Force H1 / H2 / H3 (Force BMS, FC0500M-40S or FC1000 controller) Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
40965
Manufacturer
Text, two characters per register, high byte first. Reads "Pylon" on a Pylontech BMS; the source uses the leading "pylon" as its identification test.
Ascii-1R
41015
BMS device name
Text, two characters per register. Reads e.g. "Force_H2" or "Force_H3" and names the stack family; the source derives the family from this string.
Ascii-1R
41061
BMS firmware version
The source decodes the high byte as the major and the low byte as the minor version, and treats 0 as unset.
UInt16-1R
43521
Battery state
Bits 0-2: 1 = charging, 2 = discharging, 3 = idle. The cited source documents no meaning for the remaining bits.
UInt16-1R
43551
Stack voltage
UInt16V0.1R
43562
Stack current
Signed, high word at the lower address; positive while charging.
Int32A0.01R
43581
BMS board temperature
Int16°C0.1R
43591
State of charge
UInt16%1R
43601
Cycle count
UInt16-1R
43611
Charge voltage limit
The charge voltage the BMS reports to the inverter.
UInt16V0.1R
43622
Charge current limit
High word at the lower address. Signed here, because the cited source decodes the pair with its signed 32-bit helper; the newer Pylontech Force H3X source decodes the same word as unsigned, and the two disagree (see the notes and the H3X device page).
Int32A0.01R
43641
Discharge voltage limit
The cut-off voltage the BMS reports to the inverter.
UInt16V0.1R
43652
Discharge current limit
Signed, high word at the lower address; negative while discharging. The source reports the magnitude of this value (abs).
Int32A0.01R
43681
Highest cell voltage
Published in millivolts; the factor converts to volts.
UInt16V0.001R
43691
Lowest cell voltage
UInt16V0.001R
43701
Cell with the highest voltage
Cell index counted across the whole string, zero-based as stored; the source adds 1 for display.
UInt16-1R
43711
Cell with the lowest voltage
Zero-based cell index across the whole string.
UInt16-1R
43721
Highest cell temperature
Int16°C0.1R
43731
Lowest cell temperature
Int16°C0.1R
43741
Cell with the highest temperature
Zero-based cell index across the whole string.
UInt16-1R
43751
Cell with the lowest temperature
Zero-based cell index across the whole string.
UInt16-1R
43761
Highest module voltage
UInt16V0.01R
43771
Lowest module voltage
UInt16V0.01R
43781
Module with the highest voltage
Module index, zero-based as stored; the source adds 1 for display.
UInt16-1R
43791
Module with the lowest voltage
Zero-based module index.
UInt16-1R
43801
Warmest module temperature
Int16°C0.1R
43811
Coldest module temperature
Int16°C0.1R
43821
Module with the highest temperature
Zero-based module index.
UInt16-1R
43831
Module with the lowest temperature
Zero-based module index.
UInt16-1R
43841
State of health
UInt16%1R
43852
Remaining energy
Published in Wh, high word at the lower address; the factor converts to kWh. Signed here, because the cited source decodes the pair with its signed 32-bit helper; the newer Pylontech Force H3X source decodes the same word as unsigned, and the two disagree.
Int32kWh0.001R
43872
Energy charged today
Published in Wh, high word at the lower address. The cited source calls this word a counter charged today; the newer Pylontech Force H3X source calls 0x23 a rolling counter and gives the today counters at 0x27 and 0x29 instead. The two disagree, and 0x27/0x29 are not mapped here because this source does not decode them.
Int32kWh0.001R
43892
Energy discharged today
Published in Wh, high word at the lower address. The cited source calls this word a counter discharged today; the newer Pylontech Force H3X source calls 0x25 a rolling counter and puts the today counters at 0x27 and 0x29 instead. The two disagree, and 0x27/0x29 are not mapped here because this source does not decode them.
Int32kWh0.001R
43952
Energy charged, total
Published in kWh as a whole number, high word at the lower address.
Int32kWh1R
43972
Energy discharged, total
Published in kWh as a whole number, high word at the lower address.
Int32kWh1R
44061
Modules in series
UInt16-1R
44071
Cells in series
Across the whole stack: a Force H1 or FH48074 module has 15 cells, an FH9637M module 30 and an H3 module 32.
UInt16-1R
44081
Fully charged
1 while the battery reports itself fully charged.
UInt16-1R
52008
Serial number
16 ASCII characters, two per register, high byte first.
Ascii-1R
52161
Module 1 voltage
First register of a per-module block: module m sits at 0x1460 + (m - 1). The blocks for modules 2 and up are left out of this map because the app has no repeating register array.
UInt16V0.01R
52961
Module 1 temperature
First register of a per-module block: module m sits at 0x14B0 + (m - 1).
Int16°C0.1R
53761
Cell 1 voltage
First register of a per-cell block: cell n sits at 0x1500 + (n - 1), counted across the whole string, published in millivolts. The remaining cells are left out of this map because the app has no repeating register array.
UInt16V0.001R
61441
Cell 1 temperature
First register of a per-cell block: cell n sits at 0x1800 + (n - 1). A module shares one temperature sensor between several cells.
Int16°C0.1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Combined registers

  • Stack power (calculated)Holding registers 4355 * Holding registers 4356 (W)Stack voltage times stack current, both already scaled to V and A. Positive while charging: the sign follows the current, the only signed operand. The cited source derives power the same way.
  • Cell voltage spread (calculated)Holding registers 4368 - Holding registers 4369 (V)Highest minus lowest cell voltage; the source reports this spread too.

Notes

Register map from the Home Assistant integration beolink/HA-Pylontech-H1-H2-H3-Easyconf, custom_components/pylontech_easyconf/registers.py, reader.py and README.md, at commit 43476a4ff01167907c34de1b76df7313245fc064 (2026-10-28), retrieved 2026-11-23. That integration states in its own header that Pylontech publishes the Force register map to inverter makers only, and that what it carries was verified register by register on a Force H2 against the Solarman app and the inverter's own telemetry, and agrees with the Force H1/H2/H3 profile of ha-solarman, which reads the same 64-word block at base 0x1400 instead of 0x1100. So this is a secondary source. Both bases hold the same words; the mirror covers the summary block only - the identity (0x1000), serial (0x1450), module (0x1460, 0x14B0) and cell (0x1500, 0x1800) blocks are read at those fixed addresses whichever summary base answered. Transport: the BMS is a Modbus RTU server on slave 1 and answers function 3 (read holding registers) only; it is read, never written, and no write register is seeded. Access is given over its RS-485 port at 9600 baud, which the source states for a transparent RS485 converter, with 115200 possible if the BMS was reconfigured; 8N1 is the Modbus convention, not a printed value. The same BMS also answers through a Solarman logger on TCP 8899 (Solarman V5 framing, not Modbus TCP) or through a gateway, where 502 is usual but the source names 8899 for an Elfin module, so no port is declared. Every 32-bit value is high word first. Left out: the summary words the source does not name, the per-module and per-cell arrays beyond the first entry (no repeating-array type exists here), and everything else it does not decode; cell and module numbers are seeded as stored, zero-based, with the display offset stated per row. Two words the newer Force H3X source decodes differently (0x0A, 0x21) and the today counters it puts at 0x27/0x29 are disclosed on those rows.