3200 series temperature/process controller (3204, 3208, 3216) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
11
PV (temperature) input value
Process value. Engineering units with an implied decimal point taken from the instrument's display resolution; for writes over Modbus see the Comms PV value at address 203. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1R
21
Target set-point
Target set-point with implied decimal point. The document warns not to write continuously changing values (limited EEPROM write cycles); use the remote set-point at address 26 for ramping. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
31
Manual output value
Manual output power, 0-100 % (with implied decimal point). Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16%1RW
41
Working output
Current working output power. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16%1R
51
Working set-point
Working set-point (read only). Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1R
61
Proportional band
Proportional band, 0.1 to 999.9 in display units.
UInt16-0.1RW
71
Control action
0 = reverse acting, 1 = direct acting.
UInt16-1RW
81
Integral time
Integral time constant; 0 = no integral action. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
UInt16s1RW
91
Derivative time
Derivative time constant; 0 = no derivative action. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
UInt16s1RW
111
Input range low limit
Scale range lower limit. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
121
Input range high limit
Scale range upper limit. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
131
Alarm 1 threshold
Alarm 1 trip level. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
141
Alarm 2 threshold
Alarm 2 trip level. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
151
Active set-point select
0 = set-point 1, 1 = set-point 2.
UInt16-1RW
161
Channel 2 deadband
Deadband between heating and cooling outputs. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
171
Cutback low
Cutback low limit. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
UInt16-1RW
181
Cutback high
Cutback high limit. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
UInt16-1RW
191
Relative cool / channel 2 gain
Relative cooling gain for the second output channel. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
UInt16-1RW
211
Motor travel time
Valve motor travel time (position-proportional models). Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
UInt16s1RW
231
Timer status
0 = reset, 1 = run, 2 = hold, 3 = end.
UInt16-1R
241
Set-point 1
Set-point 1, with implied decimal point. Do not write continuously (EEPROM write limit); use the remote set-point at 26. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
251
Set-point 2
Set-point 2, with implied decimal point. Do not write continuously (EEPROM write limit). Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
261
Remote (comms) set-point
Remote set-point used when remote-setpoint selection is active (address 276). Must be refreshed at least every ~5 s or the controller falls back to the selected local set-point with a remote-SP failure. Not saved at power-off and safe to write continuously. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
271
Local trim
Trim added to the remote set-point to compensate for local temperature variation. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
281
Manual reset
Manual reset value. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
301
Output high limit
Maximum output power, 0-100 %. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
UInt16%1RW
311
Output low limit
Minimum output power, 0-100 %. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
UInt16%1RW
341
Safe output value
Output value used on sensor break or other fault conditions. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16%1RW
351
Set-point rate limit
Set-point rate limit; 0 = no limit. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
UInt16-1RW
391
Calculated error
Calculated error, PV - SP. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1R
471
Alarm 1 hysteresis
Alarm 1 hysteresis. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
681
Alarm 2 hysteresis
Alarm 2 hysteresis. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
691
Alarm 3 hysteresis
Alarm 3 hysteresis. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
711
Alarm 4 hysteresis
Alarm 4 hysteresis. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
751
Instrument status
Bitmap: B0 alarm 1, B1 alarm 2, B2 alarm 3, B3 alarm 4, B4 auto/manual, B5 sensor break, B6 loop break, B7 CT low load current, B8 CT high leakage current, B9 program end, B10 PV over-range (>5 % span), B11 CT overcurrent, B12 new alarm, B13 timer/ramp running, B14 remote set-point fail, B15 auto-tune. 1 = active.
UInt16-1R
1111
Set-point high limit
Upper limit for the set-point. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
1121
Set-point low limit
Lower limit for the set-point. Values assume integer resolution mode; in full-resolution mode multiply the reading by 10^-dp.
Int16-1RW
1311
Instrument comms address
Modbus device (slave) address, 1-254.
UInt16-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Sources: Eurotherm "3200 Series - User Manual", part number HA028651 issue 15.0, December 2015, sections 15.2 (digital communications parameters, factory defaults) and 15.6 (parameter Modbus addresses), https://www.eurotherm.com/?wpdmdl=27913; and Eurotherm "2000 Series MODBUS and EI-BISYNCH Handbook", HA026230 issue 3, June 2011, sections 3.3, 3.4, 3.6 and 4.3, https://www.eurotherm.com/?wpdmdl=27877. Factory defaults from the 3200 communications table: address 1, baud rate 9600, parity none; the same table fixes the data length to 8 bits and one stop bit for Modbus (HA026230: "a start bit, eight data bits, a parity bit and one or two stop bits; all Series 2000 instruments use 1 stop bit"). Addressing: HA026230's worked frame reads "parameter address 1" with start address 0x0001, so the printed decimal parameter address is sent unchanged (zero-based). Values are 16-bit integers and the decimal point is not transmitted: HA026230 §3.5 allows integer mode (rounded) or full resolution, where the point is implied and the conversion factor must be known to both ends. No factory resolution is stated, so this seed assumes integer resolution and keeps scale 1 on the engineering values (each affected row says so); at full resolution multiply the reading by 10^-dp. Proportional band (0.1-999.9) keeps 0.1. Access is not printed per row in the source; read-only rows (PV, working output, working set-point, calculated error, instrument status, timer status) follow the document's own wording ("Read Only" for working set-point). Omitted on purpose: the parameter rows after address 71 whose names and addresses are printed as separate stacked columns in the source (79-107, 122, 141-146, 199-333) cannot be paired reliably and are left out, as are the recipe/timer/programmer blocks and the 12551 broadcast retransmission register. The instrument's EEPROM has a limited number of writes (100,000) - the document warns not to write set-points continuously; use address 26 for ramping.