  "spec_version": 1,
  "slug": "seplos-bms-3-0-modbus",
  "manufacturer": "Seplos",
  "model": "Seplos BMS 3.0 (BMS48100 / BMS48200 rack packs) RS485 Modbus RTU protocol",
  "category": "Home battery",
  "supplier_url": "https://www.seplos.com/",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 19200,
      "parity": "None",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [
    {
      "address": 4096,
      "count": 1,
      "name": "Pack voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4097,
      "count": 1,
      "name": "Pack current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4098,
      "count": 1,
      "name": "Remaining capacity",
      "data_type": "UInt16",
      "units": "Ah",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4099,
      "count": 1,
      "name": "Total capacity",
      "data_type": "UInt16",
      "units": "Ah",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4100,
      "count": 1,
      "name": "Total discharged capacity",
      "data_type": "UInt16",
      "units": "Ah",
      "scale_factor": 10,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4101,
      "count": 1,
      "name": "State of charge (SOC)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4102,
      "count": 1,
      "name": "State of health (SOH)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4103,
      "count": 1,
      "name": "Cycle count",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4104,
      "count": 1,
      "name": "Average cell voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4105,
      "count": 1,
      "name": "Average cell temperature",
      "data_type": "UInt16",
      "units": "K",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "The document prints the unit as 0.1K and it is stored as printed."
    },
    {
      "address": 4106,
      "count": 1,
      "name": "Maximum cell voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4107,
      "count": 1,
      "name": "Minimum cell voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4108,
      "count": 1,
      "name": "Maximum cell temperature",
      "data_type": "UInt16",
      "units": "K",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4109,
      "count": 1,
      "name": "Minimum cell temperature",
      "data_type": "UInt16",
      "units": "K",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4111,
      "count": 1,
      "name": "Recommended maximum discharge current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4112,
      "count": 1,
      "name": "Recommended maximum charge current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4352,
      "count": 1,
      "name": "Cell 1 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4353,
      "count": 1,
      "name": "Cell 2 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4354,
      "count": 1,
      "name": "Cell 3 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4355,
      "count": 1,
      "name": "Cell 4 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4356,
      "count": 1,
      "name": "Cell 5 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4357,
      "count": 1,
      "name": "Cell 6 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4358,
      "count": 1,
      "name": "Cell 7 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4359,
      "count": 1,
      "name": "Cell 8 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4360,
      "count": 1,
      "name": "Cell 9 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4361,
      "count": 1,
      "name": "Cell 10 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4362,
      "count": 1,
      "name": "Cell 11 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4363,
      "count": 1,
      "name": "Cell 12 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4364,
      "count": 1,
      "name": "Cell 13 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4365,
      "count": 1,
      "name": "Cell 14 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4366,
      "count": 1,
      "name": "Cell 15 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4367,
      "count": 1,
      "name": "Cell 16 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4368,
      "count": 1,
      "name": "Cell temperature sensor 1",
      "data_type": "UInt16",
      "units": "K",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4369,
      "count": 1,
      "name": "Cell temperature sensor 2",
      "data_type": "UInt16",
      "units": "K",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4370,
      "count": 1,
      "name": "Cell temperature sensor 3",
      "data_type": "UInt16",
      "units": "K",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4371,
      "count": 1,
      "name": "Cell temperature sensor 4",
      "data_type": "UInt16",
      "units": "K",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4376,
      "count": 1,
      "name": "Environment temperature",
      "data_type": "UInt16",
      "units": "K",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4377,
      "count": 1,
      "name": "Power stage temperature",
      "data_type": "UInt16",
      "units": "K",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5632,
      "count": 2,
      "name": "Number of remaining history records",
      "data_type": "UInt32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5643,
      "count": 1,
      "name": "Record: pack voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5644,
      "count": 1,
      "name": "Record: pack current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5645,
      "count": 1,
      "name": "Record: remaining capacity",
      "data_type": "UInt16",
      "units": "Ah",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5646,
      "count": 1,
      "name": "Record: cell 1 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5647,
      "count": 1,
      "name": "Record: cell 2 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5648,
      "count": 1,
      "name": "Record: cell 3 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5649,
      "count": 1,
      "name": "Record: cell 4 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5650,
      "count": 1,
      "name": "Record: cell 5 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5651,
      "count": 1,
      "name": "Record: cell 6 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5652,
      "count": 1,
      "name": "Record: cell 7 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5653,
      "count": 1,
      "name": "Record: cell 8 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5654,
      "count": 1,
      "name": "Record: cell 9 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5655,
      "count": 1,
      "name": "Record: cell 10 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5656,
      "count": 1,
      "name": "Record: cell 11 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5657,
      "count": 1,
      "name": "Record: cell 12 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5658,
      "count": 1,
      "name": "Record: cell 13 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5659,
      "count": 1,
      "name": "Record: cell 14 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5660,
      "count": 1,
      "name": "Record: cell 15 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5661,
      "count": 1,
      "name": "Record: cell 16 voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5662,
      "count": 1,
      "name": "Record: cell temperature sensor 1",
      "data_type": "UInt16",
      "units": "K",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5663,
      "count": 1,
      "name": "Record: cell temperature sensor 2",
      "data_type": "UInt16",
      "units": "K",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5664,
      "count": 1,
      "name": "Record: cell temperature sensor 3",
      "data_type": "UInt16",
      "units": "K",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5665,
      "count": 1,
      "name": "Record: cell temperature sensor 4",
      "data_type": "UInt16",
      "units": "K",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5670,
      "count": 1,
      "name": "Record: environment temperature",
      "data_type": "UInt16",
      "units": "K",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5671,
      "count": 1,
      "name": "Record: power stage temperature",
      "data_type": "UInt16",
      "units": "K",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 5888,
      "count": 10,
      "name": "Factory name",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "20-byte ASCII string."
    },
    {
      "address": 5898,
      "count": 10,
      "name": "Device name",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "20-byte ASCII string; the document marks it read/write."
    },
    {
      "address": 5908,
      "count": 1,
      "name": "Firmware version",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "The document prints a 2-byte ASCII field."
    },
    {
      "address": 5909,
      "count": 15,
      "name": "BMS serial number (QR code)",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "30-byte ASCII string."
    },
    {
      "address": 5924,
      "count": 15,
      "name": "Pack serial number (QR code)",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "30-byte ASCII string."
    },
    {
      "address": 6145,
      "count": 1,
      "name": "Inverter baud rate setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "The document prints the unit column as Kbps/bps without saying which applies."
    },
    {
      "address": 6146,
      "count": 16,
      "name": "Inverter name",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "32-byte ASCII string."
    },
    {
      "address": 6162,
      "count": 16,
      "name": "Supported protocol name",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "32-byte ASCII string."
    },
    {
      "address": 6178,
      "count": 1,
      "name": "Protocol version",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "2-byte ASCII string."
    },
    {
      "address": 8192,
      "count": 2,
      "name": "System pack voltage",
      "data_type": "UInt32",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8194,
      "count": 2,
      "name": "System current",
      "data_type": "Int32",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8196,
      "count": 2,
      "name": "System remaining capacity",
      "data_type": "UInt32",
      "units": "Ah",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8198,
      "count": 2,
      "name": "System total capacity",
      "data_type": "UInt32",
      "units": "Ah",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8200,
      "count": 2,
      "name": "System total discharged capacity",
      "data_type": "UInt32",
      "units": "Ah",
      "scale_factor": 10,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8202,
      "count": 2,
      "name": "System rated capacity",
      "data_type": "UInt32",
      "units": "Ah",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8204,
      "count": 2,
      "name": "Online pack bitmap",
      "data_type": "UInt32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Bit field; the document names the register but prints no bit table for it."
    },
    {
      "address": 8206,
      "count": 2,
      "name": "Protected pack bitmap",
      "data_type": "UInt32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Bit field; the document names the register but prints no bit table for it."
    },
    {
      "address": 8208,
      "count": 2,
      "name": "Suggested maximum discharge current",
      "data_type": "UInt32",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8210,
      "count": 2,
      "name": "Suggested maximum charge current",
      "data_type": "UInt32",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8212,
      "count": 1,
      "name": "Suggested pack over-voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8213,
      "count": 1,
      "name": "Suggested pack under-voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8214,
      "count": 1,
      "name": "Number of parallel packs",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8215,
      "count": 1,
      "name": "Average cycle count",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8216,
      "count": 1,
      "name": "System state of charge (SOC)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8217,
      "count": 1,
      "name": "System state of health (SOH)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8448,
      "count": 1,
      "name": "System maximum cell voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8449,
      "count": 1,
      "name": "System minimum cell voltage",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8450,
      "count": 1,
      "name": "System maximum cell voltage cell number",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8451,
      "count": 1,
      "name": "System minimum cell voltage cell number",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8452,
      "count": 1,
      "name": "Highest pack voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8453,
      "count": 1,
      "name": "Lowest pack voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8454,
      "count": 1,
      "name": "Highest pack voltage pack number",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8455,
      "count": 1,
      "name": "Lowest pack voltage pack number",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8456,
      "count": 1,
      "name": "Highest cell temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8457,
      "count": 1,
      "name": "Lowest cell temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8458,
      "count": 1,
      "name": "Average cell temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8459,
      "count": 1,
      "name": "Highest cell temperature cell number",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8460,
      "count": 1,
      "name": "Lowest cell temperature cell number",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8461,
      "count": 1,
      "name": "Highest power stage temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8462,
      "count": 1,
      "name": "Lowest power stage temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8463,
      "count": 1,
      "name": "Average power stage temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8464,
      "count": 1,
      "name": "Highest power stage temperature pack number",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8465,
      "count": 1,
      "name": "Lowest power stage temperature pack number",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8466,
      "count": 1,
      "name": "Highest pack SOC",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8467,
      "count": 1,
      "name": "Lowest pack SOC",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8468,
      "count": 1,
      "name": "Highest pack cycle count",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8469,
      "count": 1,
      "name": "Highest pack SOH",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    }
  ],
  "holding_registers": [],
  "combined_registers": [],
  "notes": "Source: Seplos \"BMS Modbus RTU Protocol\" (BMS48100/48200), V0.1, 2023-02-09, read from the vendor-document mirror github.com/marcelrv/seplosBMSv3 (BMS3.0 Modbus-RTU Protocol.pdf, 2026-11-23, SHA-256 43eb7428ae28f9e0bdbcf8e01b9a78a502b4ba51b12ee49c524e356cb3fd2dab). MIRROR-SOURCED: Seplos serves no download. Framing (1.1): RS-485, 19200 8N1, no parity; 0x04 read, 0x10 write, 0x01/0x0F coils. Addresses: the \"Relative Address\" column prints the address as used and nothing says to add one, so zero_based; hex is proved by rows 100A and 160B. Device ids are 0x00-0x7F with no factory value, so unit 1 is a placeholder. All rows are input registers because 2.1.1 assigns 0x04 to PIA/PIB/SPA/SCA/HIA/VIA/EIA/EIB/PCT. Seeded: PIA (0x1000), cells (0x1100), the latest history record (0x1600), version strings (0x1700), PCS identification (0x1800) and EMS EIA/EIB (0x2000/0x2100). Units are stored as printed (10mV is scale 0.01 with unit V, 0.1K stays K, likewise 0.1% and 10mAH); ASCII rows carry the printed byte counts and no byte swap, because the mirror's example response reads them big-endian. The history rows only hold a record after the non-standard request the HIA note prints (start 0x7000, 55AA first record, AA55 next). READ-ONLY: the twelve 0x1500 commands (0x150D-0x1519) are not seeded, because a wrong write can damage a pack or drop its load and no range is printed. Not seeded: PIC (0x1200) and EIC (0x2200) alarm and event blocks, which 2.1.1 assigns to 0x01 read-coil-status and which the tables print as byte groups, so they cannot be one-bit coil rows without inventing per-bit names (the mirror agrees: PIC is 144 bits, read with read_coils(0x1200, 0x90)); SPA thresholds (0x1300) and SFA switches (0x1400), R/W with no range; the 0x1500 timing/date/record rows (0x1504, 0x1500, 0x7000); the 0x1600 timestamp and event bytes (0x1602-0x160A); the protocol switches at 0x1800/0x1823. Event codes carry the document's TB02-TB18 reference, not a decoded bit list."
}