All devices

Victron Energy · Inverter/charger

Multi RS Solar 48/6000 inverter/charger with two MPPT trackers (multi service on a GX device) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
45001
Input voltage phase 1
UInt16V AC0.1R
45011
Input voltage phase 2
UInt16V AC0.1R
45021
Input voltage phase 3
UInt16V AC0.1R
45031
Input current phase 1
Int16A AC0.1R
45041
Input current phase 2
Int16A AC0.1R
45051
Input current phase 3
Int16A AC0.1R
45061
Input power phase 1
Int16W10R
45071
Input power phase 2
Int16W10R
45081
Input power phase 3
Int16W10R
45091
Input frequency
UInt16Hz0.01R
45101
Output voltage phase 1
UInt16V AC0.1R
45111
Output voltage phase 2
UInt16V AC0.1R
45121
Output voltage phase 3
UInt16V AC0.1R
45131
Output current phase 1
Int16A AC0.1R
45141
Output current phase 2
Int16A AC0.1R
45151
Output current phase 3
Int16A AC0.1R
45161
Output power phase 1
Int16W10R
45171
Output power phase 2
Int16W10R
45181
Output power phase 3
Int16W10R
45191
Output frequency
UInt16Hz0.01R
45201
AC input 1 source type
0=Unused;1=Grid;2=Genset;3=Shore
UInt16-1R
45211
AC input 2 source type
0=Unused;1=Grid;2=Genset;3=Shore
UInt16-1R
45221
Ac input 1 current limit
UInt16A0.1RW
45231
Ac input 2 current limit
UInt16A0.1RW
45241
Phase count
UInt16-1R
45251
Active AC input
0=AC Input 1;1=AC Input 2;240=Disconnected
UInt16-1R
45261
Battery voltage
UInt16V DC0.01R
45271
Battery current
Int16A DC0.1R
45281
Battery temperature
Int16°C0.1R
45291
Battery State of Charge
UInt16%0.1R
45301
Inverter/Charger state
0=Off;1=Low Power;2=Fault;3=Bulk;4=Absorption;5=Float;6=Storage;7=Equalize;8=Passthru;9=Inverting;10=Power assist;11=Power supply;252=External control
UInt16-1R
45311
Switch position
1=Charger Only;2=Inverter Only;3=On;4=Off
UInt16-1RW
45321
Temperature alarm
0=Ok;1=Warning;2=Alarm
UInt16-1R
45331
High voltage alarm
0=Ok;1=Warning;2=Alarm
UInt16-1R
45341
High AC-Out voltage alarm
0=Ok;1=Warning;2=Alarm
UInt16-1R
45351
Low battery temperature alarm
0=Ok;1=Warning;2=Alarm
UInt16-1R
45361
Low voltage alarm
0=Ok;1=Warning;2=Alarm
UInt16-1R
45371
Low AC-Out voltage alarm
0=Ok;1=Warning;2=Alarm
UInt16-1R
45381
Overload alarm
0=Ok;1=Warning;2=Alarm
UInt16-1R
45391
High DC ripple alarm
0=Ok;1=Warning;2=Alarm
UInt16-1R
45401
PV power
UInt16W1R
45411
User yield
UInt16kWh0.1R
45421
Relay on the Multi RS
0=Open;1=Closed
UInt16-1R
45431
MPP operation mode
0=Off;1=Voltage/current limited;2=MPPT active;255=Not available
UInt16-1R
45441
PV voltage
UInt16V DC0.1R
45451
Error code
0=No error;1=Battery temperature too high;2=Battery voltage too high;3=Battery temperature sensor miswired (+);4=Battery temperature sensor miswired (-);5=Battery temperature sensor disconnected;6=Battery voltage sense miswired (+);7=Battery voltage sense miswired (-);8=Battery voltage sense disconnected;9=Battery voltage wire losses too high;17=Charger temperature too high;18=Charger over-current;19=Charger current polarity reversed;20=Bulk time limit reached;22=Charger temperature sensor miswired;23=Charger temperature sensor disconnected;34=Input current too high
UInt16-1R
45462
Energy from AC-in-1 to AC-out
UInt32kWh0.01R
45482
Energy from AC-in-1 to battery
UInt32kWh0.01R
45502
Energy from AC-in-2 to AC-out
UInt32kWh0.01R
45522
Energy from AC-in-2 to battery
UInt32kWh0.01R
45542
Energy from AC-out to AC-in-1
UInt32kWh0.01R
45562
Energy from AC-out to AC-in-2
UInt32kWh0.01R
45582
Energy from battery to AC-in-1
UInt32kWh0.01R
45602
Energy from battery to AC-in-2
UInt32kWh0.01R
45622
Energy from battery to AC-out
UInt32kWh0.01R
45642
Energy from AC-out to battery
UInt32kWh0.01R
45662
Energy from solar to AC-in-1
UInt32kWh0.01R
45682
Energy from solar to AC-in-2
UInt32kWh0.01R
45702
Energy from solar to AC-out
UInt32kWh0.01R
45722
Energy from solar to battery
UInt32kWh0.01R
45741
Yield today
UInt16kWh0.1R
45751
Maximum charge power today
UInt16W1R
45761
Yield yesterday
UInt16kWh0.1R
45771
Maximum charge power yesterday
UInt16W1R
45781
Yield today for tracker 0
UInt16kWh0.1R
45791
Yield today for tracker 1
UInt16kWh0.1R
45801
Yield today for tracker 2
UInt16kWh0.1R
45811
Yield today for tracker 3
UInt16kWh0.1R
45821
Yield yesterday for tracker 0
UInt16kWh0.1R
45831
Yield yesterday for tracker 1
UInt16kWh0.1R
45841
Yield yesterday for tracker 2
UInt16kWh0.1R
45851
Yield yesterday for tracker 3
UInt16kWh0.1R
45861
Maximum charge power today for tracker 0
UInt16W1R
45871
Maximum charge power today for tracker 1
UInt16W1R
45881
Maximum charge power today for tracker 2
UInt16W1R
45891
Maximum charge power today for tracker 3
UInt16W1R
45901
Maximum charge power yesterday tracker 0
UInt16W1R
45911
Maximum charge power yesterday tracker 1
UInt16W1R
45921
Maximum charge power yesterday tracker 2
UInt16W1R
45931
Maximum charge power yesterday tracker 3
UInt16W1R
45941
PV voltage for tracker 0
UInt16V DC0.1R
45951
PV voltage for tracker 1
UInt16V DC0.1R
45961
PV voltage for tracker 2
UInt16V DC0.1R
45971
PV voltage for tracker 3
UInt16V DC0.1R
45981
PV power for tracker 0
UInt16W1R
45991
PV power for tracker 1
UInt16W1R
46001
PV power for tracker 2
UInt16W1R
46011
PV power for tracker 3
UInt16W1R
46021
Low SOC alarm
0=No alarm;1=Warning;2=Alarm
UInt16-1R
46032
User yield
Energy generated by the solarcharger since last user reset
UInt32kWh1R
46051
MPP operation mode tracker 1
0=Off;1=Voltage/current limited;2=MPPT active;255=Not available
UInt16-1R
46061
MPP operation mode tracker 2
0=Off;1=Voltage/current limited;2=MPPT active;255=Not available
UInt16-1R
46071
MPP operation mode tracker 3
0=Off;1=Voltage/current limited;2=MPPT active;255=Not available
UInt16-1R
46081
MPP operation mode tracker 4
0=Off;1=Voltage/current limited;2=MPPT active;255=Not available
UInt16-1R
46091
ESS mode
0=self-consumption (battery-life);1=self-consumption;2=Keep charged;3=External control
UInt16-1RW
46102
ESS power setpoint
Int32W1RW
46121
Disable Feed-in
0=Feed-in enabled;1=Feed-in disabled
UInt16-1RW
46131
Disable charge
0=Charge enabled;1=Charge disabled
UInt16-1RW
46141
ESS Minimum SOC Limit
UInt16%1RW
46151
Sustain active
0=Sustain inactive; 1=Sustain active
UInt16-1R
46201
Short Circuit Alarm
0=Ok;1=Warning;2=Alarm
UInt16-1R
46228
Custom Name
String[8]: 8 registers, 16 characters. The list prints string[6] as "12 characters", string[7] as "Max 14 characters" and string[16] as "32 characters", so string[n] is n registers of two characters each.
Ascii-1RW
46301
Tracker 1 enabled
0=Disabled;1=Enabled
UInt16-1R
46311
Tracker 2 enabled
0=Disabled;1=Enabled
UInt16-1R
46321
Tracker 3 enabled
0=Disabled;1=Enabled
UInt16-1R
46331
Tracker 4 enabled
0=Disabled;1=Enabled
UInt16-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

The Multi RS Solar is an inverter/charger with two integrated MPPT trackers and its own Modbus service: these are the com.victronenergy.multi registers of the Modbus TCP server that the GX device (Cerbo GX, Ekrano GX) runs, and they are a different map from the VE.Bus MultiPlus/Quattro block (victron-multiplus-quattro-vebus) — the two services share no address. Addresses are the decimal addresses of Victron's CCGX Modbus TCP register list (version 3.81, the vendor-hosted workbook linked on the supplier page), used unchanged as wire addresses, and the list's 'Scalefactor' column is a divisor, so the factors here are the equivalent multipliers. The unit ID is a declared placeholder: the register list's Unit ID mapping sheet has no preferred ID for this service (its rows cover the system, VE.Bus, VE.Direct and CAN-bus services), and the sheet's own note says a service's unit ID normally equals its device instance and is assigned dynamically since Venus OS 2.60, so read it from Settings > Integrations > Modbus TCP server > Available services on the GX device. Left out: the RESERVED rows 4616-4619 and 4621. The Custom Name at 4622 is a String[8], which the list's own ranges (string[6] = 12 characters, string[16] = 32 characters) make eight registers of two characters each; it spans 4622-4629 and 4630 follows it. The list numbers the tracker blocks 'tracker 0'-'tracker 3' for yields and PV readings but the MPP-mode rows 'tracker 1'-'tracker 4' over the same /Pv/0.../Pv/3 paths; the rows here keep the list's own labels. The list prints no byte or word order for its 32-bit values, so HighFirst is the Modbus convention, as in the library's other Victron seeds; if a two-register reading looks word-swapped, switch the device to LowFirst. Source: Victron Energy 'CCGX-Modbus-TCP-register-list-3.81.xlsx' — version 3.81, whose 'Document versions' sheet ends at Rev 54 — on victronenergy.com.