Seplos · Home battery
Seplos BMS 3.0 (BMS48100 / BMS48200 rack packs) RS485 Modbus RTU protocol Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 19200
- Parity
- None
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 4096 | 1 | Pack voltage | UInt16 | V | 0.01 | R |
| 4097 | 1 | Pack current | Int16 | A | 0.01 | R |
| 4098 | 1 | Remaining capacity | UInt16 | Ah | 0.01 | R |
| 4099 | 1 | Total capacity | UInt16 | Ah | 0.01 | R |
| 4100 | 1 | Total discharged capacity | UInt16 | Ah | 10 | R |
| 4101 | 1 | State of charge (SOC) | UInt16 | % | 0.1 | R |
| 4102 | 1 | State of health (SOH) | UInt16 | % | 0.1 | R |
| 4103 | 1 | Cycle count | UInt16 | - | 1 | R |
| 4104 | 1 | Average cell voltage | UInt16 | mV | 1 | R |
| 4105 | 1 | Average cell temperature The document prints the unit as 0.1K and it is stored as printed. | UInt16 | K | 0.1 | R |
| 4106 | 1 | Maximum cell voltage | UInt16 | mV | 1 | R |
| 4107 | 1 | Minimum cell voltage | UInt16 | mV | 1 | R |
| 4108 | 1 | Maximum cell temperature | UInt16 | K | 0.1 | R |
| 4109 | 1 | Minimum cell temperature | UInt16 | K | 0.1 | R |
| 4111 | 1 | Recommended maximum discharge current | UInt16 | A | 1 | R |
| 4112 | 1 | Recommended maximum charge current | UInt16 | A | 1 | R |
| 4352 | 1 | Cell 1 voltage | UInt16 | mV | 1 | R |
| 4353 | 1 | Cell 2 voltage | UInt16 | mV | 1 | R |
| 4354 | 1 | Cell 3 voltage | UInt16 | mV | 1 | R |
| 4355 | 1 | Cell 4 voltage | UInt16 | mV | 1 | R |
| 4356 | 1 | Cell 5 voltage | UInt16 | mV | 1 | R |
| 4357 | 1 | Cell 6 voltage | UInt16 | mV | 1 | R |
| 4358 | 1 | Cell 7 voltage | UInt16 | mV | 1 | R |
| 4359 | 1 | Cell 8 voltage | UInt16 | mV | 1 | R |
| 4360 | 1 | Cell 9 voltage | UInt16 | mV | 1 | R |
| 4361 | 1 | Cell 10 voltage | UInt16 | mV | 1 | R |
| 4362 | 1 | Cell 11 voltage | UInt16 | mV | 1 | R |
| 4363 | 1 | Cell 12 voltage | UInt16 | mV | 1 | R |
| 4364 | 1 | Cell 13 voltage | UInt16 | mV | 1 | R |
| 4365 | 1 | Cell 14 voltage | UInt16 | mV | 1 | R |
| 4366 | 1 | Cell 15 voltage | UInt16 | mV | 1 | R |
| 4367 | 1 | Cell 16 voltage | UInt16 | mV | 1 | R |
| 4368 | 1 | Cell temperature sensor 1 | UInt16 | K | 0.1 | R |
| 4369 | 1 | Cell temperature sensor 2 | UInt16 | K | 0.1 | R |
| 4370 | 1 | Cell temperature sensor 3 | UInt16 | K | 0.1 | R |
| 4371 | 1 | Cell temperature sensor 4 | UInt16 | K | 0.1 | R |
| 4376 | 1 | Environment temperature | UInt16 | K | 0.1 | R |
| 4377 | 1 | Power stage temperature | UInt16 | K | 0.1 | R |
| 5632 | 2 | Number of remaining history records | UInt32 | - | 1 | R |
| 5643 | 1 | Record: pack voltage | UInt16 | V | 0.01 | R |
| 5644 | 1 | Record: pack current | Int16 | A | 0.01 | R |
| 5645 | 1 | Record: remaining capacity | UInt16 | Ah | 0.01 | R |
| 5646 | 1 | Record: cell 1 voltage | UInt16 | mV | 1 | R |
| 5647 | 1 | Record: cell 2 voltage | UInt16 | mV | 1 | R |
| 5648 | 1 | Record: cell 3 voltage | UInt16 | mV | 1 | R |
| 5649 | 1 | Record: cell 4 voltage | UInt16 | mV | 1 | R |
| 5650 | 1 | Record: cell 5 voltage | UInt16 | mV | 1 | R |
| 5651 | 1 | Record: cell 6 voltage | UInt16 | mV | 1 | R |
| 5652 | 1 | Record: cell 7 voltage | UInt16 | mV | 1 | R |
| 5653 | 1 | Record: cell 8 voltage | UInt16 | mV | 1 | R |
| 5654 | 1 | Record: cell 9 voltage | UInt16 | mV | 1 | R |
| 5655 | 1 | Record: cell 10 voltage | UInt16 | mV | 1 | R |
| 5656 | 1 | Record: cell 11 voltage | UInt16 | mV | 1 | R |
| 5657 | 1 | Record: cell 12 voltage | UInt16 | mV | 1 | R |
| 5658 | 1 | Record: cell 13 voltage | UInt16 | mV | 1 | R |
| 5659 | 1 | Record: cell 14 voltage | UInt16 | mV | 1 | R |
| 5660 | 1 | Record: cell 15 voltage | UInt16 | mV | 1 | R |
| 5661 | 1 | Record: cell 16 voltage | UInt16 | mV | 1 | R |
| 5662 | 1 | Record: cell temperature sensor 1 | UInt16 | K | 0.1 | R |
| 5663 | 1 | Record: cell temperature sensor 2 | UInt16 | K | 0.1 | R |
| 5664 | 1 | Record: cell temperature sensor 3 | UInt16 | K | 0.1 | R |
| 5665 | 1 | Record: cell temperature sensor 4 | UInt16 | K | 0.1 | R |
| 5670 | 1 | Record: environment temperature | UInt16 | K | 0.1 | R |
| 5671 | 1 | Record: power stage temperature | UInt16 | K | 0.1 | R |
| 5888 | 10 | Factory name 20-byte ASCII string. | Ascii | - | 1 | R |
| 5898 | 10 | Device name 20-byte ASCII string; the document marks it read/write. | Ascii | - | 1 | R |
| 5908 | 1 | Firmware version The document prints a 2-byte ASCII field. | Ascii | - | 1 | R |
| 5909 | 15 | BMS serial number (QR code) 30-byte ASCII string. | Ascii | - | 1 | R |
| 5924 | 15 | Pack serial number (QR code) 30-byte ASCII string. | Ascii | - | 1 | R |
| 6145 | 1 | Inverter baud rate setting The document prints the unit column as Kbps/bps without saying which applies. | UInt16 | - | 1 | R |
| 6146 | 16 | Inverter name 32-byte ASCII string. | Ascii | - | 1 | R |
| 6162 | 16 | Supported protocol name 32-byte ASCII string. | Ascii | - | 1 | R |
| 6178 | 1 | Protocol version 2-byte ASCII string. | Ascii | - | 1 | R |
| 8192 | 2 | System pack voltage | UInt32 | V | 0.01 | R |
| 8194 | 2 | System current | Int32 | A | 0.1 | R |
| 8196 | 2 | System remaining capacity | UInt32 | Ah | 0.01 | R |
| 8198 | 2 | System total capacity | UInt32 | Ah | 0.01 | R |
| 8200 | 2 | System total discharged capacity | UInt32 | Ah | 10 | R |
| 8202 | 2 | System rated capacity | UInt32 | Ah | 0.01 | R |
| 8204 | 2 | Online pack bitmap Bit field; the document names the register but prints no bit table for it. | UInt32 | - | 1 | R |
| 8206 | 2 | Protected pack bitmap Bit field; the document names the register but prints no bit table for it. | UInt32 | - | 1 | R |
| 8208 | 2 | Suggested maximum discharge current | UInt32 | A | 0.1 | R |
| 8210 | 2 | Suggested maximum charge current | UInt32 | A | 0.1 | R |
| 8212 | 1 | Suggested pack over-voltage | UInt16 | V | 0.1 | R |
| 8213 | 1 | Suggested pack under-voltage | UInt16 | V | 0.1 | R |
| 8214 | 1 | Number of parallel packs | UInt16 | - | 1 | R |
| 8215 | 1 | Average cycle count | UInt16 | - | 1 | R |
| 8216 | 1 | System state of charge (SOC) | UInt16 | % | 0.1 | R |
| 8217 | 1 | System state of health (SOH) | UInt16 | % | 0.1 | R |
| 8448 | 1 | System maximum cell voltage | UInt16 | mV | 1 | R |
| 8449 | 1 | System minimum cell voltage | UInt16 | mV | 1 | R |
| 8450 | 1 | System maximum cell voltage cell number | UInt16 | - | 1 | R |
| 8451 | 1 | System minimum cell voltage cell number | UInt16 | - | 1 | R |
| 8452 | 1 | Highest pack voltage | UInt16 | V | 0.01 | R |
| 8453 | 1 | Lowest pack voltage | UInt16 | V | 0.01 | R |
| 8454 | 1 | Highest pack voltage pack number | UInt16 | - | 1 | R |
| 8455 | 1 | Lowest pack voltage pack number | UInt16 | - | 1 | R |
| 8456 | 1 | Highest cell temperature | Int16 | °C | 1 | R |
| 8457 | 1 | Lowest cell temperature | Int16 | °C | 1 | R |
| 8458 | 1 | Average cell temperature | Int16 | °C | 1 | R |
| 8459 | 1 | Highest cell temperature cell number | UInt16 | - | 1 | R |
| 8460 | 1 | Lowest cell temperature cell number | UInt16 | - | 1 | R |
| 8461 | 1 | Highest power stage temperature | Int16 | °C | 1 | R |
| 8462 | 1 | Lowest power stage temperature | Int16 | °C | 1 | R |
| 8463 | 1 | Average power stage temperature | Int16 | °C | 1 | R |
| 8464 | 1 | Highest power stage temperature pack number | Int16 | - | 1 | R |
| 8465 | 1 | Lowest power stage temperature pack number | Int16 | - | 1 | R |
| 8466 | 1 | Highest pack SOC | UInt16 | % | 0.1 | R |
| 8467 | 1 | Lowest pack SOC | UInt16 | % | 0.1 | R |
| 8468 | 1 | Highest pack cycle count | UInt16 | - | 1 | R |
| 8469 | 1 | Highest pack SOH | UInt16 | % | 0.1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: Seplos "BMS Modbus RTU Protocol" (BMS48100/48200), V0.1, 2023-02-09, read from the vendor-document mirror github.com/marcelrv/seplosBMSv3 (BMS3.0 Modbus-RTU Protocol.pdf, 2026-11-23, SHA-256 43eb7428ae28f9e0bdbcf8e01b9a78a502b4ba51b12ee49c524e356cb3fd2dab). MIRROR-SOURCED: Seplos serves no download. Framing (1.1): RS-485, 19200 8N1, no parity; 0x04 read, 0x10 write, 0x01/0x0F coils. Addresses: the "Relative Address" column prints the address as used and nothing says to add one, so zero_based; hex is proved by rows 100A and 160B. Device ids are 0x00-0x7F with no factory value, so unit 1 is a placeholder. All rows are input registers because 2.1.1 assigns 0x04 to PIA/PIB/SPA/SCA/HIA/VIA/EIA/EIB/PCT. Seeded: PIA (0x1000), cells (0x1100), the latest history record (0x1600), version strings (0x1700), PCS identification (0x1800) and EMS EIA/EIB (0x2000/0x2100). Units are stored as printed (10mV is scale 0.01 with unit V, 0.1K stays K, likewise 0.1% and 10mAH); ASCII rows carry the printed byte counts and no byte swap, because the mirror's example response reads them big-endian. The history rows only hold a record after the non-standard request the HIA note prints (start 0x7000, 55AA first record, AA55 next). READ-ONLY: the twelve 0x1500 commands (0x150D-0x1519) are not seeded, because a wrong write can damage a pack or drop its load and no range is printed. Not seeded: PIC (0x1200) and EIC (0x2200) alarm and event blocks, which 2.1.1 assigns to 0x01 read-coil-status and which the tables print as byte groups, so they cannot be one-bit coil rows without inventing per-bit names (the mirror agrees: PIC is 144 bits, read with read_coils(0x1200, 0x90)); SPA thresholds (0x1300) and SFA switches (0x1400), R/W with no range; the 0x1500 timing/date/record rows (0x1504, 0x1500, 0x7000); the 0x1600 timestamp and event bytes (0x1602-0x160A); the protocol switches at 0x1800/0x1823. Event codes carry the document's TB02-TB18 reference, not a decoded bit list.