Autonics · Temperature controller

TK Series PID temperature controllers (TK4S and the other four-row TK models) Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
2

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Control output RUN/STOP
Coil 000001(0000). 0 = RUN, 1 = STOP. Factory default RUN.
Binary-1RW
11
Auto-tuning run
Coil 000002(0001). 0 = OFF, 1 = ON. Factory default OFF.
Binary-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Autonics 'TK Series User Manual for Communication', revision V1.8 (file mct_tkc1_v1_8_1712en_20171218_he_20180221.pdf on the vendor's European site, https://autonics.se/wp-content/uploads/2018/03/mct_tkc1_v1_8_1712en_20171218_he_20180221.pdf, SHA-256 6f48b619e41865ffeaa1551771c3fc9c8adf9d34153f8975de0b432dd41ca59e): chapter 2 'Modbus Mapping Table' for the coils, input status, input registers and the parameter groups 0-3 and 5, which print both the Modicon-style number (400001) and the hexadecimal PDU address (0000). The seed stores the hexadecimal address unchanged and declares zero_based. Factory serial frame from the same parameter 4 group: communication address 01 (400219), speed value 96 = 9600 bps (400220), parity NONE (400221) and 2 stop bits (400222) - all four are printed 'Factory Default' cells, not inferred. The manual prints no data-length parameter at all, so the frame keeps Modbus RTU's 8 data bits (its worked frames carry one byte per register). The PDF's embedded font prints a decimal point as ')' (so the manual's '01)0' is 01.0); the seed states the decimal values an operator sees. Omitted on purpose: the control rows 0x006B-0x0075 (dead/overlap band, manual reset, heating and cooling hysteresis and OFF offsets, ramp up/down change rates, ramp time unit); the analog range and scaling rows 0x0098-0x009F; the auto-tuning-mode and output-configuration rows 0x00A4-0x00A9; the alarm 1/2 block 0x00C8-0x00D6; the analog-transmission and alarm-3 blocks 0x00D7-0x00D9 and 0x00E0-0x00E8 (optional output boards); the manual-mode MV rows 0x00FF-0x0102; the parameter-lock rows 0x0105-0x010A with the password at 0x010B; the 30-word user parameter group 0x012C-0x0149 (meaning set by each parameter); and every 'Reserved' range. The self-describing start/quantity rows are in the input area (input 0x0075-0x007C) and are not seeded either.