Fox ESS · EV charger

EV Charger (EVC, A/C series) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
40961
Device address
Modbus device address of the charger (factory default 1).
UInt16-1R
40971
Software version
Example: 0x0110 = version 1.16.
UInt16-1R
40981
Stop reason
0 = none, 1 = stopped on command, 2 = timed charging completed, 3 = S2 timeout, 4 = charging pause timeout, 5 = emergency stop button pressed, 6 = abnormal CP voltage, 7 = abnormal connector removal, 8 = abnormal AC contactor, 9 = abnormal electronic lock, 10 = abnormal card reader, 11 = overcurrent, 12 = overvoltage, 13 = undervoltage, 14 = charging port overtemperature, 15 = leakage current, 16 = N line reversed, 17 = abnormal frequency, 18 = charging stop button pressed, 19 = abnormal circuit breaker, 20 = phase loss, 21 = abnormal PE, 22 = abnormal external meter, 23 = environment overtemperature, 24 = metering chip failure, 25 = access control failure, 26 = phase-switch box fault, 27 = predetermined energy reached.
UInt16-1R
40991
Connector status
0 = idle, 1 = connect, 2 = start, 3 = charging, 4 = pause, 5 = finish, 6 = fault, 7 = reserve, 8 = locked.
UInt16-1R
41001
CP status
0 = CP fault, 1 = CP 12 V (not connected), 2 = CP 9 V (connected), 3 = CP 6 V (car ready).
UInt16-1R
41011
CC connection status
0 = plug unconnected, 1 = plug connected.
UInt16-1R
41021
Charging port temperature
Raw * 0.1 - 50. Not fitted on the plug version; fixed 0xFFFF from certain firmware versions.
UInt16°C0.1 (offset -50)R
41031
EVC environment temperature
Raw * 0.1 - 50.
UInt16°C0.1 (offset -50)R
41041
Voltage phase A
UInt16V0.1R
41051
Voltage phase B
UInt16V0.1R
41061
Voltage phase C
UInt16V0.1R
41071
Current phase A
UInt16A0.1R
41081
Current phase B
UInt16A0.1R
41091
Current phase C
UInt16A0.1R
41101
Active power
UInt16kW0.1R
41111
Electronic lock status
0 = unlocked, 1 = locked.
UInt16-1R
41121
Current phase sequence
0 = three-phase, 1 = L2, 2 = L3, 3 = reserve. Only meaningful with the external phase-switch box.
UInt16-1R
41131
Max supported power
Model rating.
UInt16kW0.1R
41141
Min supported power
UInt16kW0.1R
41151
Max supported current
Per phase; model rating.
UInt16A0.1R
41161
Min supported current
UInt16A0.1R
41171
System alarm information
Alarm bitfield, see the alarm code appendix of the protocol.
UInt16-1R
41182
Current energy
Internal meter reading.
UInt32kWh0.1R
41202
Total charging energy
UInt32kWh0.1R
41222
System fault information
Fault bitfield, see the fault code appendix of the protocol.
UInt32-1R
41242
RFID card
UID of the card that started the current session.
UInt32-1R
41264
Id model code
8 bytes, e.g. A022KP1.
Ascii-1R
413016
Id serial number
32 bytes, zero padded.
Ascii-1R
414610
Extended RFID card
20 bytes, zero padded; only on some models.
Ascii-1R
41561
Connector number
1 = single connector, 2 = dual connector.
UInt16-1R
41571
Single/three-phase switching status
0 = idle, 1 = switching 3-phase to single-phase, 2 = switching single-phase to 3-phase.
UInt16-1R
41581
Single/three-phase work status
0 = idle, 1 = three-phase charging, 2 = single-phase charging.
UInt16-1R
41591
Real-time power phase A
UInt16kW0.1R
41601
Real-time power phase B
UInt16kW0.1R
41611
Real-time power phase C
UInt16kW0.1R
122881
Work mode
0 = controlled mode, 1 = plug and charge, 2 = lock mode. Takes effect only while no connector is connected.
UInt16-1RW
122891
Max charging current
Applies for one minute, then reverts to the rated maximum; 0 stops charging.
UInt16A0.1RW
122901
Max charging power
Applies for one minute, then reverts to the rated maximum; 0 stops charging.
UInt16kW0.1RW
122911
Allowable charge time
0xFFFF = no limit.
UInt16min1RW
122921
Allowable charge energy
0xFFFF = no limit.
UInt16kWh1RW
122931
Time validity
How long the last command value is valid; default 180 s, range 10-255 s.
UInt16s1RW
122941
Default current
Current used when the link to the EMS is lost.
UInt16A0.1RW
122981
Single/three-phase automatic switching
0 = disabled, 1 = enabled; switches at 4.2 kW. Not supported on single-phase models.
UInt16-1RW
122991
EVC suspend switching minimum interval
0-30 min, default 12 min.
UInt16min1RW
123001
Current charging connector number
1 = connector 1 (default), 0 = the EVC itself; only multi-connector models.
UInt16-1RW
123011
Minimum interval for EVC suspended status change
0-1800 s, default 720 s; finer-grained form of register 12299.
UInt16s1RW
163841
Electronic lock control
0 = no action, 1 = unlock, 2 = lock.
UInt16-1W
163851
Charging control
0 = no action, 1 = start charging, 2 = stop charging.
UInt16-1W
163861
Phase sequence switching
0 = three-phase, 1 = L2, 2 = L3; only with the external phase-switch box.
UInt16-1W
163871
Restart
Write 0xA5A5 to restart the charger.
UInt16-1W

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

MIRROR-SOURCED (vendor-authored, hosting unconfirmed). Source: Fox ESS "EV Charger - Modbus TCP & RTU Protocol V1.06" (file number MTWH-2024-0001, dated 2025-07-02), chapter 2 "Register List" and sections 2.1-2.50 for types, scaling and enums; the vendor's EV charger protocol document, read from the copy of the protocol document in Fox ESS's own website asset storage (the vendor download pages serve the user manuals, not this protocol) at https://cdn.prod.website-files.com/6a7ae62372cb780ff5be747e/6abaad94818d6bac9bad9d21_Fox-ESS-EV-Charger-Modbus-TCP---RTU-Protocol-1.06-(1).pdf. Section 1.4 item (5) documents the Modbus TCP default port 502, and the MBAP unit-identification field (§1.6.1.1) and §2.1 both give the device address range with default 1; the table prints hex register addresses (0x1000 = 4096) which are stored here unchanged as zero-based wire addresses. All rows are holding registers on function codes 3/6/16. Temperatures scale as raw * 0.1 - 50 C. The document's RTU baud rate is not stated anywhere, so only the TCP transport is declared; the RTU path would need the site's own gateway settings. Alarm and fault bit fields are referenced by register, not transcribed row by row. This is the wallbox itself, a different device family from the library's Fox ESS inverter seeds (fox-ess-h3, fox-ess-h3-pro-smart, fox-ess-avocado), whose register map it does not share. File identity: SHA-256 5a47f709341d34d53b04e12fc466d84fc6ea78db3379dc933f4ea41d98df1e68 (PDF, downloaded 2026-11-07).