  "spec_version": 1,
  "slug": "growatt-spf-es-offgrid",
  "manufacturer": "Growatt",
  "model": "OffGrid SPF 3-5K off-grid inverter/charger",
  "category": "Inverter/charger",
  "supplier_url": "https://www.growatt.com/",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 9600,
      "parity": "None",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [
    {
      "address": 0,
      "count": 1,
      "name": "System run state",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 standby, 1 PV and grid combine discharge, 2 discharge, 3 fault, 4 flash, 5 PV charge, 6 AC charge, 7 combine charge, 8 combine charge and bypass, 9 PV charge and bypass, 10 AC charge and bypass, 11 bypass, 12 PV charge and discharge."
    },
    {
      "address": 1,
      "count": 1,
      "name": "PV1 voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 2,
      "count": 1,
      "name": "PV2 voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 3,
      "count": 2,
      "name": "PV1 charge power",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 3, low word at 4. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 5,
      "count": 2,
      "name": "PV2 charge power",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 5, low word at 6. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 7,
      "count": 1,
      "name": "Buck 1 current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 8,
      "count": 1,
      "name": "Buck 2 current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 9,
      "count": 2,
      "name": "Output active power",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 9, low word at 10. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 11,
      "count": 2,
      "name": "Output apparent power",
      "data_type": "UInt32",
      "units": "VA",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 11, low word at 12. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 13,
      "count": 2,
      "name": "AC charge power",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 13, low word at 14. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 15,
      "count": 2,
      "name": "AC charge apparent power",
      "data_type": "UInt32",
      "units": "VA",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 15, low word at 16. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 17,
      "count": 1,
      "name": "Battery voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "The document labels this row M3."
    },
    {
      "address": 18,
      "count": 1,
      "name": "Battery state of charge",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Document range 0-100."
    },
    {
      "address": 19,
      "count": 1,
      "name": "Bus voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 20,
      "count": 1,
      "name": "AC input voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 21,
      "count": 1,
      "name": "AC input frequency",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "The document's scale cell for this row is split across the page break; the continuation prints 0.01 Hz."
    },
    {
      "address": 22,
      "count": 1,
      "name": "AC output voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 23,
      "count": 1,
      "name": "AC output frequency",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 24,
      "count": 1,
      "name": "Output DC voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 25,
      "count": 1,
      "name": "Inverter temperature",
      "data_type": "UInt16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 26,
      "count": 1,
      "name": "DC-DC temperature",
      "data_type": "UInt16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 27,
      "count": 1,
      "name": "Load percent",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Document range 0-1000 raw."
    },
    {
      "address": 28,
      "count": 1,
      "name": "Battery-port voltage (DSP)",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 29,
      "count": 1,
      "name": "Battery-bus voltage (DSP)",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 30,
      "count": 2,
      "name": "Total work time",
      "data_type": "UInt32",
      "units": "s",
      "scale_factor": 0.5,
      "offset": 0,
      "access": "R",
      "description": "High word at register 30, low word at 31; the document's 0.5 s scale cell is split across the page break and its continuation prints S. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 32,
      "count": 1,
      "name": "Buck 1 temperature",
      "data_type": "UInt16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 33,
      "count": 1,
      "name": "Buck 2 temperature",
      "data_type": "UInt16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 34,
      "count": 1,
      "name": "Output current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 35,
      "count": 1,
      "name": "Inverter current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 36,
      "count": 2,
      "name": "AC input power",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 36, low word at 37. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 38,
      "count": 2,
      "name": "AC input apparent power",
      "data_type": "UInt32",
      "units": "VA",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 38, low word at 39. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 40,
      "count": 1,
      "name": "Fault bits",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Bit field; the document names the row and its bit table is not part of this map section."
    },
    {
      "address": 41,
      "count": 1,
      "name": "Warning bits",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Bit field, low word."
    },
    {
      "address": 42,
      "count": 1,
      "name": "Warning bits, high word",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Bit field, high word."
    },
    {
      "address": 43,
      "count": 1,
      "name": "Warning value",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "The document gives no unit or decode for this row."
    },
    {
      "address": 48,
      "count": 2,
      "name": "PV1 energy today",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 48, low word at 49. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 50,
      "count": 2,
      "name": "PV1 energy total",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 50, low word at 51. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 52,
      "count": 2,
      "name": "PV2 energy today",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 52, low word at 53. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 54,
      "count": 2,
      "name": "PV2 energy total",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 54, low word at 55. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 56,
      "count": 2,
      "name": "AC charge energy today",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 56, low word at 57. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 58,
      "count": 2,
      "name": "AC charge energy total",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 58, low word at 59. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 60,
      "count": 2,
      "name": "Battery discharge energy today",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 60, low word at 61. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 62,
      "count": 2,
      "name": "Battery discharge energy total",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 62, low word at 63. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 64,
      "count": 2,
      "name": "AC discharge energy today",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 64, low word at 65. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 66,
      "count": 2,
      "name": "AC discharge energy total",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 66, low word at 67. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 68,
      "count": 1,
      "name": "AC charge battery current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "The document's scale cell for this row continues on the next page, which prints A."
    },
    {
      "address": 69,
      "count": 2,
      "name": "AC discharge power",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 69, low word at 70. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 71,
      "count": 2,
      "name": "AC discharge apparent power",
      "data_type": "UInt32",
      "units": "VA",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 71, low word at 72. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 73,
      "count": 2,
      "name": "Battery discharge power",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 73, low word at 74. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 75,
      "count": 2,
      "name": "Battery discharge apparent power",
      "data_type": "UInt32",
      "units": "VA",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 75, low word at 76. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    },
    {
      "address": 77,
      "count": 2,
      "name": "Battery power",
      "data_type": "Int32",
      "units": "W",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "High word at register 77, low word at 78. The document prints the scale 0.1 W on this row, so the 32-bit value carries 0.1 W per count. Positive while the battery discharges, negative while it charges, as the document prints. Printed as a high word and a low word in the document; the two registers are adjacent and the high word comes first, so it is read as one 32-bit value."
    }
  ],
  "holding_registers": [],
  "combined_registers": [],
  "notes": "Source: Growatt \"OffGrid SPF5000 Modbus RS485&RS232 RTU Protocol\", title block V0.14 dated 2020-10-16 (the distributor file name carries 2021-04-20 and the revision table adds a V0.15 line), 24 pages, mirror drive.google.com/uc?export=download&id=1CztpSeLzf8EmdCK5OaEKOAoKrVegPyWQ (SHA-256 376a778f8f4bdf1f9013b22252d26e248835dda49ed8b01941e47ff23815c603, retrieved 2026-11-23). MIRROR-SOURCED and Growatt-authored, but Growatt serves no copy. The earlier distributor link (amosplanet.org/wp-content/uploads/2022/05/OffGrid-Modbus-RS485RS232-RTU-Protocol-V0.14-20210420.pdf) no longer resolves (no A record) and this copy is bit-identical to it. Scope is the OffGrid SPF 3-5K family the document names (the revision notes say the map came from the sp3000 protocol for spf3-5K, and the model enum prints 3 kW and 5 kW), so no 6 kW model is claimed. Framing, section 3: 9600 bps, 8 data bits, no parity, 1 stop bit. Section 4.2 numbers its input registers from 00 and is read with 0x04; unit 1 is cited from holding row 30 (Com Address, 1-254, initial value 1). Seeded: the whole §4.2 telemetry map - run state enum, PV voltages, buck currents, output and AC powers, battery voltage/SOC/power, bus, grid and output voltage and frequency, temperatures, load percent, work time, the ten energy counters - each high/low word pair read as one 32-bit value (high word printed first, registers adjacent) with the pair's printed scale (0.1 W, 0.1 VA, 0.1 kWh, 0.5 s), plus the fault and warning words. Not seeded: the §4.1 holding map (about 160 settings rows) because its cells drift out of step with the address column and a wrong battery threshold can damage a pack; input rows 44-47, whose widths and values are inconsistent; input rows 79-162, which the document does not print. Three scale cells (input 21, 30, 68) split across page breaks are taken from their printed continuation, stated on those rows. The source claims no hardware validation."
}