  "spec_version": 1,
  "slug": "solis-grid-tied-string-inverters",
  "manufacturer": "Solis",
  "model": "S6-GR1P / 1P-5G / 3P-4G grid-tied string inverters",
  "category": "Solar inverter",
  "supplier_url": "https://www.solisinverters.com/",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 9600,
      "parity": "None",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [
    {
      "address": 2999,
      "count": 1,
      "name": "Product Model",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3000,
      "count": 1,
      "name": "DSP Software Version",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3001,
      "count": 1,
      "name": "LCD Software Version",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3004,
      "count": 2,
      "name": "Load Power",
      "data_type": "UInt32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "32-bit value, high word at 3004. Two of the three definitions give kW with 0.001, the third the same quantity in W with 1; the register is identical."
    },
    {
      "address": 3006,
      "count": 2,
      "name": "PV Power",
      "data_type": "UInt32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "32-bit value, high word at 3006. All three definitions name the pair 3007/3006 PV power at 0.001 kW; one of them also uses the same pair as the input to a derived inverter-efficiency row, which is why an earlier pass read 3006 as a conflicting meaning."
    },
    {
      "address": 3008,
      "count": 2,
      "name": "Total Production",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3010,
      "count": 2,
      "name": "Monthly Production",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3014,
      "count": 1,
      "name": "Today Production",
      "data_type": "UInt16",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3016,
      "count": 2,
      "name": "Yearly Production",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3021,
      "count": 1,
      "name": "PV1 Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3022,
      "count": 1,
      "name": "PV1 Current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3023,
      "count": 1,
      "name": "PV2 Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3024,
      "count": 1,
      "name": "PV2 Current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3025,
      "count": 1,
      "name": "PV3 Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3026,
      "count": 1,
      "name": "PV3 Current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3033,
      "count": 1,
      "name": "Load L1 Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3034,
      "count": 1,
      "name": "Load L2 Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3035,
      "count": 1,
      "name": "Load L3 voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Single-phase definitions name the same register the load voltage, three-phase ones the L3 load voltage."
    },
    {
      "address": 3036,
      "count": 1,
      "name": "Load L1 Current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3037,
      "count": 1,
      "name": "Load L2 Current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3038,
      "count": 1,
      "name": "Load L3 Current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Single-phase definitions name the same register the load current, three-phase ones the L3 load current."
    },
    {
      "address": 3040,
      "count": 1,
      "name": "Working Mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 = no response mode, 1 = volt-watt default, 2 = volt-var, 3 = fixed power factor, 4 = fixed reactive power, 5 = power-power-factor, 6 = rule 21 volt-watt (definition for the 1P-5G units)."
    },
    {
      "address": 3041,
      "count": 1,
      "name": "Inverter Temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Signed: two of the three definitions read it as signed (rule 2), the third as unsigned (rule 1); a radiator temperature below freezing is possible, so the signed reading is used."
    },
    {
      "address": 3042,
      "count": 1,
      "name": "Load Frequency",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3043,
      "count": 1,
      "name": "Inverter Status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "The four operating codes the definitions agree on: 0 = waiting, 1 = open loop / open run, 2 = soft start, 3 = generating (on grid). Codes from 0x1004 up are grid and DC faults, but the two definitions list them differently (e.g. 0x1010 is over-voltage in one and under-voltage in the other), so they are not transcribed here."
    },
    {
      "address": 3071,
      "count": 1,
      "name": "Operating Status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Bit field: bit 0 normal, 1 initialising, 2 grid off, 4 standby, 5 derating, 6 limiting (definition for the 1P-5G units)."
    },
    {
      "address": 3113,
      "count": 1,
      "name": "Inverter AC Export Power",
      "data_type": "UInt16",
      "units": "kW",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    }
  ],
  "holding_registers": [],
  "combined_registers": [],
  "notes": "Solis grid-tied string inverter map, built from the Solarman community definitions for the S6-GR1P, 1P-5G and 3P-4G single- and three-phase grid-tied families (ha-solarman commit 84982c5be1cda2c9642d87dd37e2bffd4aef6b83, files solis_s6-gr1p.yaml, solis_1p-5g.yaml, solis_3p-4g.yaml; SHA-256 deda5f35..., 33e7f095..., a9cd8703...). SECONDARY: the definitions cite no vendor document (two say 'Reference: ???'), so this is a community map. Types come from the definitions' own rules as the ha-solarman parser reads them (rule 1/3 unsigned, 2/4 signed; registers-list length is the width, first listed register the least significant word), which is why every 32-bit row is 2 registers and the device takes HighFirst: the definitions list e.g. [3007, 3006] for PV power, so the low word sits at the higher address. The RS-485 frame is not from these files: evcc's Solis template (templates/definition/meter/solis.yaml, 'Ginlong - Solis Inverter', pinned at commit d0763ede3e692491de2cef3056ca39258c3e180f, 2026-09-30, SHA-256 640e05fa6e0f4ec7a7958a5477d57012c698511e59019f76aec1cd851c531ded) declares modbus over rs485 at 9600 bps with unit 1, and 8N1 is evcc's serial default - a declared convention, not a printed value. No fetched Solis document prints the frame for the grid-tied S6/1P/3P units themselves: Solis' storage-model protocol (https://www.scss.tcd.ie/Brian.Coghlan/Elios4you/RS485_MODBUS-Hybrid-BACoghlan-201811228-1854.pdf, SHA-256 dd769abaec08cc455c6d9d0542358cab0c7eafbe8ce2d2e63c2670de0f4cb956) prints 9600/None/8/1 for those models only and is background here, not the citation. 3006 is PV power: all three definitions name the 3007/3006 pair that way, and one only reuses it as the input to a derived efficiency row. The three identity rows at 2999-3001 are plain UInt16 because no definition prints their value meanings. Register numbers are wire addresses (zero_based)."
}