CFW100 frequency inverter Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
11
Speed reference (P001)
P001. Speed reference in the unit and scale defined by P208 (reference scale), P209 (engineering unit) and P210 (decimal places); no fixed factor applies because the unit is a setting. Read-only over Modbus, like every monitor.
UInt16-1R
21
Output speed (motor) (P002)
P002. Speed imposed on the inverter output, at the same scale as P001 (P208/P209/P210), without the output compensations.
UInt16-1R
31
Motor current (P003)
P003. Inverter output current in A rms; parameter range 0.0 to 10.0 A, i.e. one decimal place.
UInt16A0.1R
41
DC link voltage (P004)
P004. DC link direct voltage in V; parameter range 0 to 524 V.
UInt16V1R
51
Output frequency (motor) (P005)
P005. Frequency actually applied to the motor in Hz; parameter range 0.0 to 400.0 Hz, one decimal place.
UInt16Hz0.1R
61
Inverter status (P006)
P006. 0 = ready, 1 = run, 2 = undervoltage, 3 = fault, 4 = self-tuning, 5 = configuration, 6 = DC braking, 7 = reserved, 8 = fire mode.
UInt16-1R
71
Output voltage (P007)
P007. Line voltage at the inverter output in V; parameter range 0 to 240 V.
UInt16V1R
91
Motor torque (P009)
P009. Torque developed by the motor in % of the rated torque; parameter range -200.0 to 200.0 %, one decimal place.
Int16%0.1R
111
Power factor (P011)
P011. Power factor, the relation between real and total power absorbed by the motor; parameter range 0.00 to 1.00.
UInt16-0.01R
121
DI8 to DI1 status (P012)
P012. Digital input status, bit 0 = DI1 through bit 7 = DI8; the activation level depends on P271 for each DIx.
Hex-1R
131
DO3 to DO1 status (P013)
P013. Digital output status, bit 0 = DO1, bit 1 = DO2, bit 2 = DO3.
Hex-1R
181
AI1 value (P018)
P018. Analog input AI1 in % of full scale after the offset action and gain (P230 to P245); parameter range -100.0 to 100.0 %.
Int16%0.1R
1001
Acceleration time (P100)
P100. Acceleration ramp time of the active ramp; parameter range 0.1 to 999.9 s, factory 5.0 s.
UInt16s0.1RW
1011
Deceleration time (P101)
P101. Deceleration ramp time of the active ramp; parameter range 0.1 to 999.9 s, factory 5.0 s.
UInt16s0.1RW
6801
Logical status (P680)
P680. Status word, bits: 1 run command, 2 fire mode, 5 second ramp, 6 configuration status, 7 alarm, 8 running, 9 enabled, 10 forward, 11 JOG, 12 remote, 13 undervoltage, 15 fault.
UInt16-1R
6811
13-bit speed (P681)
P681. 13-bit speed with signal: 0 = 0 and 8192 (2000h) = the motor rated frequency P403, maximum 32767 = four times P403, so raw / 8192 is the fraction of P403 and the percentage shown is that fraction times 100. Negative values mean reverse. Read-only.
UInt16% of rated frequencyx / 8192 * 100R
6821
Serial/USB control word (P682)
P682. Serial interface control word; only writable over the serial interface. Bits: 0 run/stop, 1 general enable, 2 speed direction, 3 JOG, 4 LOC/REM, 5 second ramp, 7 fault reset. The drive must be programmed to be controlled via serial (P105 and P220 to P228).
UInt16-1RW
6831
Serial speed reference (P683)
P683. Serial speed reference in the same 13-bit scale as P681: 8192 (2000h) = rated frequency P403, so raw / 8192 is the fraction of P403 and the percentage shown is that fraction times 100. Negative values reverse the direction together with P682 bit 2.
Int16% of rated frequencyx / 8192 * 100RW
3081
Serial address (P308)
P308. Modbus RTU slave address, range 1 to 247, factory 1.
UInt16-1RW
3101
Serial baud rate (P310)
P310. 0 = 9600, 1 = 19200, 2 = 38400, 3 = 57600, 4 = 76800 bits/s; factory 1 (19200).
UInt16-1RW
3111
Serial bytes configuration (P311)
P311. 0 = 8 bits no parity 1 stop, 1 = 8 bits even parity 1 stop, 2 = 8 bits odd parity 1 stop, 3 = 8 bits no parity 2 stop, 4 = 8 bits even parity 2 stop, 5 = 8 bits odd parity 2 stop; factory 1.
UInt16-1RW
3121
Serial protocol (P312)
P312. 2 = Modbus RTU slave, 3 = BACnet, 5 = Modbus RTU master; factory 2.
UInt16-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

All CFW100 parameters are available as 16-bit holding registers and the data addressing uses offset zero, so the parameter number is the register address (P683 is address 683 = 02ABh). Factory serial settings are P308 = 1, P310 = 1 (19200 bit/s), P311 = 1 (8 bits, even parity, 1 stop bit) and P312 = 2 (Modbus RTU slave). To control the drive over the serial line, program P105 and P220 to P228 for the serial command and reference sources; P682 and P683 are only writable through the serial interface. Read-only parameters (P001 to P018, P680, P681) cannot be written. Sources: WEG 'CFW100 Modbus RTU User's Manual', document 10002909455/01 - section 5.2 Memory Map (parameter number equals register address), section 6 (function codes 03/04/06/16) and the P682/P683 control word and speed reference descriptions; PDF at https://static.weg.net/medias/downloadcenter/h77/hf0/WEG-cfw100-modbus-rtu-manual-10002909455-manual-english.pdf. Parameter ranges, scales and factory settings are from the WEG 'CFW100 Programming Manual', document 10008008405, chapter 0 Quick Reference of Parameters, chapter 11 READ parameters and section 12.2 SERIAL (P308 to P312); PDF at https://static.weg.net/medias/downloadcenter/ha6/he3/WEG-CFW100-programming-manual-10008008405-en.pdf.