Force H1 / H2 / H3 (Force BMS, FC0500M-40S or FC1000 controller) Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 9600
- Parity
- None
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 4096 | 5 | Manufacturer Text, two characters per register, high byte first. Reads "Pylon" on a Pylontech BMS; the source uses the leading "pylon" as its identification test. | Ascii | - | 1 | R |
| 4101 | 5 | BMS device name Text, two characters per register. Reads e.g. "Force_H2" or "Force_H3" and names the stack family; the source derives the family from this string. | Ascii | - | 1 | R |
| 4106 | 1 | BMS firmware version The source decodes the high byte as the major and the low byte as the minor version, and treats 0 as unset. | UInt16 | - | 1 | R |
| 4352 | 1 | Battery state Bits 0-2: 1 = charging, 2 = discharging, 3 = idle. The cited source documents no meaning for the remaining bits. | UInt16 | - | 1 | R |
| 4355 | 1 | Stack voltage | UInt16 | V | 0.1 | R |
| 4356 | 2 | Stack current Signed, high word at the lower address; positive while charging. | Int32 | A | 0.01 | R |
| 4358 | 1 | BMS board temperature | Int16 | °C | 0.1 | R |
| 4359 | 1 | State of charge | UInt16 | % | 1 | R |
| 4360 | 1 | Cycle count | UInt16 | - | 1 | R |
| 4361 | 1 | Charge voltage limit The charge voltage the BMS reports to the inverter. | UInt16 | V | 0.1 | R |
| 4362 | 2 | Charge current limit High word at the lower address. Signed here, because the cited source decodes the pair with its signed 32-bit helper; the newer Pylontech Force H3X source decodes the same word as unsigned, and the two disagree (see the notes and the H3X device page). | Int32 | A | 0.01 | R |
| 4364 | 1 | Discharge voltage limit The cut-off voltage the BMS reports to the inverter. | UInt16 | V | 0.1 | R |
| 4365 | 2 | Discharge current limit Signed, high word at the lower address; negative while discharging. The source reports the magnitude of this value (abs). | Int32 | A | 0.01 | R |
| 4368 | 1 | Highest cell voltage Published in millivolts; the factor converts to volts. | UInt16 | V | 0.001 | R |
| 4369 | 1 | Lowest cell voltage | UInt16 | V | 0.001 | R |
| 4370 | 1 | Cell with the highest voltage Cell index counted across the whole string, zero-based as stored; the source adds 1 for display. | UInt16 | - | 1 | R |
| 4371 | 1 | Cell with the lowest voltage Zero-based cell index across the whole string. | UInt16 | - | 1 | R |
| 4372 | 1 | Highest cell temperature | Int16 | °C | 0.1 | R |
| 4373 | 1 | Lowest cell temperature | Int16 | °C | 0.1 | R |
| 4374 | 1 | Cell with the highest temperature Zero-based cell index across the whole string. | UInt16 | - | 1 | R |
| 4375 | 1 | Cell with the lowest temperature Zero-based cell index across the whole string. | UInt16 | - | 1 | R |
| 4376 | 1 | Highest module voltage | UInt16 | V | 0.01 | R |
| 4377 | 1 | Lowest module voltage | UInt16 | V | 0.01 | R |
| 4378 | 1 | Module with the highest voltage Module index, zero-based as stored; the source adds 1 for display. | UInt16 | - | 1 | R |
| 4379 | 1 | Module with the lowest voltage Zero-based module index. | UInt16 | - | 1 | R |
| 4380 | 1 | Warmest module temperature | Int16 | °C | 0.1 | R |
| 4381 | 1 | Coldest module temperature | Int16 | °C | 0.1 | R |
| 4382 | 1 | Module with the highest temperature Zero-based module index. | UInt16 | - | 1 | R |
| 4383 | 1 | Module with the lowest temperature Zero-based module index. | UInt16 | - | 1 | R |
| 4384 | 1 | State of health | UInt16 | % | 1 | R |
| 4385 | 2 | Remaining energy Published in Wh, high word at the lower address; the factor converts to kWh. Signed here, because the cited source decodes the pair with its signed 32-bit helper; the newer Pylontech Force H3X source decodes the same word as unsigned, and the two disagree. | Int32 | kWh | 0.001 | R |
| 4387 | 2 | Energy charged today Published in Wh, high word at the lower address. The cited source calls this word a counter charged today; the newer Pylontech Force H3X source calls 0x23 a rolling counter and gives the today counters at 0x27 and 0x29 instead. The two disagree, and 0x27/0x29 are not mapped here because this source does not decode them. | Int32 | kWh | 0.001 | R |
| 4389 | 2 | Energy discharged today Published in Wh, high word at the lower address. The cited source calls this word a counter discharged today; the newer Pylontech Force H3X source calls 0x25 a rolling counter and puts the today counters at 0x27 and 0x29 instead. The two disagree, and 0x27/0x29 are not mapped here because this source does not decode them. | Int32 | kWh | 0.001 | R |
| 4395 | 2 | Energy charged, total Published in kWh as a whole number, high word at the lower address. | Int32 | kWh | 1 | R |
| 4397 | 2 | Energy discharged, total Published in kWh as a whole number, high word at the lower address. | Int32 | kWh | 1 | R |
| 4406 | 1 | Modules in series | UInt16 | - | 1 | R |
| 4407 | 1 | Cells in series Across the whole stack: a Force H1 or FH48074 module has 15 cells, an FH9637M module 30 and an H3 module 32. | UInt16 | - | 1 | R |
| 4408 | 1 | Fully charged 1 while the battery reports itself fully charged. | UInt16 | - | 1 | R |
| 5200 | 8 | Serial number 16 ASCII characters, two per register, high byte first. | Ascii | - | 1 | R |
| 5216 | 1 | Module 1 voltage First register of a per-module block: module m sits at 0x1460 + (m - 1). The blocks for modules 2 and up are left out of this map because the app has no repeating register array. | UInt16 | V | 0.01 | R |
| 5296 | 1 | Module 1 temperature First register of a per-module block: module m sits at 0x14B0 + (m - 1). | Int16 | °C | 0.1 | R |
| 5376 | 1 | Cell 1 voltage First register of a per-cell block: cell n sits at 0x1500 + (n - 1), counted across the whole string, published in millivolts. The remaining cells are left out of this map because the app has no repeating register array. | UInt16 | V | 0.001 | R |
| 6144 | 1 | Cell 1 temperature First register of a per-cell block: cell n sits at 0x1800 + (n - 1). A module shares one temperature sensor between several cells. | Int16 | °C | 0.1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Combined registers
- Stack power (calculated)Holding registers 4355 * Holding registers 4356 (W)Stack voltage times stack current, both already scaled to V and A. Positive while charging: the sign follows the current, the only signed operand. The cited source derives power the same way.
- Cell voltage spread (calculated)Holding registers 4368 - Holding registers 4369 (V)Highest minus lowest cell voltage; the source reports this spread too.
Notes
Register map from the Home Assistant integration beolink/HA-Pylontech-H1-H2-H3-Easyconf, custom_components/pylontech_easyconf/registers.py, reader.py and README.md, at commit 43476a4ff01167907c34de1b76df7313245fc064 (2026-10-28), retrieved 2026-11-23. That integration states in its own header that Pylontech publishes the Force register map to inverter makers only, and that what it carries was verified register by register on a Force H2 against the Solarman app and the inverter's own telemetry, and agrees with the Force H1/H2/H3 profile of ha-solarman, which reads the same 64-word block at base 0x1400 instead of 0x1100. So this is a secondary source. Both bases hold the same words; the mirror covers the summary block only - the identity (0x1000), serial (0x1450), module (0x1460, 0x14B0) and cell (0x1500, 0x1800) blocks are read at those fixed addresses whichever summary base answered. Transport: the BMS is a Modbus RTU server on slave 1 and answers function 3 (read holding registers) only; it is read, never written, and no write register is seeded. Access is given over its RS-485 port at 9600 baud, which the source states for a transparent RS485 converter, with 115200 possible if the BMS was reconfigured; 8N1 is the Modbus convention, not a printed value. The same BMS also answers through a Solarman logger on TCP 8899 (Solarman V5 framing, not Modbus TCP) or through a gateway, where 502 is usual but the source names 8899 for an Elfin module, so no port is declared. Every 32-bit value is high word first. Left out: the summary words the source does not name, the per-module and per-cell arrays beyond the first entry (no repeating-array type exists here), and everything else it does not decode; cell and module numbers are seeded as stored, zero-based, with the display offset stated per row. Two words the newer Force H3X source decodes differently (0x0A, 0x21) and the today counters it puts at 0x27/0x29 are disclosed on those rows.