All devices

BLUETTI · Home battery

Balco 260 / Balco 500 balcony storage Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
Low word first

Register map

AddressCountNameTypeUnitScaleAccess
500011
Number of Inverters
UInt16-1R
500022
AC Load Power (Total)
UInt32W1R
500042
PV Power (Total)
UInt32W1R
500062
Grid Power (Total)
Signed 32-bit value, as the sheet's type column is int. The sheet prints no sign convention for the totals row, and the vendor repository's issue #12 reports the value as the sum of the three phase magnitudes, so import and export cannot be told apart in it.
Int32W1R
500082
Inverter Power (Total)
Signed 32-bit value, as the sheet's type column is int, 2 registers wide. On a live Balco 260 the pair 50008-50009 reads [64336, 0xFFFF], which is -1200 W low word first (bluetti-community/bluetti-modbus test suite, bluetti-registers#20), matching the charging power computed from pack voltage and current at the same moment.
Int32W1R
500102
PV to AC Load Power
UInt32W1R
500122
AC Load Energy (Total)
UInt32kWh0.1R
500142
PV Charging Energy (Total)
UInt32kWh0.1R
500162
Grid Charging Energy (Total)
UInt32kWh0.1R
500182
Feed-in Grid Energy
UInt32kWh0.1R
500202
PV to AC Load Energy
UInt32kWh0.1R
500221
Inverter Operating Status
0 = stop, 1 = off-grid operation, 2 = grid-connected load, 3 = grid-connected operation, 4 = grid-connected charging, 5 = grid-connected discharging, 6 = inverter fault, 7 = abnormal off-grid. Values as printed in the vendor sheet.
UInt16-1R
502006
Inverter Type
Ascii-1R
502141
Grid Access Frequency
UInt16Hz0.1R
502152
Grid Charging Power (Single)
Int32W1R
502172
AC Load Power (Single)
UInt32W1R
502192
PV Charging Power (Single)
UInt32W1R
502212
PV to AC Load Power (Single)
UInt32W1R
502232
Grid Charging Energy (Single)
UInt32kWh0.1R
502252
Feed-in Grid Energy (Single)
UInt32kWh0.1R
502272
AC Load Energy (Single)
UInt32kWh0.1R
502292
PV Charging Energy (Single)
UInt32kWh0.1R
502312
PV to AC Load Energy (Single)
UInt32kWh0.1R
502341
System Phase Number
UInt16-1R
502361
Grid1 Voltage
UInt16V0.1R
502371
Grid1 Current
Int16A0.1R
502391
Grid2 Voltage
UInt16V0.1R
502401
Grid2 Current
Int16A0.1R
502421
Grid3 Voltage
UInt16V0.1R
502431
Grid3 Current
Int16A0.1R
502441
AC System Phase Number
UInt16-1R
502451
AC Load1 Power
UInt16W1R
502461
AC Load1 Voltage
UInt16V0.1R
502471
AC Load1 Current
UInt16A0.1R
502481
AC Load2 Power
UInt16W1R
502491
AC Load2 Voltage
UInt16V0.1R
502501
AC Load2 Current
UInt16A0.1R
502511
AC Load3 Power
UInt16W1R
502521
AC Load3 Voltage
UInt16V0.1R
502531
AC Load3 Current
UInt16A0.1R
502541
Inverter System Phase Number
UInt16-1R
502551
Inverter1 Operation Status
0 = stop, 1 = off-grid operation, 2 = grid-connected load, 3 = grid-connected operation, 4 = grid-connected charging, 5 = grid-connected discharging.
UInt16-1R
502561
Inverter1 Power
UInt16W1R
502571
Inverter1 Voltage
UInt16V0.1R
502581
Inverter1 Current
UInt16A0.1R
502591
Inverter2 Operation Status
0 = stop, 1 = off-grid operation, 2 = grid-connected load, 3 = grid-connected operation, 4 = grid-connected charging, 5 = grid-connected discharging.
UInt16-1R
502601
Inverter2 Power
UInt16W1R
502611
Inverter2 Voltage
UInt16V0.1R
502621
Inverter2 Current
UInt16A0.1R
502631
Inverter3 Operation Status
0 = stop, 1 = off-grid operation, 2 = grid-connected load, 3 = grid-connected operation, 4 = grid-connected charging, 5 = grid-connected discharging.
UInt16-1R
502641
Inverter3 Power
UInt16W1R
502651
Inverter3 Voltage
UInt16V0.1R
502661
Inverter3 Current
UInt16A0.1R
502671
PV Total Number
Bit 0-3 = number of DC PV inputs, bit 4-7 = number of AC PV inputs.
UInt16-1R
502681
PV1 Type
0 = reserve, 1 = CAR, 2 = adapter, 3 = other; 100 = DC PV and 101 = AC PV on the models that report them
UInt16-1R
502691
PV1 Input Power
UInt16W1R
502701
PV1 Input Voltage
UInt16V0.1R
502711
PV1 Input Current
UInt16A0.1R
502721
PV2 Type
0 = reserve, 1 = CAR, 2 = adapter, 3 = other; 100 = DC PV and 101 = AC PV on the models that report them. Only the inputs a model actually has are meaningful: a measured EP2000 reports two DC inputs and reads junk in the slots from PV3 up (vendor repository issue #12), so treat PV3 to PV5 as model-dependent on the BalcoXX family too.
UInt16-1R
502761
PV3 Type
0 = reserve, 1 = CAR, 2 = adapter, 3 = other; 100 = DC PV and 101 = AC PV on the models that report them. Only the inputs a model actually has are meaningful: a measured EP2000 reports two DC inputs and reads junk in the slots from PV3 up (vendor repository issue #12), so treat PV3 to PV5 as model-dependent on the BalcoXX family too.
UInt16-1R
502801
PV4 Type
0 = reserve, 1 = CAR, 2 = adapter, 3 = other; 100 = DC PV and 101 = AC PV on the models that report them. Only the inputs a model actually has are meaningful: a measured EP2000 reports two DC inputs and reads junk in the slots from PV3 up (vendor repository issue #12), so treat PV3 to PV5 as model-dependent on the BalcoXX family too.
UInt16-1R
502841
PV5 Type
0 = reserve, 1 = CAR, 2 = adapter, 3 = other; 100 = DC PV and 101 = AC PV on the models that report them. Only the inputs a model actually has are meaningful: a measured EP2000 reports two DC inputs and reads junk in the slots from PV3 up (vendor repository issue #12), so treat PV3 to PV5 as model-dependent on the BalcoXX family too.
UInt16-1R
510021
Total Pack Voltage
UInt16V0.1R
510031
Total Pack Current
UInt16A0.1R
512006
Pack Type
Ascii-1R
512101
Total Pack Software Number
UInt16-1R
512191
Pack Voltage
UInt16V0.1R
512201
Pack Current
The sheet types the pack current as unsigned, unlike the string-level current rows. BLUETTI support reports that the Balco 260 encodes it as the raw value minus 30000 at 0.1 A (quoted in the vendor repository's issue #12), which the offset applies; the sheet documents neither the offset nor a sign.
UInt16A0.1 (offset -3000)R
512211
Pack SOC
UInt16%1R
512221
Pack SOH
UInt16%1R
512231
Pack Cycle Count
UInt16-1R
512241
Pack Average Temperature
The sheet gives -40 to 160. On an EP2000 the same row reads degrees Celsius plus 40 (measured: raw 58 while the packs were at 18 °C, vendor repository issues #12 and #145), and this sheet's range fits that encoding, but no Balco has been measured and the Balco 500 community entry reads the row as plain °C. Seeded without an offset until one is measured.
Int16°C1R
512341
Pack Total Cell Count
UInt16-1R
512351
Pack Total NTC Count
UInt16-1R
512362
Pack Total Charging Energy
UInt32Wh1R
512382
Pack Total Discharging Energy
UInt32Wh1R
512481
Pack Estimated Full Charge Time
Minutes. On measured EP2000 units this estimate and its discharge counterpart 51249 always read the same value, charging or discharging (vendor repository issue #12); no such reading exists for a Balco.
UInt16min1R
512491
Pack Estimated Full Discharge Time
Minutes. Reads the same value as 51248 on measured EP2000 units.
UInt16min1R
530016
IoT Model
Ascii-1R
570011
AC load output switch
0 = off, 1 = on.
UInt16-1RW
570091
AC grid charging switch
0 = off, 1 = on.
UInt16-1RW
570101
AC grid feed-in switch
0 = off, 1 = on.
UInt16-1RW
570161
Battery empty SOC threshold
Discharging stops at this state of charge. The sheet prints 0 to 100, in percent, as the valid range.
UInt16%1RW
570171
Battery full SOC threshold
Charging stops at this state of charge. The sheet prints 0 to 100, in percent, as the valid range.
UInt16%1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Register map from BLUETTI's open Modbus TCP list, bluetti-official/bluetti-modbus-tcp-slave at commit cee4c98e: doc/Bluetti-Open-Modbus-TCP-register-list.xlsx (SHA-256 aa7687c5be29c605d03aef1957b5f79ee52000debe564a4d1038d9efce0a1371), sheet "BalcoXX", retrieved 2026-11-23. Its README gives the transport: Modbus TCP slave, slave address 1 by default, port set on its web page (502 in the example), Modbus TCP enabled there first; the Overview adds that address 250 is the aggregate unit. Function 3 at the sheet's wire addresses; its unit column is the scale. 32-bit values are LITTLE word first: the Overview states "Register Data principle: Little-end storage; Modbus Protocol transmission principle: Big-end transmission", and bluetti-community/bluetti-modbus, the library Home Assistant reads these registers with, decodes multi-word values with word_order="little" - its real-hardware test (bluetti-registers#20) reads a live Balco 260's 50008-50009 as [64336, 0xFFFF] and decodes -1200 W, which only low-word-first gives. Left out, and why: 51001 and 51004-51008 (pack count, total SOC, SOH, status, two time estimates) answer only at unit ID 250 and read 0 at a device's own unit ID (Home Assistant core's bluetti_modbus const.py); also the warning and fault bit fields, the 64-bit serials, the version registers, the BMS protect/error/alarm words, self-consumption percent (sheet 0.01 against community 1), the int-or-uint per-phase grid power rows, and PV2-PV5 power, voltage and current, whose unit column carries the PV index while the vendor repository's issue #12 measures 1 W / 0.1 V / 0.1 A like PV1. Cross-checked against bluetti-community/bluetti-registers at 3f0707a6 (balco260.json, balco500.json): addresses, widths and access agree. Home Assistant core's bluetti_modbus names only the Balco 260 as tested, so the 500 rests on the vendor sheet and those community files. Five write registers are seeded, each with its valid values in its description.