  "spec_version": 1,
  "slug": "pylontech-force-h1-h2-h3",
  "manufacturer": "Pylontech",
  "model": "Force H1 / H2 / H3 (Force BMS, FC0500M-40S or FC1000 controller)",
  "category": "Home battery",
  "supplier_url": "https://en.pylontech.com.cn/products/forceh3",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 9600,
      "parity": "None",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [],
  "holding_registers": [
    {
      "address": 4096,
      "count": 5,
      "name": "Manufacturer",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Text, two characters per register, high byte first. Reads \"Pylon\" on a Pylontech BMS; the source uses the leading \"pylon\" as its identification test."
    },
    {
      "address": 4101,
      "count": 5,
      "name": "BMS device name",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Text, two characters per register. Reads e.g. \"Force_H2\" or \"Force_H3\" and names the stack family; the source derives the family from this string."
    },
    {
      "address": 4106,
      "count": 1,
      "name": "BMS firmware version",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "The source decodes the high byte as the major and the low byte as the minor version, and treats 0 as unset."
    },
    {
      "address": 4352,
      "count": 1,
      "name": "Battery state",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Bits 0-2: 1 = charging, 2 = discharging, 3 = idle. The cited source documents no meaning for the remaining bits."
    },
    {
      "address": 4355,
      "count": 1,
      "name": "Stack voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4356,
      "count": 2,
      "name": "Stack current",
      "data_type": "Int32",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Signed, high word at the lower address; positive while charging."
    },
    {
      "address": 4358,
      "count": 1,
      "name": "BMS board temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4359,
      "count": 1,
      "name": "State of charge",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4360,
      "count": 1,
      "name": "Cycle count",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4361,
      "count": 1,
      "name": "Charge voltage limit",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "The charge voltage the BMS reports to the inverter."
    },
    {
      "address": 4362,
      "count": 2,
      "name": "Charge current limit",
      "data_type": "Int32",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "High word at the lower address. Signed here, because the cited source decodes the pair with its signed 32-bit helper; the newer Pylontech Force H3X source decodes the same word as unsigned, and the two disagree (see the notes and the H3X device page)."
    },
    {
      "address": 4364,
      "count": 1,
      "name": "Discharge voltage limit",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "The cut-off voltage the BMS reports to the inverter."
    },
    {
      "address": 4365,
      "count": 2,
      "name": "Discharge current limit",
      "data_type": "Int32",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Signed, high word at the lower address; negative while discharging. The source reports the magnitude of this value (abs)."
    },
    {
      "address": 4368,
      "count": 1,
      "name": "Highest cell voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Published in millivolts; the factor converts to volts."
    },
    {
      "address": 4369,
      "count": 1,
      "name": "Lowest cell voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4370,
      "count": 1,
      "name": "Cell with the highest voltage",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Cell index counted across the whole string, zero-based as stored; the source adds 1 for display."
    },
    {
      "address": 4371,
      "count": 1,
      "name": "Cell with the lowest voltage",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Zero-based cell index across the whole string."
    },
    {
      "address": 4372,
      "count": 1,
      "name": "Highest cell temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4373,
      "count": 1,
      "name": "Lowest cell temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4374,
      "count": 1,
      "name": "Cell with the highest temperature",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Zero-based cell index across the whole string."
    },
    {
      "address": 4375,
      "count": 1,
      "name": "Cell with the lowest temperature",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Zero-based cell index across the whole string."
    },
    {
      "address": 4376,
      "count": 1,
      "name": "Highest module voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4377,
      "count": 1,
      "name": "Lowest module voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4378,
      "count": 1,
      "name": "Module with the highest voltage",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Module index, zero-based as stored; the source adds 1 for display."
    },
    {
      "address": 4379,
      "count": 1,
      "name": "Module with the lowest voltage",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Zero-based module index."
    },
    {
      "address": 4380,
      "count": 1,
      "name": "Warmest module temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4381,
      "count": 1,
      "name": "Coldest module temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4382,
      "count": 1,
      "name": "Module with the highest temperature",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Zero-based module index."
    },
    {
      "address": 4383,
      "count": 1,
      "name": "Module with the lowest temperature",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Zero-based module index."
    },
    {
      "address": 4384,
      "count": 1,
      "name": "State of health",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4385,
      "count": 2,
      "name": "Remaining energy",
      "data_type": "Int32",
      "units": "kWh",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Published in Wh, high word at the lower address; the factor converts to kWh. Signed here, because the cited source decodes the pair with its signed 32-bit helper; the newer Pylontech Force H3X source decodes the same word as unsigned, and the two disagree."
    },
    {
      "address": 4387,
      "count": 2,
      "name": "Energy charged today",
      "data_type": "Int32",
      "units": "kWh",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Published in Wh, high word at the lower address. The cited source calls this word a counter charged today; the newer Pylontech Force H3X source calls 0x23 a rolling counter and gives the today counters at 0x27 and 0x29 instead. The two disagree, and 0x27/0x29 are not mapped here because this source does not decode them."
    },
    {
      "address": 4389,
      "count": 2,
      "name": "Energy discharged today",
      "data_type": "Int32",
      "units": "kWh",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Published in Wh, high word at the lower address. The cited source calls this word a counter discharged today; the newer Pylontech Force H3X source calls 0x25 a rolling counter and puts the today counters at 0x27 and 0x29 instead. The two disagree, and 0x27/0x29 are not mapped here because this source does not decode them."
    },
    {
      "address": 4395,
      "count": 2,
      "name": "Energy charged, total",
      "data_type": "Int32",
      "units": "kWh",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Published in kWh as a whole number, high word at the lower address."
    },
    {
      "address": 4397,
      "count": 2,
      "name": "Energy discharged, total",
      "data_type": "Int32",
      "units": "kWh",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Published in kWh as a whole number, high word at the lower address."
    },
    {
      "address": 4406,
      "count": 1,
      "name": "Modules in series",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 4407,
      "count": 1,
      "name": "Cells in series",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Across the whole stack: a Force H1 or FH48074 module has 15 cells, an FH9637M module 30 and an H3 module 32."
    },
    {
      "address": 4408,
      "count": 1,
      "name": "Fully charged",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "1 while the battery reports itself fully charged."
    },
    {
      "address": 5200,
      "count": 8,
      "name": "Serial number",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "16 ASCII characters, two per register, high byte first."
    },
    {
      "address": 5216,
      "count": 1,
      "name": "Module 1 voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "First register of a per-module block: module m sits at 0x1460 + (m - 1). The blocks for modules 2 and up are left out of this map because the app has no repeating register array."
    },
    {
      "address": 5296,
      "count": 1,
      "name": "Module 1 temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "First register of a per-module block: module m sits at 0x14B0 + (m - 1)."
    },
    {
      "address": 5376,
      "count": 1,
      "name": "Cell 1 voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "First register of a per-cell block: cell n sits at 0x1500 + (n - 1), counted across the whole string, published in millivolts. The remaining cells are left out of this map because the app has no repeating register array."
    },
    {
      "address": 6144,
      "count": 1,
      "name": "Cell 1 temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "First register of a per-cell block: cell n sits at 0x1800 + (n - 1). A module shares one temperature sensor between several cells."
    }
  ],
  "combined_registers": [
    {
      "id": "stack-power-calculated",
      "label": "Stack power (calculated)",
      "operator": "*",
      "operand_a": {
        "register_type": "holding_registers",
        "register_address": 4355
      },
      "operand_b": {
        "register_type": "holding_registers",
        "register_address": 4356
      },
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "description": "Stack voltage times stack current, both already scaled to V and A. Positive while charging: the sign follows the current, the only signed operand. The cited source derives power the same way."
    },
    {
      "id": "cell-voltage-spread-calculated",
      "label": "Cell voltage spread (calculated)",
      "operator": "-",
      "operand_a": {
        "register_type": "holding_registers",
        "register_address": 4368
      },
      "operand_b": {
        "register_type": "holding_registers",
        "register_address": 4369
      },
      "units": "V",
      "scale_factor": 1,
      "offset": 0,
      "description": "Highest minus lowest cell voltage; the source reports this spread too."
    }
  ],
  "notes": "Register map from the Home Assistant integration beolink/HA-Pylontech-H1-H2-H3-Easyconf, custom_components/pylontech_easyconf/registers.py, reader.py and README.md, at commit 43476a4ff01167907c34de1b76df7313245fc064 (2026-10-28), retrieved 2026-11-23. That integration states in its own header that Pylontech publishes the Force register map to inverter makers only, and that what it carries was verified register by register on a Force H2 against the Solarman app and the inverter's own telemetry, and agrees with the Force H1/H2/H3 profile of ha-solarman, which reads the same 64-word block at base 0x1400 instead of 0x1100. So this is a secondary source. Both bases hold the same words; the mirror covers the summary block only - the identity (0x1000), serial (0x1450), module (0x1460, 0x14B0) and cell (0x1500, 0x1800) blocks are read at those fixed addresses whichever summary base answered. Transport: the BMS is a Modbus RTU server on slave 1 and answers function 3 (read holding registers) only; it is read, never written, and no write register is seeded. Access is given over its RS-485 port at 9600 baud, which the source states for a transparent RS485 converter, with 115200 possible if the BMS was reconfigured; 8N1 is the Modbus convention, not a printed value. The same BMS also answers through a Solarman logger on TCP 8899 (Solarman V5 framing, not Modbus TCP) or through a gateway, where 502 is usual but the source names 8899 for an Elfin module, so no port is declared. Every 32-bit value is high word first. Left out: the summary words the source does not name, the per-module and per-cell arrays beyond the first entry (no repeating-array type exists here), and everything else it does not decode; cell and module numbers are seeded as stored, zero-based, with the display offset stated per row. Two words the newer Force H3X source decodes differently (0x0A, 0x21) and the today counters it puts at 0x27/0x29 are disclosed on those rows."
}