All devices

Studer Innotec · Inverter/charger

Studer Next3 converter (with solar inputs 1 and 2) as seen through the Next gateway's Modbus server Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
14
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
51002
Converter status
Enum; the document's enum 1 lists the values (NoWarningsOrErrors, warnings, errors).
UInt32-1R
51022
Converter error bits
Bitfield; the document's enum 0 lists the bits and says which of them clear by themselves.
UInt32-1R
51042
Fan 1 speed
Float32RPM1R
51062
Fan 2 speed
Float32RPM1R
51082
Fan 3 speed
Float32RPM1R
51102
Fan 4 speed
Float32RPM1R
51122
Fan 5 speed
Float32RPM1R
51142
External power supply current
Float32A1R
51162
Power supply voltage
Float32V1R
51562
ADC noise warning channels
Bitfield of ADC channels whose noise exceeds the document's threshold; enum 2 lists the channels.
UInt32-1R
51582
ADC noise error channels
Bitfield of the ADC channels whose noise exceeds the document's error threshold (id 33); enum 2 lists the channels. A separate register from the warning channels at 5156.
UInt32-1R
51622
Noise of the selected ADC channel
Noise of the ADC channel chosen by the 'ADC channel selection' property (id 30), in per mille as printed.
Float32‰1R
69002
Solar input 1 voltage
Float32V1R
69022
Solar input 1 current
Float32A1R
69042
Solar input 1 sunshine today
The document prints the unit s and no scale factor.
UInt32s1R
69062
Solar input 1 sunshine previous day
UInt32s1R
69082
Solar input 1 status
Enum; the document's enum 0 lists the states.
UInt32-1R
69102
Solar input 1 cause of error
Bitfield; the document prints that it is cleared once the converter restarts.
UInt32-1R
69122
Solar input 1 errors
Bitfield; enum 1 lists the bits.
UInt32-1R
69142
Solar input 1 warnings
Bitfield; enum 2 lists the bits.
UInt32-1R
69162
Solar input 1 depolarization state
Enum 3.
UInt32-1R
69182
Solar input 1 limitation state
Enum 4.
UInt32-1R
72002
Solar input 2 voltage
Float32V1R
72022
Solar input 2 current
Float32A1R
72042
Solar input 2 sunshine today
The document prints the unit s and no scale factor.
UInt32s1R
72062
Solar input 2 sunshine previous day
UInt32s1R
72082
Solar input 2 status
Enum; the document's enum 0 lists the states.
UInt32-1R
72102
Solar input 2 cause of error
Bitfield; the document prints that it is cleared once the converter restarts.
UInt32-1R
72122
Solar input 2 errors
Bitfield; enum 1 lists the bits.
UInt32-1R
72142
Solar input 2 warnings
Bitfield; enum 2 lists the bits.
UInt32-1R
72162
Solar input 2 depolarization state
Enum 3.
UInt32-1R
72182
Solar input 2 limitation state
Enum 4.
UInt32-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Studer Innotec "Studer Modbus Addresses", its generated catalogue of the Modbus object model, at technext3.studer-innotec.com/web/content/208609 (read 2026-11-23, SHA-256 e782a79238180a17d5f87eaa7ac71890ace0232d016bdf741ebf473b295f3cda; Object Model 10.73, 2023-07-19). It covers the NEXT platform only (Next1, Next3, NextGateway) and names neither Xtender nor VarioTrack. SCOPE: the Next3 converter object (10.x.17) and its two solar objects (10.x.23, 10.x.24), one unit ID. ADDRESSES ARE MODBUS ADDRESSES: its section on the external-ID/Modbus-address correspondence says the Address column is the register, the group being chosen by the unit ID and the instance by the address in the group's range. Next3 device addresses print as 14 to 28, so 14, the first, is a placeholder; the numbers recur in other groups (5100 is also a System-group measurement at unit 1). TRANSPORT: the NextGateway 'Modbus server' object (20.x.15) prints 4202 'Modbus TCP port', default 502, range 0-65535, and 4218 'Modbus mode' with 0 Off, 1 RTU, 2 TCP, so the seed is Modbus TCP at 502 and the gateway must be in TCP mode. CAVEAT: property 4200 'Base address' (range 0-135, default 0) shifts the addresses if another base is set. WORD ORDER: none printed; HighFirst is the schema default, not cited. TYPES: Float32 where the catalogue prints float (no scale factor printed, so the float is the value), and enum and bitfield rows as two-register UInt32 per the size column, with enum tables cited by number. Left out: integer rows whose unit could hide a scale factor, wrapped labels, the signal and write rows (on, off, depolarization enable, ADC channel selection at 5160), the aux relay, command-input and battery-contributor objects, and the Next1 and NextGateway groups. Parsing: the PDF has no table borders and its header cells render doubled (UUsseerr); every row came from a line whose address, size, type and R/W cells agreed. No hardware validation is claimed.