Charger Gemini / Gemini flex / CORE / HOME+ (V3) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
1001
Car state
0 = unknown / charging station defective, 1 = charging station ready, no car, 2 = car is charging, 3 = waiting for car, 4 = charging finished, car still connected.
UInt16-1R
1011
Cable ampere coding
Type 2 cable coding: 13 to 32 = ampere coding, 0 = no cable.
UInt16A1R
1052
Firmware version
Firmware version as ASCII (4 bytes).
Ascii-1R
1071
Error
1 = RCCB (residual current circuit breaker), 3 = phase disturbance, 8 = no ground (ground detection), 10 and any other value = internal error.
UInt16-1R
1082
Voltage L1
UInt32V1R
1102
Voltage L2
UInt32V1R
1122
Voltage L3
UInt32V1R
1142
Current L1
Raw value in 0.1 A.
UInt32A0.1R
1162
Current L2
Raw value in 0.1 A.
UInt32A0.1R
1182
Current L3
Raw value in 0.1 A.
UInt32A0.1R
1202
Power total
Raw value in 0.01 kW.
UInt32kW0.01R
1282
Energy total
Total charged energy in 0.1 kWh.
UInt32kWh0.1R
1322
Energy, current charge
Energy of the running charging process in deka-watt-seconds, i.e. raw x 10 Ws (100000 = 1000000 Ws = 277 Wh).
UInt32Ws10R
1442
Voltage N
UInt32V1R
1462
Power L1
Raw value in 0.1 kW.
UInt32kW0.1R
1482
Power L2
Raw value in 0.1 kW.
UInt32kW0.1R
1502
Power L3
Raw value in 0.1 kW.
UInt32kW0.1R
1522
Power factor L1
UInt32%1R
1542
Power factor L2
UInt32%1R
1562
Power factor L3
UInt32%1R
1582
Power factor N
UInt32%1R
2021
Adapter input
0 = no adapter, 1 = 16 A adapter connected.
UInt16-1R
2031
Unlocked by
Number of the RFID card that activated the current charging process.
UInt16-1R
2051
Phases
Binary flags 0b00ABCDEF: A/B/C = phase 3/2/1 before the contactor, D/E/F = phase 3/2/1 after the contactor. 0b00001000 = phase 1 available, 0b00111000 = phases 1-3 available.
Binary-1R
3046
Serial number
Serial number of the charger as ASCII (12 bytes).
Ascii-1R
3154
IP address
IP address, one byte per register (8 bytes).
Ascii-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: go-e, "GO-E Charger Modbus TCP/IP Documentation English", version 1.0, 2020-10-01, published by the vendor as go-eCharger Modbus TCP API v1 in its own repository (https://github.com/goecharger/go-eCharger-API-v1, file "go-eCharger Modbus TCP API v1 EN.md"). The document fixes everything this seed encodes: port 502 over WLAN, unit ID 1, "the Register ID is 0-indexed" (so the numbers below are wire addresses), multi-register values are big-endian 16-bit words, input registers are read-only and holding registers are readable and writable. The API has to be enabled in the go-e app under advanced settings and needs firmware 0.40 or newer. Earlier passes recorded go-e as an HTTP-only device; the vendor Modbus TCP document above lifts that skip. Model scope follows the vendor API family and the evcc go-e-v3 template: Charger Gemini, Gemini flex, CORE, HOME+ and V3. Deliberately left out because the document's own columns cannot be paired: MAC (301-303, a 48-bit integer, and this schema has no 48-bit type), SUBNET (319-322, a 64-bit integer), HOSTNAME (310-314, five registers listed against a six-register length column) and GATEWAY (323-326, four registers against an "ascii (4 byte)" length). The register names in the table are the vendor's API keys (for example AMLERE_L2 for level 2, a typo in the document); the display names here are the same keys spelled out. The power rows are in 0.1 kW and the session energy in deka-watt-seconds, which is why the session row carries a factor of 10 and a unit of Ws instead of a kWh scale that would not be exact.