All devices

Growatt · Inverter/charger

OffGrid SPF 3-5K off-grid inverter/charger Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
System run state
0 standby, 1 PV and grid combine discharge, 2 discharge, 3 fault, 4 flash, 5 PV charge, 6 AC charge, 7 combine charge, 8 combine charge and bypass, 9 PV charge and bypass, 10 AC charge and bypass, 11 bypass, 12 PV charge and discharge.
UInt16-1R
11
PV1 voltage
UInt16V0.1R
21
PV2 voltage
UInt16V0.1R
32
PV1 charge power
High word at register 3, low word at 4. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32W0.1R
52
PV2 charge power
High word at register 5, low word at 6. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32W0.1R
71
Buck 1 current
UInt16A0.1R
81
Buck 2 current
UInt16A0.1R
92
Output active power
High word at register 9, low word at 10. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32W0.1R
112
Output apparent power
High word at register 11, low word at 12. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32VA0.1R
132
AC charge power
High word at register 13, low word at 14. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32W0.1R
152
AC charge apparent power
High word at register 15, low word at 16. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32VA0.1R
171
Battery voltage
The document labels this row M3.
UInt16V0.01R
181
Battery state of charge
Document range 0-100.
UInt16%1R
191
Bus voltage
UInt16V0.1R
201
AC input voltage
UInt16V0.1R
211
AC input frequency
The document's scale cell for this row is split across the page break; the continuation prints 0.01 Hz.
UInt16Hz0.01R
221
AC output voltage
UInt16V0.1R
231
AC output frequency
UInt16Hz0.01R
241
Output DC voltage
UInt16V0.1R
251
Inverter temperature
UInt16°C0.1R
261
DC-DC temperature
UInt16°C0.1R
271
Load percent
Document range 0-1000 raw.
UInt16%0.1R
281
Battery-port voltage (DSP)
UInt16V0.01R
291
Battery-bus voltage (DSP)
UInt16V0.01R
302
Total work time
High word at register 30, low word at 31; the document's 0.5 s scale cell is split across the page break and its continuation prints S. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32s0.5R
321
Buck 1 temperature
UInt16°C0.1R
331
Buck 2 temperature
UInt16°C0.1R
341
Output current
UInt16A0.1R
351
Inverter current
UInt16A0.1R
362
AC input power
High word at register 36, low word at 37. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32W0.1R
382
AC input apparent power
High word at register 38, low word at 39. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32VA0.1R
401
Fault bits
Bit field; the document names the row and its bit table is not part of this map section.
Hex-1R
411
Warning bits
Bit field, low word.
Hex-1R
421
Warning bits, high word
Bit field, high word.
Hex-1R
431
Warning value
The document gives no unit or decode for this row.
UInt16-1R
482
PV1 energy today
High word at register 48, low word at 49. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32kWh0.1R
502
PV1 energy total
High word at register 50, low word at 51. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32kWh0.1R
522
PV2 energy today
High word at register 52, low word at 53. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32kWh0.1R
542
PV2 energy total
High word at register 54, low word at 55. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32kWh0.1R
562
AC charge energy today
High word at register 56, low word at 57. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32kWh0.1R
582
AC charge energy total
High word at register 58, low word at 59. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32kWh0.1R
602
Battery discharge energy today
High word at register 60, low word at 61. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32kWh0.1R
622
Battery discharge energy total
High word at register 62, low word at 63. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32kWh0.1R
642
AC discharge energy today
High word at register 64, low word at 65. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32kWh0.1R
662
AC discharge energy total
High word at register 66, low word at 67. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32kWh0.1R
681
AC charge battery current
The document's scale cell for this row continues on the next page, which prints A.
UInt16A0.1R
692
AC discharge power
High word at register 69, low word at 70. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32W0.1R
712
AC discharge apparent power
High word at register 71, low word at 72. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32VA0.1R
732
Battery discharge power
High word at register 73, low word at 74. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32W0.1R
752
Battery discharge apparent power
High word at register 75, low word at 76. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
UInt32VA0.1R
772
Battery power
High word at register 77, low word at 78. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Positive while the battery discharges, negative while it charges, as the document prints. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value.
Int32W0.1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Growatt "OffGrid SPF5000 Modbus RS485&RS232 RTU Protocol", title block V0.14 dated 2020-10-16 (the distributor file name carries 2021-04-20 and the revision table adds a V0.15 line), 24 pages, mirror drive.google.com/uc?export=download&id=1CztpSeLzf8EmdCK5OaEKOAoKrVegPyWQ (SHA-256 376a778f8f4bdf1f9013b22252d26e248835dda49ed8b01941e47ff23815c603, retrieved 2026-11-23). MIRROR-SOURCED and Growatt-authored, but Growatt serves no copy. The earlier distributor link (amosplanet.org/wp-content/uploads/2022/05/OffGrid-Modbus-RS485RS232-RTU-Protocol-V0.14-20210420.pdf) no longer resolves (no A record) and this copy is bit-identical to it. Scope is the OffGrid SPF 3-5K family the document names (the revision notes say the map came from the sp3000 protocol for spf3-5K, and the model enum prints 3 kW and 5 kW), so no 6 kW model is claimed. Framing, section 3: 9600 bps, 8 data bits, no parity, 1 stop bit. Section 4.2 numbers its input registers from 00 and is read with 0x04; unit 1 is cited from holding row 30 (Com Address, 1-254, initial value 1). Seeded: the whole §4.2 telemetry map - run state enum, PV voltages, buck currents, output and AC powers, battery voltage/SOC/power, bus, grid and output voltage and frequency, temperatures, load percent, work time, the ten energy counters - each high/low word pair read as one 32-bit value (high word printed first, registers adjacent) with the pair's printed scale (0.1 W, 0.1 VA, 0.1 kWh, 0.5 s), plus the fault and warning words. Not seeded: the §4.1 holding map (about 160 settings rows) because its cells drift out of step with the address column and a wrong battery threshold can damage a pack; input rows 44-47, whose widths and values are inconsistent; input rows 79-162, which the document does not print. Three scale cells (input 21, 30, 68) split across page breaks are taken from their printed continuation, stated on those rows. The source claims no hardware validation.