XG series grid-tied inverters (XG3-70 kW, XG100-136 kW) and XD series hybrid inverter (XD1-12 kW) Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
123051
RS-485 protocol
0 = MODBUS; other values are retained and unused.
UInt16-1R
123061
RS-485 address
Slave address 1-247, kept after power-off.
UInt16-1RW
123071
RS-485 baud rate
Baud rate: 0 = 9600 bps, 1 = 115200 bps.
UInt16-1RW
123081
Date, year and month
Year in the high byte (20-99), month in the low byte (1-12).
UInt16-1RW
123091
Date, day and hour
Day in the high byte (1-31), hour in the low byte (0-23).
UInt16-1RW
123101
Date, minute and second
Minute in the high byte (0-59), second in the low byte (0-59).
UInt16-1RW
123111
Date, weekday
UInt16-1R
123121
Remote shutdown command
Write 0xAAAA to shut down, 0x5555 to start, 0xBBBB to shut down without cutting the EPS output; any other value does nothing.
UInt16-1RW
123131
Percent of active power setting
Active power limit, 0-1000 raw in 0.1 % steps (0-100.0 %), kept after power-off.
UInt16%0.1RW
123141
Reactive power control mode
Reactive power control mode: 0 power-factor control, 1 reactive-power percentage, 2 Q(V) curve, 3 active-power priority, 4 fixed/default PF curve, 5 P-PF curve; kept after power-off (the range column says 0-2 while the remark lists 0-5). The document lists it R/W, but it selects the grid-support strategy, so it is read-only here.
UInt16-1R
123151
Power factor setting
Power factor setpoint in 0.001 steps: +800 to +1000 and -800 to -1000 map to 0.8-1.0, the sign choosing the direction; kept after power-off. Listed R/W by the document, read-only here because the power factor is a grid-support setting.
Int16-0.001R
123161
Reactive power setting
Reactive power setpoint in 0.1 % steps, -660 to +660 (+-66 %), described by the document as -60 % to 60 %; kept after power-off. Listed R/W by the document, read-only here because it is a grid-support setting.
Int16%0.1R
123171
LCD language
Display language: 0 simplified Chinese, 1 English, 2 traditional Chinese, 3 Italian, 4 Korean, 5 German; kept after power-off.
UInt16-1RW
123211
Power setting
Power setpoint in 0.1 kW steps, 10-1360 raw; the document gives 567 = 56.7 kW and 1200 = 120 kW for an XG100-136 kW unit; kept after power-off. Listed R/W by the document, read-only here because the meaning of the setpoint is tied to the unit's rating class.
UInt16kW0.1R
123221
PV input mode
Input mode: 0 independent inputs, 1 parallel inputs, 2 DC source (aging) mode; kept after power-off. Listed R/W by the document, read-only here because the DC-source (aging) mode is a factory test mode.
UInt16-1R
143361
Software version identifier (high 16 bits)
ASCII code of the high word of the software version identifier.
UInt16-1R
143371
Software version identifier (lower 16 bits)
ASCII code of the low word of the software version identifier.
UInt16-1R
143381
Software version number 1
Main DSP version, 1-9999: units and tens carry the test version, thousands and hundreds the release version.
UInt16-1R
143391
Software version number 2
Auxiliary DSP version number, 1-9999.
UInt16-1R
143401
Software version number 3
CPLD version number, 1-9999.
UInt16-1R
143411
Software version number 4
ARM version number, 1-9999.
UInt16-1R
143421
Inverter working status
Working mode: 0 initialization, 1 wait, 2 on-grid, 3 fault, 4 burning program, 5 off-grid, 6 bypass, 7 PID repair, 8 PID inhibition, 9 snow removal, 10 SVG. The range column says 0-3 while the remark lists 0-10.
UInt16-1R
143431
Main alarm code
Main alarm code; the document refers to its XG/XD alarm and fault code tables.
UInt16-1R
143441
Sub-alarm code
UInt16-1R
143451
Main fault code
UInt16-1R
143461
Sub-fault code
UInt16-1R
143472
Alarm bit
UInt32-1R
143492
Fault bit
UInt32-1R
143511
PBUS voltage
UInt16V0.1R
143521
NBUS voltage
UInt16V0.1R
143531
Grid line voltage RS
UInt16V0.1R
143541
Grid line voltage ST
UInt16V0.1R
143551
Grid line voltage TR
UInt16V0.1R
143561
Grid phase voltage R
UInt16V0.1R
143571
Grid phase voltage S
UInt16V0.1R
143581
Grid phase voltage T
UInt16V0.1R
143591
Grid current R phase
Int16A0.01R
143601
Grid current S phase
Int16A0.01R
143611
Grid current T phase
Int16A0.01R
143621
Grid frequency RS
UInt16Hz0.01R
143631
Countdown to grid connection
UInt16s1R
143641
Load power
UInt16kW0.1R
143652
Active power
Int32W0.1R
143672
Reactive power
Int32VAR0.1R
143691
Power factor
Power factor in 0.001 steps: 800 is 0.8, -800 is -0.8.
Int16-0.001R
143701
Inverter module R temperature
Range -400 to 1400 raw, i.e. -40.0 °C to 140.0 °C.
Int16°C0.1R
143711
Inverter module S temperature
Range -400 to 1400 raw, i.e. -40.0 °C to 140.0 °C.
Int16°C0.1R
143721
Inverter module T temperature
Range -400 to 1400 raw, i.e. -40.0 °C to 140.0 °C.
Int16°C0.1R
143731
Ambient temperature
Range -400 to 1400 raw, i.e. -40.0 °C to 140.0 °C.
Int16°C0.1R
143741
Radiator temperature
Range -400 to 1400 raw, i.e. -40.0 °C to 140.0 °C.
Int16°C0.1R
143752
Meter power
Int32W0.1R
143771
Leakage current
Int16mA0.1R
143782
Derating power
UInt32W0.1R
143801
Derating mode
Derating reason: 0 none, 1 high voltage, 2 BST high temperature, 3 inverter, 4 ambient temperature, 5 power setting, 6 MPPT reset, 7 reactive power, 8 loading slope, 9 AC high voltage, 10 ATE adjust, 11 single-inverter anti-reflux, 12 multi-inverter anti-reflux (the printed list stops there).
UInt16-1R
143812
Power generation time
32-bit value: high word 0x382D, low word 0x382E, scaling 0.5 s.
UInt32s0.5R
143831
PV energy today
UInt16kWh0.1R
143842
PV energy total
32-bit value: high word 0x3830, low word 0x3831, scaling 0.1 kWh.
UInt32kWh0.1R
143861
DC current R phase
Int16mA0.1R
143871
DC current S phase
Int16mA0.1R
143881
DC current T phase
Int16mA0.1R
143891
DC insulation resistance
UInt16kΩ1R
143901
PV1 voltage
UInt16V0.1R
143911
PV1 current
Int16A0.01R
143921
PV2 voltage
UInt16V0.1R
143931
PV2 current
Int16A0.01R
143941
PV3 voltage
UInt16V0.1R
143951
PV3 current
Int16A0.01R
143961
PV4 voltage
UInt16V0.1R
143971
PV4 current
Int16A0.01R
143981
PV5 voltage
UInt16V0.1R
143991
PV5 current
Int16A0.01R
144001
PV6 voltage
UInt16V0.1R
144011
PV6 current
Int16A0.01R
144021
PV7 voltage
UInt16V0.1R
144031
PV7 current
Int16A0.01R
144041
PV8 voltage
UInt16V0.1R
144051
PV8 current
Int16A0.01R
144061
PV9 voltage
UInt16V0.1R
144071
PV9 current
Int16A0.01R
144081
PV10 voltage
UInt16V0.1R
144091
PV10 current
Int16A0.01R
144101
PV11 voltage
UInt16V0.1R
144111
PV11 current
Int16A0.01R
144121
PV12 voltage
UInt16V0.1R
144131
PV12 current
Int16A0.01R
144141
String 1 current
Int16A0.01R
144151
String 3 current
Int16A0.01R
144161
String 5 current
Int16A0.01R
144171
String 7 current
Int16A0.01R
144181
String 9 current
Int16A0.01R
144191
String 11 current
Int16A0.01R
144201
String 13 current
Int16A0.01R
144211
String 15 current
Int16A0.01R
144221
String 17 current
Int16A0.01R
144231
String 19 current
Int16A0.01R
144241
String 21 current
Int16A0.01R
144251
String 23 current
Int16A0.01R
144501
Internal hardware fault bits
Bit field: bit 0 external flash fault, bit 1 EEPROM read fault, bit 2 EEPROM write fault, bit 3 GFCI self-test failure, bits 4-15 reserved.
UInt16-1R
144511
String 2 current
Int16A0.01R
144521
String 4 current
Int16A0.01R
144531
String 6 current
Int16A0.01R
144541
String 8 current
Int16A0.01R
144551
String 10 current
Int16A0.01R
144561
String 12 current
Int16A0.01R
144571
String 14 current
Int16A0.01R
144581
String 16 current
Int16A0.01R
144591
String 18 current
Int16A0.01R
144601
String 20 current
Int16A0.01R
144611
String 22 current
Int16A0.01R
144621
String 24 current
Int16A0.01R
144632
Large-inverter active power
Manufacturer's special data (100-136kW)
Int32W0.1R
144651
Inverter model
UInt16-1R
144661
Inverter efficiency
Efficiency in 0.1 % steps, 1-1000; the document notes a default of 0 for one OEM.
UInt16%0.1R
144671
RTC state
RTC state: 1 configured, 0 not configured.
UInt16-1R
144681
Meter communication quality
UInt16%0.1R
144811
CT current
Int16A0.01R
144821
Load energy today
UInt16kWh0.1R
144832
Load energy total
32-bit value: high word 0x3893, low word 0x3894, scaling 0.1 kWh.
UInt32kWh0.1R
144851
Energy exported today
UInt16kWh0.1R
144862
Energy exported total
32-bit value: high word 0x3896, low word 0x3897, scaling 0.1 kWh.
UInt32kWh0.1R
144881
Energy imported today
UInt16kWh0.1R
144892
Energy imported total
32-bit value: high word 0x3899, low word 0x389a, scaling 0.1 kWh.
UInt32kWh0.1R
144911
Battery charge energy today
UInt16kWh0.1R
144922
Battery charge energy total
32-bit value: high word 0x389c, low word 0x389d, scaling 0.1 kWh.
UInt32kWh0.1R
144941
Battery discharge energy today
UInt16kWh0.1R
144952
Battery discharge energy total
32-bit value: high word 0x389f, low word 0x38a0, scaling 0.1 kWh.
UInt32kWh0.1R
145342
R phase meter power
32-bit value, high word at 0x38C6, low word at 0x38C7.
Int32W0.1R
145362
S phase meter power
32-bit value, high word at 0x38C8, low word at 0x38C9.
Int32W0.1R
145382
T phase meter power
32-bit value, high word at 0x38CA, low word at 0x38CB.
Int32W0.1R
145402
Daily peak power
32-bit value, high word at 0x38CC, low word at 0x38CD.
UInt32W1R
145482
AC-side input and output power
32-bit value, high word at 0x38D4, low word at 0x38D5; + is charging power, - is discharging power.
Int32W0.1R
145642
PV total power (flow diagram)
32-bit value, high word at 0x38E4, low word at 0x38E5; the document labels this block the new energy-flow version.
UInt32W1R
145662
Load power (flow diagram)
32-bit value, high word at 0x38E6, low word at 0x38E7; the document labels this block the new energy-flow version.
UInt32W1R
145921
Energy-storage fault bit 0
First of the eight energy-storage fault words; the document prints no bit list for it.
UInt16-1R
145931
Energy-storage fault bit 1
UInt16-1R
145941
Energy-storage fault bit 2
UInt16-1R
145951
Energy-storage fault bit 3
UInt16-1R
145961
Energy-storage fault bit 4
UInt16-1R
145971
Energy-storage fault bit 5
UInt16-1R
145981
Energy-storage fault bit 6
UInt16-1R
145991
Energy-storage fault bit 7
UInt16-1R
146002
Battery power
Positive is charging power, negative is discharging power.
Int32W0.1R
146021
Battery voltage
UInt16V0.1R
146031
Battery current
Int16A0.1R
146042
User load active power R phase
Int32W0.1R
146062
User load active power S phase
Int32W0.1R
146082
User load active power T phase
Int32W0.1R
146102
User load active power total
Int32W0.1R
146122
Grid active power R phase
Int32W0.1R
146142
Grid active power S phase
Int32W0.1R
146162
Grid active power T phase
Int32W0.1R
146182
Grid active power total
Int32W0.1R
146202
Local load active power R phase
Int32W0.1R
146222
Local load active power S phase
Int32W0.1R
146242
Local load active power T phase
Int32W0.1R
146262
Local load active power total
Int32W0.1R
146281
Battery charge/discharge state
0 neither charging nor discharging, 1 charging, 2 discharging.
UInt16-1R
146291
Bus voltage 2
LLC side voltage
UInt16V0.1R
146301
EPS frequency
UInt16Hz0.01R
146311
EPS output voltage R
UInt16V0.1R
146321
EPS output current R
UInt16A0.01R
146332
EPS output power R
Int32W0.1R
146351
EPS output voltage S
UInt16V0.1R
146361
EPS output current S
UInt16A0.01R
146372
EPS output power S
Int32W0.1R
146391
EPS output voltage T
UInt16V0.1R
146401
EPS output current T
UInt16A0.01R
146412
EPS output power T
Int32W0.1R
146432
EPS output power total
Int32W0.1R
146471
Battery charge CV voltage
Recommended charging voltage, PCS cannot exceed this value
UInt16V0.1R
146481
Battery discharge cut-off voltage
Discharge end voltage, PCS cannot exceed this value
UInt16V0.1R
146491
Battery maximum charge current
Maximum charging current, PCS cannot exceed this value
UInt16A0.1R
146501
Battery maximum discharge current
Maximum discharge current, PCS cannot exceed this value
UInt16A0.1R
146511
Battery SOC
Range 0-100; the document prints no data-type cell for this row.
UInt16%1R
146521
Battery SOH
Range 0-100; the document prints no data-type cell for this row.
UInt16%1R
146531
Battery charge inhibited
Range 0-1.
UInt16-1R
146541
Battery discharge inhibited
Range 0-1.
UInt16-1R
146551
Battery module status byte 1
0 normal, 1 prompt, 2 warning, 3 alarm, 4 fault.
UInt16-1R
146561
Battery warning status
Warning bytes 1-2, high byte first.
UInt16-1R
146571
Battery alarm status
Alarm bytes 1-2, high byte first.
UInt16-1R
146581
Battery fault status 1
Fault bytes 1-2, high byte first.
UInt16-1R
146591
Battery fault status 2
Fault bytes 3-4, high byte first.
UInt16-1R
146601
Maximum cell voltage
Range 0-5000.
UInt16mV1R
146611
Minimum cell voltage
Range 0-5000.
UInt16mV1R
146621
Maximum cell temperature
Range -400-1500, i.e. -40.0 °C to 150.0 °C.
Int16°C0.1R
146631
Minimum cell temperature
Printed range -400-11500, i.e. -40.0 °C to 1150.0 °C.
Int16°C0.1R
146641
Maximum cell voltage cell ID
UInt16-1R
146651
Minimum cell voltage cell ID
UInt16-1R
146661
Maximum cell temperature cell ID
UInt16-1R
146671
Minimum cell temperature cell ID
UInt16-1R
146691
Battery temperature
UInt16°C0.1R
146781
Battery charge/discharge cycles
Charge/discharge cycles counted by the BMS.
UInt16-1R
146791
Battery 1 voltage sampled by DSP
Battery 1 voltage measured by the DSP.
UInt16V0.1R
146971
Total battery current
Int16A0.1R
147042
Battery 2 power
+ is charging power, - is discharging power, battery 2
Int32W0.1R
147061
Battery 2 voltage
UInt16V0.1R
147071
Battery 2 current
Int16A0.1R
147081
Battery 2 charge/discharge state
0 neither charging nor discharging, 1 charging, 2 discharging.
UInt16-1R
147091
Battery 2 voltage sampled by DSP
Battery 2 voltage measured by the DSP.
UInt16V0.1R
147121
Battery 2 CHG CV voltage
Recommended charging voltage, PCS cannot exceed this value
UInt16V0.1R
147131
Battery 2 DSG Cut voltage
Discharge end voltage, PCS cannot exceed this value
UInt16V0.1R
147141
Battery 2 MAX charge current
Maximum charging current, PCS cannot exceed this value
UInt16A0.1R
147151
Battery 2 MAX discharge current
Maximum discharge current, PCS cannot exceed this value
UInt16A0.1R
151051
PV1 power
UInt16W0.1R
151061
PV2 power
UInt16W0.1R
151071
PV3 power
UInt16W0.1R
151081
PV4 power
UInt16W0.1R
151091
PV5 power
UInt16W0.1R
151101
PV6 power
UInt16W0.1R
151111
PV7 power
UInt16W0.1R
151121
PV8 power
UInt16W0.1R
151131
PV9 power
UInt16W0.1R
151141
PV10 power
UInt16W0.1R
151151
PV11 power
UInt16W0.1R
151161
PV12 power
UInt16W0.1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

INVT Solar RS485 Communication Protocol V1.38, 16-07-2024, 60 pages: the Modbus RTU protocol for the XG grid-tied inverters (single- and three-phase) and the XD single-phase hybrid inverter. INVT serves brochures at www.invt-solar.com/downloads.html but not this file, so the copy read is the vendor document mirrored at https://github.com/user-attachments/files/17638743/INVT.Modbus.July.2024.pdf, SHA-256 d7ddf2c46c52f9862a05cbf71e22253e27a983bca21141f6759aee129f928998, retrieved 2026-11-23 (MIRROR-SOURCED). Addresses are the printed hex wire addresses (regions given as 0x3000-0x307D, 0x3100-0x317D and 0x3800-0x397D), so the map is zero_based; 0x3800 is stored as 32768. Framing is section 1: fixed 9600 8N1, function codes 03 and 10. No factory slave address is printed (set from the keypad, 1-247), so unit 1 is a placeholder. 32-bit totals print as a high word then a low word at consecutive addresses, so HighFirst is the documented order; rows the document prints as one 2-register value (e.g. 0x381D) carry the same big-endian order. Seeded: run information 0x3800-0x38A0 and the meter/flow powers 0x38C6-0x38E6, the XD storage region 0x3900-0x397D, PV1-PV12 power 0x3B01-0x3B0C, and eight settings that print both effect and valid values. Five more settings it prints (0x301A-0x301C grid support, 0x3021 rating-class setpoint, 0x3022 aging mode) are seeded read-only. Left out: 0x301E-0x3020 and 0x302E-0x317D (remarks truncated or grid thresholds), the auto-test block 0x38A1-0x38C5, the 0.01 kWh duplicates at 0x38D6-0x38DA, the Chinese-only meter-2 rows, per-order harmonics 0x3B3B-0x3B77, protection points and fan speeds 0x3B0D-0x3B23, snow removal, fault history, I/V curves, waveform buffers, AFCI history, scan status, debug words and the Battery Name ASCII block. The Solarman definition invt_xd-tl.yaml reads 0x3817-0x3819 as 0.1 mA and 0.01 A, i.e. the same 0.01 A the document prints, so no scale conflict remains. No source claims a hardware test.