": 17,
      "count": 1,
      "name": "PLL frequency (S1.6.2)",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 17. Mains frequency measured by the phase-locked loop, 0.0 to 99.9 Hz."
    },
    {
      "address": 21,
      "count": 1,
      "name": "SCR blocking voltage R-U (S1.4.1)",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 21. R-U thyristor blocking voltage, 0.0 to 999.9 V."
    },
    {
      "address": 22,
      "count": 1,
      "name": "SCR blocking voltage S-V (S1.4.2)",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 22. S-V thyristor blocking voltage, 0.0 to 999.9 V."
    },
    {
      "address": 23,
      "count": 1,
      "name": "SCR blocking voltage T-W (S1.4.3)",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 23. T-W thyristor blocking voltage, 0.0 to 999.9 V."
    },
    {
      "address": 24,
      "count": 2,
      "name": "Current, average (S1.1.4)",
      "data_type": "UInt32",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 24. Current, 32-bit value with one decimal place (0.0 to 14544.0 A), so the two words carry the value times 10."
    },
    {
      "address": 26,
      "count": 2,
      "name": "Current, R phase (S1.1.1)",
      "data_type": "UInt32",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 26. Current, 32-bit value with one decimal place (0.0 to 14544.0 A), so the two words carry the value times 10."
    },
    {
      "address": 28,
      "count": 2,
      "name": "Current, S phase (S1.1.2)",
      "data_type": "UInt32",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 28. Current, 32-bit value with one decimal place (0.0 to 14544.0 A), so the two words carry the value times 10."
    },
    {
      "address": 30,
      "count": 2,
      "name": "Current, T phase (S1.1.3)",
      "data_type": "UInt32",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 30. Current, 32-bit value with one decimal place (0.0 to 14544.0 A), so the two words carry the value times 10."
    },
    {
      "address": 33,
      "count": 1,
      "name": "Main line voltage R-S (S1.2.1)",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 33. R-S line voltage, 0.0 to 999.9 V."
    },
    {
      "address": 34,
      "count": 1,
      "name": "Main line voltage S-T (S1.2.2)",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 34. S-T line voltage, 0.0 to 999.9 V."
    },
    {
      "address": 35,
      "count": 1,
      "name": "Main line voltage T-R (S1.2.3)",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 35. T-R line voltage, 0.0 to 999.9 V."
    },
    {
      "address": 50,
      "count": 1,
      "name": "Thermal class status, of maximum (S4.2.1)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 50. Thermal class status in % of the maximum, 0.0 to 100.0 %."
    },
    {
      "address": 60,
      "count": 1,
      "name": "SCR temperature (S4.1.1)",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 60. Thyristor (SCR) temperature, -22 to 260 °C, unit 1 °C."
    },
    {
      "address": 63,
      "count": 1,
      "name": "Motor temperature, channel 1 (S4.3.1)",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 63. Motor temperature channel 1, -20 to 260 °C, unit 1 °C."
    },
    {
      "address": 64,
      "count": 1,
      "name": "Motor temperature, channel 2 (S4.3.2)",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 64. Motor temperature channel 2, -20 to 260 °C, unit 1 °C."
    },
    {
      "address": 65,
      "count": 1,
      "name": "Motor temperature, channel 3 (S4.3.3)",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 65. Motor temperature channel 3, -20 to 260 °C, unit 1 °C."
    },
    {
      "address": 66,
      "count": 1,
      "name": "Motor temperature, channel 4 (S4.3.4)",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 66. Motor temperature channel 4, -20 to 260 °C, unit 1 °C."
    },
    {
      "address": 67,
      "count": 1,
      "name": "Motor temperature, channel 5 (S4.3.5)",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 67. Motor temperature channel 5, -20 to 260 °C, unit 1 °C."
    },
    {
      "address": 68,
      "count": 1,
      "name": "Motor temperature, channel 6 (S4.3.6)",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 68. Motor temperature channel 6, -20 to 260 °C, unit 1 °C."
    },
    {
      "address": 232,
      "count": 1,
      "name": "Active command source (S3.1.2)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 232. 0 HMI keys LOC, 1 HMI keys REM, 2 DIx LOC, 3 DIx REM, 4 USB LOC, 5 USB REM, 6 SoftPLC LOC, 7 SoftPLC REM, 8 slot 1 LOC, 9 slot 1 REM, 10 slot 2 LOC, 11 slot 2 REM."
    },
    {
      "address": 294,
      "count": 1,
      "name": "SSW model, current (S3.3.1)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 294. 0 = 10-30 A, 1 = 45-105 A, 2 = 130-200 A, 3 = 255-412 A, 4 = 480-670 A, 5 = 820-950 A, 6 = 1100-1400 A."
    },
    {
      "address": 296,
      "count": 1,
      "name": "SSW model, voltage (S3.3.2)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 296. 0 = 220-575 V, 1 = 380-690 V."
    },
    {
      "address": 297,
      "count": 1,
      "name": "SSW model, control voltage (S3.3.3)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 297. 0 = 110-240 V, 1 = 110-130 V, 2 = 220-240 V, 3 = 24 V."
    },
    {
      "address": 298,
      "count": 2,
      "name": "Serial number (S3.3.4)",
      "data_type": "UInt32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 298. Device serial number, 0 to 4294967295, two registers."
    },
    {
      "address": 673,
      "count": 1,
      "name": "Analog output, percent (S2.2.1)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Net Id 673. Analog output in %, 0.00 to 100.00 %."
    },
    {
      "address": 674,
      "count": 1,
      "name": "Analog output, current (S2.2.2)",
      "data_type": "UInt16",
      "units": "mA",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Net Id 674. Analog output current, 0.000 to 20.000 mA."
    },
    {
      "address": 675,
      "count": 1,
      "name": "Analog output, voltage (S2.2.3)",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Net Id 675. Analog output voltage, 0.000 to 10.000 V."
    },
    {
      "address": 676,
      "count": 1,
      "name": "Analog output, 10 bits (S2.2.4)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 676. Analog output raw value, 0 to 1023."
    },
    {
      "address": 677,
      "count": 1,
      "name": "Digital inputs (S2.1.1)",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 677. Bit 0 = DI1, bit 1 = DI2, bit 2 = DI3, bit 3 = DI4, bit 4 = DI5, bit 5 = DI6, bits 6-15 reserved."
    },
    {
      "address": 678,
      "count": 1,
      "name": "Digital outputs (S2.1.2)",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 678. Bit 0 = DO1, bit 1 = DO2, bit 2 = DO3, bits 3-15 reserved."
    },
    {
      "address": 679,
      "count": 1,
      "name": "Actual status (S3.1.1)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 679. 0 ready, 1 initial test, 2 fault, 3 ramp up, 4 full voltage, 5 bypass, 6 reserved, 7 ramp down, 8 braking, 9 FWD/REV, 10 jog, 11 reserved, 12 re-start delay, 13 general disabled, 14 configuration."
    },
    {
      "address": 680,
      "count": 1,
      "name": "Status word (S3.1.3.1 / S5.1.1)",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 680. Bits: 0 running, 1 general enabled, 2 jog, 3 initial test, 4 ramp up, 5 full voltage, 6 bypass, 7 ramp down, 8 remote, 9 braking, 10 FWD/REV, 11 reverse, 12 Ton, 13 Toff, 14 alarm, 15 fault."
    },
    {
      "address": 681,
      "count": 1,
      "name": "Command word, HMI key (S5.2.2)",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Net Id 681. Bits: 0 start/stop, 1 general enabled, 2 jog, 3 FWD/REV, 4 LOC/REM, 7 reset, 8-15 reserved."
    },
    {
      "address": 683,
      "count": 1,
      "name": "Command word, DIx (S5.2.1)",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Net Id 683. Bits: 0 start/stop, 1 general enabled, 2 jog, 3 FWD/REV, 4 LOC/REM, 7 reset, 8 brake, 9 emergency start, 10-15 reserved."
    },
    {
      "address": 684,
      "count": 1,
      "name": "Command word, SoftPLC (S5.2.4)",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Net Id 684. Bits: 0 start/stop, 1 general enabled, 2 jog, 3 FWD/REV, 4 LOC/REM, 7 reset, 8-15 reserved."
    },
    {
      "address": 685,
      "count": 1,
      "name": "Command word slot 1 (S5.2.5)",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Net Id 685. Command word written by the communication module in slot 1; same bit layout as the DIx command word."
    },
    {
      "address": 686,
      "count": 1,
      "name": "Command word slot 2 (S5.2.6)",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Net Id 686. Command word written by the communication module in slot 2; same bit layout as the DIx command word."
    },
    {
      "address": 692,
      "count": 1,
      "name": "Configuration mode status (S3.1.4.1)",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Net Id 692. Bits: 0 system initialization, 1 firmware download, 2 oriented start-up, 3 incompatible, 4 reset needed, 5 copy HMI, 6 test mode, 7-15 reserved."
    }
  ],
  "combined_registers": [],
  "notes": "The SSW900 reaches Modbus RTU through the SSW900-CRS485-W communication module. All parameters are available as 16-bit holding registers and the data addressing uses offset zero, so the parameter network address (Net Id) is the register address; the status word is register 680, the slot 1 and slot 2 command words are 685 and 686. Factory serial settings are C8.2.1 Serial protocol = 2 (Modbus RTU), C8.2.2 Address = 1, C8.2.3 Baud rate = 1 (19200 bit/s) and C8.2.4 Bytes config = 1 (8 bits, even parity, 1 stop bit). Values are integers without a decimal point; the number of decimal places per parameter is listed in the manual's table 10.2 and is applied as the scale factor here. Every 32-bit parameter occupies two consecutive registers and is written by the master word by word; the low word comes first (word_order LowFirst). Registers 1500-1549 are a read area and 1600-1619 a write area for cyclic data, each containing the values of the parameters whose Net Ids are configured in C8.1.1.5-C8.1.1.54 (read) and C8.1.2.6-C8.1.2.25 (write); they are not listed because their content is a configuration choice. Only the status, measurement, I/O and command words used in practice are listed; the motor and protection parameter groups are reachable through their own Net Ids. Source: WEG 'SSW900-CRS485-W Modbus RTU User's Guide', document 10004628707, revision 06, published 10/2024 for software 1.6X - section 7.2 Memory Map (parameter Net Id = register address; the main parameters S3.1.3.1 status word 680 and S5.2.5/S5.2.6 command words 685/686), section C8.2 RS485 Serial (factory settings) and table 10.2 'Characteristics of the parameters for the communication protocol' (Net Ids and decimal places for every parameter); PDF at https://static.weg.net/medias/downloadcenter/h5a/hb1/WEG-manual-modbus-rtu-10004628707-SSW900-en.pdf."
}