Victron Energy · Inverter/charger
Multi RS Solar 48/6000 inverter/charger with two MPPT trackers (multi service on a GX device) Modbus register map
Default configuration
- Protocol
- Modbus TCP
- Port
- 502
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 4500 | 1 | Input voltage phase 1 | UInt16 | V AC | 0.1 | R |
| 4501 | 1 | Input voltage phase 2 | UInt16 | V AC | 0.1 | R |
| 4502 | 1 | Input voltage phase 3 | UInt16 | V AC | 0.1 | R |
| 4503 | 1 | Input current phase 1 | Int16 | A AC | 0.1 | R |
| 4504 | 1 | Input current phase 2 | Int16 | A AC | 0.1 | R |
| 4505 | 1 | Input current phase 3 | Int16 | A AC | 0.1 | R |
| 4506 | 1 | Input power phase 1 | Int16 | W | 10 | R |
| 4507 | 1 | Input power phase 2 | Int16 | W | 10 | R |
| 4508 | 1 | Input power phase 3 | Int16 | W | 10 | R |
| 4509 | 1 | Input frequency | UInt16 | Hz | 0.01 | R |
| 4510 | 1 | Output voltage phase 1 | UInt16 | V AC | 0.1 | R |
| 4511 | 1 | Output voltage phase 2 | UInt16 | V AC | 0.1 | R |
| 4512 | 1 | Output voltage phase 3 | UInt16 | V AC | 0.1 | R |
| 4513 | 1 | Output current phase 1 | Int16 | A AC | 0.1 | R |
| 4514 | 1 | Output current phase 2 | Int16 | A AC | 0.1 | R |
| 4515 | 1 | Output current phase 3 | Int16 | A AC | 0.1 | R |
| 4516 | 1 | Output power phase 1 | Int16 | W | 10 | R |
| 4517 | 1 | Output power phase 2 | Int16 | W | 10 | R |
| 4518 | 1 | Output power phase 3 | Int16 | W | 10 | R |
| 4519 | 1 | Output frequency | UInt16 | Hz | 0.01 | R |
| 4520 | 1 | AC input 1 source type 0=Unused;1=Grid;2=Genset;3=Shore | UInt16 | - | 1 | R |
| 4521 | 1 | AC input 2 source type 0=Unused;1=Grid;2=Genset;3=Shore | UInt16 | - | 1 | R |
| 4522 | 1 | Ac input 1 current limit | UInt16 | A | 0.1 | RW |
| 4523 | 1 | Ac input 2 current limit | UInt16 | A | 0.1 | RW |
| 4524 | 1 | Phase count | UInt16 | - | 1 | R |
| 4525 | 1 | Active AC input 0=AC Input 1;1=AC Input 2;240=Disconnected | UInt16 | - | 1 | R |
| 4526 | 1 | Battery voltage | UInt16 | V DC | 0.01 | R |
| 4527 | 1 | Battery current | Int16 | A DC | 0.1 | R |
| 4528 | 1 | Battery temperature | Int16 | °C | 0.1 | R |
| 4529 | 1 | Battery State of Charge | UInt16 | % | 0.1 | R |
| 4530 | 1 | Inverter/Charger state 0=Off;1=Low Power;2=Fault;3=Bulk;4=Absorption;5=Float;6=Storage;7=Equalize;8=Passthru;9=Inverting;10=Power assist;11=Power supply;252=External control | UInt16 | - | 1 | R |
| 4531 | 1 | Switch position 1=Charger Only;2=Inverter Only;3=On;4=Off | UInt16 | - | 1 | RW |
| 4532 | 1 | Temperature alarm 0=Ok;1=Warning;2=Alarm | UInt16 | - | 1 | R |
| 4533 | 1 | High voltage alarm 0=Ok;1=Warning;2=Alarm | UInt16 | - | 1 | R |
| 4534 | 1 | High AC-Out voltage alarm 0=Ok;1=Warning;2=Alarm | UInt16 | - | 1 | R |
| 4535 | 1 | Low battery temperature alarm 0=Ok;1=Warning;2=Alarm | UInt16 | - | 1 | R |
| 4536 | 1 | Low voltage alarm 0=Ok;1=Warning;2=Alarm | UInt16 | - | 1 | R |
| 4537 | 1 | Low AC-Out voltage alarm 0=Ok;1=Warning;2=Alarm | UInt16 | - | 1 | R |
| 4538 | 1 | Overload alarm 0=Ok;1=Warning;2=Alarm | UInt16 | - | 1 | R |
| 4539 | 1 | High DC ripple alarm 0=Ok;1=Warning;2=Alarm | UInt16 | - | 1 | R |
| 4540 | 1 | PV power | UInt16 | W | 1 | R |
| 4541 | 1 | User yield | UInt16 | kWh | 0.1 | R |
| 4542 | 1 | Relay on the Multi RS 0=Open;1=Closed | UInt16 | - | 1 | R |
| 4543 | 1 | MPP operation mode 0=Off;1=Voltage/current limited;2=MPPT active;255=Not available | UInt16 | - | 1 | R |
| 4544 | 1 | PV voltage | UInt16 | V DC | 0.1 | R |
| 4545 | 1 | Error code 0=No error;1=Battery temperature too high;2=Battery voltage too high;3=Battery temperature sensor miswired (+);4=Battery temperature sensor miswired (-);5=Battery temperature sensor disconnected;6=Battery voltage sense miswired (+);7=Battery voltage sense miswired (-);8=Battery voltage sense disconnected;9=Battery voltage wire losses too high;17=Charger temperature too high;18=Charger over-current;19=Charger current polarity reversed;20=Bulk time limit reached;22=Charger temperature sensor miswired;23=Charger temperature sensor disconnected;34=Input current too high | UInt16 | - | 1 | R |
| 4546 | 2 | Energy from AC-in-1 to AC-out | UInt32 | kWh | 0.01 | R |
| 4548 | 2 | Energy from AC-in-1 to battery | UInt32 | kWh | 0.01 | R |
| 4550 | 2 | Energy from AC-in-2 to AC-out | UInt32 | kWh | 0.01 | R |
| 4552 | 2 | Energy from AC-in-2 to battery | UInt32 | kWh | 0.01 | R |
| 4554 | 2 | Energy from AC-out to AC-in-1 | UInt32 | kWh | 0.01 | R |
| 4556 | 2 | Energy from AC-out to AC-in-2 | UInt32 | kWh | 0.01 | R |
| 4558 | 2 | Energy from battery to AC-in-1 | UInt32 | kWh | 0.01 | R |
| 4560 | 2 | Energy from battery to AC-in-2 | UInt32 | kWh | 0.01 | R |
| 4562 | 2 | Energy from battery to AC-out | UInt32 | kWh | 0.01 | R |
| 4564 | 2 | Energy from AC-out to battery | UInt32 | kWh | 0.01 | R |
| 4566 | 2 | Energy from solar to AC-in-1 | UInt32 | kWh | 0.01 | R |
| 4568 | 2 | Energy from solar to AC-in-2 | UInt32 | kWh | 0.01 | R |
| 4570 | 2 | Energy from solar to AC-out | UInt32 | kWh | 0.01 | R |
| 4572 | 2 | Energy from solar to battery | UInt32 | kWh | 0.01 | R |
| 4574 | 1 | Yield today | UInt16 | kWh | 0.1 | R |
| 4575 | 1 | Maximum charge power today | UInt16 | W | 1 | R |
| 4576 | 1 | Yield yesterday | UInt16 | kWh | 0.1 | R |
| 4577 | 1 | Maximum charge power yesterday | UInt16 | W | 1 | R |
| 4578 | 1 | Yield today for tracker 0 | UInt16 | kWh | 0.1 | R |
| 4579 | 1 | Yield today for tracker 1 | UInt16 | kWh | 0.1 | R |
| 4580 | 1 | Yield today for tracker 2 | UInt16 | kWh | 0.1 | R |
| 4581 | 1 | Yield today for tracker 3 | UInt16 | kWh | 0.1 | R |
| 4582 | 1 | Yield yesterday for tracker 0 | UInt16 | kWh | 0.1 | R |
| 4583 | 1 | Yield yesterday for tracker 1 | UInt16 | kWh | 0.1 | R |
| 4584 | 1 | Yield yesterday for tracker 2 | UInt16 | kWh | 0.1 | R |
| 4585 | 1 | Yield yesterday for tracker 3 | UInt16 | kWh | 0.1 | R |
| 4586 | 1 | Maximum charge power today for tracker 0 | UInt16 | W | 1 | R |
| 4587 | 1 | Maximum charge power today for tracker 1 | UInt16 | W | 1 | R |
| 4588 | 1 | Maximum charge power today for tracker 2 | UInt16 | W | 1 | R |
| 4589 | 1 | Maximum charge power today for tracker 3 | UInt16 | W | 1 | R |
| 4590 | 1 | Maximum charge power yesterday tracker 0 | UInt16 | W | 1 | R |
| 4591 | 1 | Maximum charge power yesterday tracker 1 | UInt16 | W | 1 | R |
| 4592 | 1 | Maximum charge power yesterday tracker 2 | UInt16 | W | 1 | R |
| 4593 | 1 | Maximum charge power yesterday tracker 3 | UInt16 | W | 1 | R |
| 4594 | 1 | PV voltage for tracker 0 | UInt16 | V DC | 0.1 | R |
| 4595 | 1 | PV voltage for tracker 1 | UInt16 | V DC | 0.1 | R |
| 4596 | 1 | PV voltage for tracker 2 | UInt16 | V DC | 0.1 | R |
| 4597 | 1 | PV voltage for tracker 3 | UInt16 | V DC | 0.1 | R |
| 4598 | 1 | PV power for tracker 0 | UInt16 | W | 1 | R |
| 4599 | 1 | PV power for tracker 1 | UInt16 | W | 1 | R |
| 4600 | 1 | PV power for tracker 2 | UInt16 | W | 1 | R |
| 4601 | 1 | PV power for tracker 3 | UInt16 | W | 1 | R |
| 4602 | 1 | Low SOC alarm 0=No alarm;1=Warning;2=Alarm | UInt16 | - | 1 | R |
| 4603 | 2 | User yield Energy generated by the solarcharger since last user reset | UInt32 | kWh | 1 | R |
| 4605 | 1 | MPP operation mode tracker 1 0=Off;1=Voltage/current limited;2=MPPT active;255=Not available | UInt16 | - | 1 | R |
| 4606 | 1 | MPP operation mode tracker 2 0=Off;1=Voltage/current limited;2=MPPT active;255=Not available | UInt16 | - | 1 | R |
| 4607 | 1 | MPP operation mode tracker 3 0=Off;1=Voltage/current limited;2=MPPT active;255=Not available | UInt16 | - | 1 | R |
| 4608 | 1 | MPP operation mode tracker 4 0=Off;1=Voltage/current limited;2=MPPT active;255=Not available | UInt16 | - | 1 | R |
| 4609 | 1 | ESS mode 0=self-consumption (battery-life);1=self-consumption;2=Keep charged;3=External control | UInt16 | - | 1 | RW |
| 4610 | 2 | ESS power setpoint | Int32 | W | 1 | RW |
| 4612 | 1 | Disable Feed-in 0=Feed-in enabled;1=Feed-in disabled | UInt16 | - | 1 | RW |
| 4613 | 1 | Disable charge 0=Charge enabled;1=Charge disabled | UInt16 | - | 1 | RW |
| 4614 | 1 | ESS Minimum SOC Limit | UInt16 | % | 1 | RW |
| 4615 | 1 | Sustain active 0=Sustain inactive; 1=Sustain active | UInt16 | - | 1 | R |
| 4620 | 1 | Short Circuit Alarm 0=Ok;1=Warning;2=Alarm | UInt16 | - | 1 | R |
| 4622 | 8 | Custom Name String[8]: 8 registers, 16 characters. The list prints string[6] as "12 characters", string[7] as "Max 14 characters" and string[16] as "32 characters", so string[n] is n registers of two characters each. | Ascii | - | 1 | RW |
| 4630 | 1 | Tracker 1 enabled 0=Disabled;1=Enabled | UInt16 | - | 1 | R |
| 4631 | 1 | Tracker 2 enabled 0=Disabled;1=Enabled | UInt16 | - | 1 | R |
| 4632 | 1 | Tracker 3 enabled 0=Disabled;1=Enabled | UInt16 | - | 1 | R |
| 4633 | 1 | Tracker 4 enabled 0=Disabled;1=Enabled | UInt16 | - | 1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
The Multi RS Solar is an inverter/charger with two integrated MPPT trackers and its own Modbus service: these are the com.victronenergy.multi registers of the Modbus TCP server that the GX device (Cerbo GX, Ekrano GX) runs, and they are a different map from the VE.Bus MultiPlus/Quattro block (victron-multiplus-quattro-vebus) — the two services share no address. Addresses are the decimal addresses of Victron's CCGX Modbus TCP register list (version 3.81, the vendor-hosted workbook linked on the supplier page), used unchanged as wire addresses, and the list's 'Scalefactor' column is a divisor, so the factors here are the equivalent multipliers. The unit ID is a declared placeholder: the register list's Unit ID mapping sheet has no preferred ID for this service (its rows cover the system, VE.Bus, VE.Direct and CAN-bus services), and the sheet's own note says a service's unit ID normally equals its device instance and is assigned dynamically since Venus OS 2.60, so read it from Settings > Integrations > Modbus TCP server > Available services on the GX device. Left out: the RESERVED rows 4616-4619 and 4621. The Custom Name at 4622 is a String[8], which the list's own ranges (string[6] = 12 characters, string[16] = 32 characters) make eight registers of two characters each; it spans 4622-4629 and 4630 follows it. The list numbers the tracker blocks 'tracker 0'-'tracker 3' for yields and PV readings but the MPP-mode rows 'tracker 1'-'tracker 4' over the same /Pv/0.../Pv/3 paths; the rows here keep the list's own labels. The list prints no byte or word order for its 32-bit values, so HighFirst is the Modbus convention, as in the library's other Victron seeds; if a two-register reading looks word-swapped, switch the device to LowFirst. Source: Victron Energy 'CCGX-Modbus-TCP-register-list-3.81.xlsx' — version 3.81, whose 'Document versions' sheet ends at Rev 54 — on victronenergy.com.