  "spec_version": 1,
  "slug": "weg-cfw100",
  "manufacturer": "WEG",
  "model": "CFW100 frequency inverter",
  "category": "VFD",
  "supplier_url": "https://www.weg.net/catalog/weg/US/en/Drives/Variable-Speed-Drives/OEM-and-General-Purpose-Drives/Frequency-Inverter-CFW100/c/GLOBAL_WDC_INVERTER_CFW100",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 19200,
      "parity": "Even",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [],
  "holding_registers": [
    {
      "address": 1,
      "count": 1,
      "name": "Speed reference (P001)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "P001. Speed reference in the unit and scale defined by P208 (reference scale), P209 (engineering unit) and P210 (decimal places); no fixed factor applies because the unit is a setting. Read-only over Modbus, like every monitor."
    },
    {
      "address": 2,
      "count": 1,
      "name": "Output speed (motor) (P002)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "P002. Speed imposed on the inverter output, at the same scale as P001 (P208/P209/P210), without the output compensations."
    },
    {
      "address": 3,
      "count": 1,
      "name": "Motor current (P003)",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "P003. Inverter output current in A rms; parameter range 0.0 to 10.0 A, i.e. one decimal place."
    },
    {
      "address": 4,
      "count": 1,
      "name": "DC link voltage (P004)",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "P004. DC link direct voltage in V; parameter range 0 to 524 V."
    },
    {
      "address": 5,
      "count": 1,
      "name": "Output frequency (motor) (P005)",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "P005. Frequency actually applied to the motor in Hz; parameter range 0.0 to 400.0 Hz, one decimal place."
    },
    {
      "address": 6,
      "count": 1,
      "name": "Inverter status (P006)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "P006. 0 = ready, 1 = run, 2 = undervoltage, 3 = fault, 4 = self-tuning, 5 = configuration, 6 = DC braking, 7 = reserved, 8 = fire mode."
    },
    {
      "address": 7,
      "count": 1,
      "name": "Output voltage (P007)",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "P007. Line voltage at the inverter output in V; parameter range 0 to 240 V."
    },
    {
      "address": 9,
      "count": 1,
      "name": "Motor torque (P009)",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "P009. Torque developed by the motor in % of the rated torque; parameter range -200.0 to 200.0 %, one decimal place."
    },
    {
      "address": 11,
      "count": 1,
      "name": "Power factor (P011)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "P011. Power factor, the relation between real and total power absorbed by the motor; parameter range 0.00 to 1.00."
    },
    {
      "address": 12,
      "count": 1,
      "name": "DI8 to DI1 status (P012)",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "P012. Digital input status, bit 0 = DI1 through bit 7 = DI8; the activation level depends on P271 for each DIx."
    },
    {
      "address": 13,
      "count": 1,
      "name": "DO3 to DO1 status (P013)",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "P013. Digital output status, bit 0 = DO1, bit 1 = DO2, bit 2 = DO3."
    },
    {
      "address": 18,
      "count": 1,
      "name": "AI1 value (P018)",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "P018. Analog input AI1 in % of full scale after the offset action and gain (P230 to P245); parameter range -100.0 to 100.0 %."
    },
    {
      "address": 100,
      "count": 1,
      "name": "Acceleration time (P100)",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "P100. Acceleration ramp time of the active ramp; parameter range 0.1 to 999.9 s, factory 5.0 s."
    },
    {
      "address": 101,
      "count": 1,
      "name": "Deceleration time (P101)",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "P101. Deceleration ramp time of the active ramp; parameter range 0.1 to 999.9 s, factory 5.0 s."
    },
    {
      "address": 680,
      "count": 1,
      "name": "Logical status (P680)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "P680. Status word, bits: 1 run command, 2 fire mode, 5 second ramp, 6 configuration status, 7 alarm, 8 running, 9 enabled, 10 forward, 11 JOG, 12 remote, 13 undervoltage, 15 fault."
    },
    {
      "address": 681,
      "count": 1,
      "name": "13-bit speed (P681)",
      "data_type": "UInt16",
      "units": "% of rated frequency",
      "scale_factor": 1,
      "offset": 0,
      "formula": "x / 8192 * 100",
      "access": "R",
      "description": "P681. 13-bit speed with signal: 0 = 0 and 8192 (2000h) = the motor rated frequency P403, maximum 32767 = four times P403, so raw / 8192 is the fraction of P403 and the percentage shown is that fraction times 100. Negative values mean reverse. Read-only."
    },
    {
      "address": 682,
      "count": 1,
      "name": "Serial/USB control word (P682)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "P682. Serial interface control word; only writable over the serial interface. Bits: 0 run/stop, 1 general enable, 2 speed direction, 3 JOG, 4 LOC/REM, 5 second ramp, 7 fault reset. The drive must be programmed to be controlled via serial (P105 and P220 to P228)."
    },
    {
      "address": 683,
      "count": 1,
      "name": "Serial speed reference (P683)",
      "data_type": "Int16",
      "units": "% of rated frequency",
      "scale_factor": 1,
      "offset": 0,
      "formula": "x / 8192 * 100",
      "access": "RW",
      "description": "P683. Serial speed reference in the same 13-bit scale as P681: 8192 (2000h) = rated frequency P403, so raw / 8192 is the fraction of P403 and the percentage shown is that fraction times 100. Negative values reverse the direction together with P682 bit 2."
    },
    {
      "address": 308,
      "count": 1,
      "name": "Serial address (P308)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "P308. Modbus RTU slave address, range 1 to 247, factory 1."
    },
    {
      "address": 310,
      "count": 1,
      "name": "Serial baud rate (P310)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "P310. 0 = 9600, 1 = 19200, 2 = 38400, 3 = 57600, 4 = 76800 bits/s; factory 1 (19200)."
    },
    {
      "address": 311,
      "count": 1,
      "name": "Serial bytes configuration (P311)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "P311. 0 = 8 bits no parity 1 stop, 1 = 8 bits even parity 1 stop, 2 = 8 bits odd parity 1 stop, 3 = 8 bits no parity 2 stop, 4 = 8 bits even parity 2 stop, 5 = 8 bits odd parity 2 stop; factory 1."
    },
    {
      "address": 312,
      "count": 1,
      "name": "Serial protocol (P312)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "P312. 2 = Modbus RTU slave, 3 = BACnet, 5 = Modbus RTU master; factory 2."
    }
  ],
  "combined_registers": [],
  "notes": "All CFW100 parameters are available as 16-bit holding registers and the data addressing uses offset zero, so the parameter number is the register address (P683 is address 683 = 02ABh). Factory serial settings are P308 = 1, P310 = 1 (19200 bit/s), P311 = 1 (8 bits, even parity, 1 stop bit) and P312 = 2 (Modbus RTU slave). To control the drive over the serial line, program P105 and P220 to P228 for the serial command and reference sources; P682 and P683 are only writable through the serial interface. Read-only parameters (P001 to P018, P680, P681) cannot be written. Sources: WEG 'CFW100 Modbus RTU User's Manual', document 10002909455/01 - section 5.2 Memory Map (parameter number equals register address), section 6 (function codes 03/04/06/16) and the P682/P683 control word and speed reference descriptions; PDF at https://static.weg.net/medias/downloadcenter/h77/hf0/WEG-cfw100-modbus-rtu-manual-10002909455-manual-english.pdf. Parameter ranges, scales and factory settings are from the WEG 'CFW100 Programming Manual', document 10008008405, chapter 0 Quick Reference of Parameters, chapter 11 READ parameters and section 12.2 SERIAL (P308 to P312); PDF at https://static.weg.net/medias/downloadcenter/ha6/he3/WEG-CFW100-programming-manual-10008008405-en.pdf."
}