All devices

Circutor · Power analyzer

CVM-C10 / CVM-C10 series power analyzer Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
02
L1 phase voltage
UInt32V0.1R
22
L1 current
UInt32A0.001R
42
L1 active power
Int32W1R
62
L1 inductive reactive power
Int32var1R
82
L1 capacitive reactive power
Int32var1R
102
L1 apparent power
UInt32VA1R
122
L1 power factor
Int32-0.01R
142
L1 cos phi
Int32-0.01R
162
L2 phase voltage
UInt32V0.1R
182
L2 current
UInt32A0.001R
202
L2 active power
Int32W1R
222
L2 inductive reactive power
Int32var1R
242
L2 capacitive reactive power
Int32var1R
262
L2 apparent power
UInt32VA1R
282
L2 power factor
Int32-0.01R
302
L2 cos phi
Int32-0.01R
322
L3 phase voltage
UInt32V0.1R
342
L3 current
UInt32A0.001R
362
L3 active power
Int32W1R
382
L3 inductive reactive power
Int32var1R
402
L3 capacitive reactive power
Int32var1R
422
L3 apparent power
UInt32VA1R
442
L3 power factor
Int32-0.01R
462
L3 cos phi
Int32-0.01R
482
Three-phase active power
Int32W1R
502
Three-phase inductive reactive power
Int32var1R
522
Three-phase capacitive reactive power
Int32var1R
542
Three-phase apparent power
UInt32VA1R
562
Three-phase power factor
Int32-0.01R
582
Three-phase cos phi
Int32-0.01R
602
Frequency
UInt32Hz0.01R
622
L1-L2 voltage
UInt32V0.1R
642
L2-L3 voltage
UInt32V0.1R
662
L3-L1 voltage
UInt32V0.1R
682
Neutral current
UInt32A0.001R
702
L1 voltage THD
UInt32%0.1R
722
L2 voltage THD
UInt32%0.1R
742
L3 voltage THD
UInt32%0.1R
762
L1 current THD
UInt32%0.1R
782
L2 current THD
UInt32%0.1R
802
L3 current THD
UInt32%0.1R
822
Maximum demand, three-phase active power
Int32W1R
842
Maximum demand, three-phase apparent power
UInt32VA1R
862
Maximum demand, average current
UInt32A0.001R
882
Maximum demand, current L1
UInt32A0.001R
902
Maximum demand, current L2
UInt32A0.001R
922
Maximum demand, current L3
UInt32A0.001R
5122
Maximum demand, three-phase inductive reactive power
Int32var1R
5142
Maximum demand, three-phase capacitive reactive power
Int32var1R
2202
Consumed active energy (kWh counter)
UInt32kWh1R
2222
Consumed active energy (Wh counter)
UInt32Wh1R
2242
Consumed inductive reactive energy (kvarh counter)
UInt32kvarh1R
2262
Consumed inductive reactive energy (varh counter)
UInt32varh1R
2282
Consumed capacitive reactive energy (kvarh counter)
UInt32kvarh1R
2302
Consumed capacitive reactive energy (varh counter)
UInt32varh1R
2322
Consumed apparent energy (kVAh counter)
UInt32kVAh1R
2342
Consumed apparent energy (VAh counter)
UInt32VAh1R
2402
Generated active energy (kWh counter)
UInt32kWh1R
2422
Generated active energy (Wh counter)
UInt32Wh1R
2442
Generated inductive reactive energy (kvarh counter)
UInt32kvarh1R
2462
Generated inductive reactive energy (varh counter)
UInt32varh1R
2482
Generated capacitive reactive energy (kvarh counter)
UInt32kvarh1R
2502
Generated capacitive reactive energy (varh counter)
UInt32varh1R
2522
Generated apparent energy (kVAh counter)
UInt32kVAh1R
2542
Generated apparent energy (VAh counter)
UInt32VAh1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

RS-485 device read natively over Modbus RTU. Source: Circutor "CVM-C10 - Instruction Manual" M001B01-03-23A (revision 23A, 05/21). Section 4.10.3.1 (Table 19) gives the instantaneous and maximum-demand variables in hexadecimal, each a 32-bit integer, with the unit column carrying the implied decimals (V x 10, mA, W, var, VA, x 100 for power factor and cos phi, Hz x 100, % x 10 for THD); 4.10.3.2 (Table 20) gives the energies; 4.10.3.8.16 Table 46 gives the factory Modbus frame (peripheral number 1, transmission speed 0 = 9600, parity 0 = no parity, data bits 0 = 8 bits, stop bits 0 = 1 stop bit); and the worked example in 4.10.2.1 reads register 0000 as 0000 084D hex = 2125 at "V x 10" = 212.5 V, which fixes the high-word-first order and the scaling. Addresses are the document's hexadecimal wire addresses (register pair 00-01 is address 0). Measurements are input registers (function 04, which the document implements alongside 03) and the six communication settings are holding registers written with 0x10. The document prints no signedness column, so Int32 for the power, power-factor, cos phi and maximum-demand power rows and UInt32 for voltages, currents, apparent power, THD, frequency and energies is a declared convention, not a cited fact. The unit column prints "kvarL"/"kvarC" for the two 0x200/0x202 maximum-demand rows; those are symbols rather than units, so the rows carry var. Both counter sets of every energy are seeded (kWh/kvarh/kVAh and the finer Wh/varh/VAh). Left out by scope: the maximum and minimum columns at 0x106-0x207, the tariff 1/2/3 columns of Table 20 with the CO2, cost and hours-per-tariff rows, the harmonics of Table 21 (16-bit percentages with no implied-decimal statement) and the two BACnet rows of Table 46 (0x2EE0-0x2EE2). Not a duplicate of any library seed: Circutor is not in the library and the CVM-C10 map (0x00-0x5D instantaneous, 0xDC-0xFE energies) is unique.

Related devices