CHINT · Energy meter

DTSU666 / DSSU666 Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Software version
Int16-1R
31
Wiring mode
0 = three phase four wire, 1 = three phase three wire.
Int16-1RW
61
Current transformer ratio (IrAt)
CT ratio; 1 when the meter is connected directly.
Int16-1RW
71
Voltage transformer ratio (UrAt)
Voltage transformer ratio UrAt; 1.0 when the meter is connected directly. The manual documents the ratio as 0.1 to 1999.9, so the register carries one decimal place.
Int16-1RW
101
Display scroll time
Int16s1RW
111
Backlight time
0 = backlight always on.
Int16min1RW
441
Protocol / parity selection
1 = DL/T645, 2 = no parity with 2 stop bits, 3 = no parity with 1 stop bit, 4 = even parity with 1 stop bit, 5 = odd parity with 1 stop bit.
Int16-1RW
451
Baud rate
0 = 1200, 1 = 2400, 2 = 4800, 3 = 9600.
Int16-1RW
461
Modbus address
1 to 247.
Int16-1RW
41262
Forward active energy, total
Float32kWh1R
41282
Forward active energy, phase A
Float32kWh1R
41302
Forward active energy, phase B
Float32kWh1R
41322
Forward active energy, phase C
Float32kWh1R
41342
Forward active energy, net
Float32kWh1R
41362
Reverse active energy, total
Float32kWh1R
41382
Reverse active energy, phase A
Float32kWh1R
41402
Reverse active energy, phase B
Float32kWh1R
41422
Reverse active energy, phase C
Float32kWh1R
41442
Reverse active energy, net
Float32kWh1R
81922
Line voltage Uab
Float32V0.1R
81942
Line voltage Ubc
Float32V0.1R
81962
Line voltage Uca
Float32V0.1R
81982
Phase voltage Ua
Invalid in three phase three wire mode.
Float32V0.1R
82002
Phase voltage Ub
Invalid in three phase three wire mode.
Float32V0.1R
82022
Phase voltage Uc
Float32V0.1R
82042
Phase current Ia
Float32A0.001R
82062
Phase current Ib
Float32A0.001R
82082
Phase current Ic
Float32A0.001R
82102
Combined active power
Float32W0.1R
82122
Phase A active power
Float32W0.1R
82142
Phase B active power
Invalid in three phase three wire mode.
Float32W0.1R
82162
Phase C active power
Float32W0.1R
82182
Combined reactive power
Float32var0.1R
82202
Phase A reactive power
Float32var0.1R
82222
Phase B reactive power
Float32var0.1R
82242
Phase C reactive power
Float32var0.1R
82342
Combined power factor
Positive = inductive, negative = capacitive.
Float32-0.001R
82362
Phase A power factor
Float32-0.001R
82382
Phase B power factor
Float32-0.001R
82402
Phase C power factor
Float32-0.001R
82602
Frequency
Float32Hz0.01R

Notes

RS-485 device: reach it through a Modbus RTU-to-TCP gateway using the factory serial settings above (slave address 1, 9600 bps, 8N1). Source: CHINT 'DTSU666/DSSU666 User Manual' ZTW0.464.0104 V1, table 11 (Modbus protocol address table). Measurements and energy counters are IEEE-754 single precision floats with the high word first (ABCD), read with function code 03. The manual gives the value resolution (0.1 V, 0.001 A, 0.1 W, 0.001 PF, 0.01 Hz, 1 kWh), which is applied here as the scale factor. The register numbers in the manual are the wire addresses.