Autonics · Temperature controller
TK Series PID temperature controllers (TK4S and the other four-row TK models) Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 9600
- Parity
- None
- Data bits
- 8
- Stop bits
- 2
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 0 | 1 | Control output RUN/STOP Coil 000001(0000). 0 = RUN, 1 = STOP. Factory default RUN. | Binary | - | 1 | RW |
| 1 | 1 | Auto-tuning run Coil 000002(0001). 0 = OFF, 1 = ON. Factory default OFF. | Binary | - | 1 | RW |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: Autonics 'TK Series User Manual for Communication', revision V1.8 (file mct_tkc1_v1_8_1712en_20171218_he_20180221.pdf on the vendor's European site, https://autonics.se/wp-content/uploads/2018/03/mct_tkc1_v1_8_1712en_20171218_he_20180221.pdf, SHA-256 6f48b619e41865ffeaa1551771c3fc9c8adf9d34153f8975de0b432dd41ca59e): chapter 2 'Modbus Mapping Table' for the coils, input status, input registers and the parameter groups 0-3 and 5, which print both the Modicon-style number (400001) and the hexadecimal PDU address (0000). The seed stores the hexadecimal address unchanged and declares zero_based. Factory serial frame from the same parameter 4 group: communication address 01 (400219), speed value 96 = 9600 bps (400220), parity NONE (400221) and 2 stop bits (400222) - all four are printed 'Factory Default' cells, not inferred. The manual prints no data-length parameter at all, so the frame keeps Modbus RTU's 8 data bits (its worked frames carry one byte per register). The PDF's embedded font prints a decimal point as ')' (so the manual's '01)0' is 01.0); the seed states the decimal values an operator sees. Omitted on purpose: the control rows 0x006B-0x0075 (dead/overlap band, manual reset, heating and cooling hysteresis and OFF offsets, ramp up/down change rates, ramp time unit); the analog range and scaling rows 0x0098-0x009F; the auto-tuning-mode and output-configuration rows 0x00A4-0x00A9; the alarm 1/2 block 0x00C8-0x00D6; the analog-transmission and alarm-3 blocks 0x00D7-0x00D9 and 0x00E0-0x00E8 (optional output boards); the manual-mode MV rows 0x00FF-0x0102; the parameter-lock rows 0x0105-0x010A with the password at 0x010B; the 30-word user parameter group 0x012C-0x0149 (meaning set by each parameter); and every 'Reserved' range. The self-describing start/quantity rows are in the input area (input 0x0075-0x007C) and are not seeded either.