Solis · Solar inverter
S6-GR1P / 1P-5G / 3P-4G grid-tied string inverters Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 9600
- Parity
- None
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 2999 | 1 | Product Model | UInt16 | - | 1 | R |
| 3000 | 1 | DSP Software Version | UInt16 | - | 1 | R |
| 3001 | 1 | LCD Software Version | UInt16 | - | 1 | R |
| 3004 | 2 | Load Power 32-bit value, high word at 3004. Two of the three definitions give kW with 0.001, the third the same quantity in W with 1; the register is identical. | UInt32 | kW | 0.001 | R |
| 3006 | 2 | PV Power 32-bit value, high word at 3006. All three definitions name the pair 3007/3006 PV power at 0.001 kW; one of them also uses the same pair as the input to a derived inverter-efficiency row, which is why an earlier pass read 3006 as a conflicting meaning. | UInt32 | kW | 0.001 | R |
| 3008 | 2 | Total Production | UInt32 | kWh | 1 | R |
| 3010 | 2 | Monthly Production | UInt32 | kWh | 1 | R |
| 3014 | 1 | Today Production | UInt16 | kWh | 0.1 | R |
| 3016 | 2 | Yearly Production | UInt32 | kWh | 1 | R |
| 3021 | 1 | PV1 Voltage | UInt16 | V | 0.1 | R |
| 3022 | 1 | PV1 Current | UInt16 | A | 0.1 | R |
| 3023 | 1 | PV2 Voltage | UInt16 | V | 0.1 | R |
| 3024 | 1 | PV2 Current | UInt16 | A | 0.1 | R |
| 3025 | 1 | PV3 Voltage | UInt16 | V | 0.1 | R |
| 3026 | 1 | PV3 Current | UInt16 | A | 0.1 | R |
| 3033 | 1 | Load L1 Voltage | UInt16 | V | 0.1 | R |
| 3034 | 1 | Load L2 Voltage | UInt16 | V | 0.1 | R |
| 3035 | 1 | Load L3 voltage Single-phase definitions name the same register the load voltage, three-phase ones the L3 load voltage. | UInt16 | V | 0.1 | R |
| 3036 | 1 | Load L1 Current | UInt16 | A | 0.1 | R |
| 3037 | 1 | Load L2 Current | UInt16 | A | 0.1 | R |
| 3038 | 1 | Load L3 Current Single-phase definitions name the same register the load current, three-phase ones the L3 load current. | UInt16 | A | 0.1 | R |
| 3040 | 1 | Working Mode 0 = no response mode, 1 = volt-watt default, 2 = volt-var, 3 = fixed power factor, 4 = fixed reactive power, 5 = power-power-factor, 6 = rule 21 volt-watt (definition for the 1P-5G units). | UInt16 | - | 1 | R |
| 3041 | 1 | Inverter Temperature Signed: two of the three definitions read it as signed (rule 2), the third as unsigned (rule 1); a radiator temperature below freezing is possible, so the signed reading is used. | Int16 | °C | 0.1 | R |
| 3042 | 1 | Load Frequency | UInt16 | Hz | 0.01 | R |
| 3043 | 1 | Inverter Status The four operating codes the definitions agree on: 0 = waiting, 1 = open loop / open run, 2 = soft start, 3 = generating (on grid). Codes from 0x1004 up are grid and DC faults, but the two definitions list them differently (e.g. 0x1010 is over-voltage in one and under-voltage in the other), so they are not transcribed here. | UInt16 | - | 1 | R |
| 3071 | 1 | Operating Status Bit field: bit 0 normal, 1 initialising, 2 grid off, 4 standby, 5 derating, 6 limiting (definition for the 1P-5G units). | UInt16 | - | 1 | R |
| 3113 | 1 | Inverter AC Export Power | UInt16 | kW | 0.01 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Solis grid-tied string inverter map, built from the Solarman community definitions for the S6-GR1P, 1P-5G and 3P-4G single- and three-phase grid-tied families (ha-solarman commit 84982c5be1cda2c9642d87dd37e2bffd4aef6b83, files solis_s6-gr1p.yaml, solis_1p-5g.yaml, solis_3p-4g.yaml; SHA-256 deda5f35..., 33e7f095..., a9cd8703...). SECONDARY: the definitions cite no vendor document (two say 'Reference: ???'), so this is a community map. Types come from the definitions' own rules as the ha-solarman parser reads them (rule 1/3 unsigned, 2/4 signed; registers-list length is the width, first listed register the least significant word), which is why every 32-bit row is 2 registers and the device takes HighFirst: the definitions list e.g. [3007, 3006] for PV power, so the low word sits at the higher address. The RS-485 frame is not from these files: evcc's Solis template (templates/definition/meter/solis.yaml, 'Ginlong - Solis Inverter', pinned at commit d0763ede3e692491de2cef3056ca39258c3e180f, 2026-09-30, SHA-256 640e05fa6e0f4ec7a7958a5477d57012c698511e59019f76aec1cd851c531ded) declares modbus over rs485 at 9600 bps with unit 1, and 8N1 is evcc's serial default - a declared convention, not a printed value. No fetched Solis document prints the frame for the grid-tied S6/1P/3P units themselves: Solis' storage-model protocol (https://www.scss.tcd.ie/Brian.Coghlan/Elios4you/RS485_MODBUS-Hybrid-BACoghlan-201811228-1854.pdf, SHA-256 dd769abaec08cc455c6d9d0542358cab0c7eafbe8ce2d2e63c2670de0f4cb956) prints 9600/None/8/1 for those models only and is background here, not the citation. 3006 is PV power: all three definitions name the 3007/3006 pair that way, and one only reuses it as the input to a derived efficiency row. The three identity rows at 2999-3001 are plain UInt16 because no definition prints their value meanings. Register numbers are wire addresses (zero_based).