  "spec_version": 1,
  "slug": "autonics-tk-series",
  "manufacturer": "Autonics",
  "model": "TK Series PID temperature controllers (TK4S and the other four-row TK models)",
  "category": "Temperature controller",
  "supplier_url": "https://www.autonics.com/",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 9600,
      "parity": "None",
      "data_bits": 8,
      "stop_bits": 2
    }
  },
  "coils": [
    {
      "address": 0,
      "count": 1,
      "name": "Control output RUN/STOP",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Coil 000001(0000). 0 = RUN, 1 = STOP. Factory default RUN."
    },
    {
      "address": 1,
      "count": 1,
      "name": "Auto-tuning run",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Coil 000002(0001). 0 = OFF, 1 = ON. Factory default OFF."
    }
  ],
  "discrete_inputs": [
    {
      "address": 0,
      "count": 1,
      "name": "℃ indicator",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Input status 100001(0000), read with function 02. The same flag is bit 0 of input register 0x03EE."
    },
    {
      "address": 1,
      "count": 1,
      "name": "℉ indicator",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Input status 100002(0001), read with function 02. The same flag is bit 1 of input register 0x03EE."
    },
    {
      "address": 2,
      "count": 1,
      "name": "% indicator",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Input status 100003(0002), read with function 02. The same flag is bit 2 of input register 0x03EE."
    },
    {
      "address": 3,
      "count": 1,
      "name": "OUT1 indicator",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Input status 100004(0003), read with function 02. The same flag is bit 3 of input register 0x03EE."
    },
    {
      "address": 4,
      "count": 1,
      "name": "OUT2 indicator",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Input status 100005(0004), read with function 02. The same flag is bit 4 of input register 0x03EE."
    },
    {
      "address": 5,
      "count": 1,
      "name": "AT indicator",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Input status 100006(0005), read with function 02. The same flag is bit 5 of input register 0x03EE."
    },
    {
      "address": 6,
      "count": 1,
      "name": "SV1 indicator",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Input status 100007(0006), read with function 02. The same flag is bit 6 of input register 0x03EE."
    },
    {
      "address": 7,
      "count": 1,
      "name": "SV2 indicator",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Input status 100008(0007), read with function 02. The same flag is bit 7 of input register 0x03EE."
    },
    {
      "address": 8,
      "count": 1,
      "name": "SV3 indicator",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Input status 100009(0008), read with function 02. The same flag is bit 8 of input register 0x03EE."
    },
    {
      "address": 9,
      "count": 1,
      "name": "AL1 indicator",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Input status 100010(0009), read with function 02. The same flag is bit 9 of input register 0x03EE."
    },
    {
      "address": 10,
      "count": 1,
      "name": "AL2 indicator",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Input status 100011(000A), read with function 02. The same flag is bit 10 of input register 0x03EE."
    },
    {
      "address": 11,
      "count": 1,
      "name": "MAN indicator",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Input status 100012(000B), read with function 02. The same flag is bit 11 of input register 0x03EE."
    },
    {
      "address": 12,
      "count": 1,
      "name": "DI-1 input status",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Input status 100013(000C), read with function 02. The same flag is bit 12 of input register 0x03EE."
    },
    {
      "address": 13,
      "count": 1,
      "name": "DI-2 input status",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Input status 100014(000D), read with function 02. The same flag is bit 13 of input register 0x03EE."
    }
  ],
  "input_registers": [
    {
      "address": 100,
      "count": 1,
      "name": "Product number high word",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300101(0064)."
    },
    {
      "address": 101,
      "count": 1,
      "name": "Product number low word",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300102(0065)."
    },
    {
      "address": 102,
      "count": 1,
      "name": "Hardware version",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300103(0066)."
    },
    {
      "address": 103,
      "count": 1,
      "name": "Software version",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300104(0067)."
    },
    {
      "address": 104,
      "count": 1,
      "name": "Model name character 1",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300105(0068). Two ASCII characters per register: the manual's factory-default column prints 'TK' (product name) in 300105, '4' (4-row indicator) in 300106, '14' (option output) in 300107 and 'RR' (OUT1/OUT2 output) in 300108, so the ten registers spell the model code."
    },
    {
      "address": 105,
      "count": 1,
      "name": "Model name character 2",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300106(0069). Two ASCII characters per register: the manual's factory-default column prints 'TK' (product name) in 300105, '4' (4-row indicator) in 300106, '14' (option output) in 300107 and 'RR' (OUT1/OUT2 output) in 300108, so the ten registers spell the model code."
    },
    {
      "address": 106,
      "count": 1,
      "name": "Model name character 3",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300107(006A). Two ASCII characters per register: the manual's factory-default column prints 'TK' (product name) in 300105, '4' (4-row indicator) in 300106, '14' (option output) in 300107 and 'RR' (OUT1/OUT2 output) in 300108, so the ten registers spell the model code."
    },
    {
      "address": 107,
      "count": 1,
      "name": "Model name character 4",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300108(006B). Two ASCII characters per register: the manual's factory-default column prints 'TK' (product name) in 300105, '4' (4-row indicator) in 300106, '14' (option output) in 300107 and 'RR' (OUT1/OUT2 output) in 300108, so the ten registers spell the model code."
    },
    {
      "address": 108,
      "count": 1,
      "name": "Model name character 5",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300109(006C). Two ASCII characters per register: the manual's factory-default column prints 'TK' (product name) in 300105, '4' (4-row indicator) in 300106, '14' (option output) in 300107 and 'RR' (OUT1/OUT2 output) in 300108, so the ten registers spell the model code."
    },
    {
      "address": 109,
      "count": 1,
      "name": "Model name character 6",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300110(006D). Two ASCII characters per register: the manual's factory-default column prints 'TK' (product name) in 300105, '4' (4-row indicator) in 300106, '14' (option output) in 300107 and 'RR' (OUT1/OUT2 output) in 300108, so the ten registers spell the model code."
    },
    {
      "address": 110,
      "count": 1,
      "name": "Model name character 7",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300111(006E). Two ASCII characters per register: the manual's factory-default column prints 'TK' (product name) in 300105, '4' (4-row indicator) in 300106, '14' (option output) in 300107 and 'RR' (OUT1/OUT2 output) in 300108, so the ten registers spell the model code."
    },
    {
      "address": 111,
      "count": 1,
      "name": "Model name character 8",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300112(006F). Two ASCII characters per register: the manual's factory-default column prints 'TK' (product name) in 300105, '4' (4-row indicator) in 300106, '14' (option output) in 300107 and 'RR' (OUT1/OUT2 output) in 300108, so the ten registers spell the model code."
    },
    {
      "address": 112,
      "count": 1,
      "name": "Model name character 9",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300113(0070). Two ASCII characters per register: the manual's factory-default column prints 'TK' (product name) in 300105, '4' (4-row indicator) in 300106, '14' (option output) in 300107 and 'RR' (OUT1/OUT2 output) in 300108, so the ten registers spell the model code."
    },
    {
      "address": 113,
      "count": 1,
      "name": "Model name character 10",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300114(0071). Two ASCII characters per register: the manual's factory-default column prints 'TK' (product name) in 300105, '4' (4-row indicator) in 300106, '14' (option output) in 300107 and 'RR' (OUT1/OUT2 output) in 300108, so the ten registers spell the model code."
    },
    {
      "address": 1000,
      "count": 1,
      "name": "Process value (PV)",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 301001(03E8). Range -1999 to 9999. The decimal point position comes from 0x03E9; for analog input the value follows the scaling limits."
    },
    {
      "address": 1001,
      "count": 1,
      "name": "Decimal point location",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 301002(03E9). 0 = no decimal, 1 = one, 2 = two, 3 = three decimal places."
    },
    {
      "address": 1002,
      "count": 1,
      "name": "Indicator unit",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 301003(03EA). 0 = the manual's ℃ code, 1 = its ℉ code, 2 = the third code (printed as a garbled '?/O' glyph in the PDF), 3 = OFF. Use register 0x0097 (sensor temperature unit) for the measurement unit."
    },
    {
      "address": 1003,
      "count": 1,
      "name": "SV setting value",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 301004(03EB). Between the SV low limit (0x00A0) and SV high limit (0x00A1); factory default 0000. Same decimal point as the PV."
    },
    {
      "address": 1004,
      "count": 1,
      "name": "Heating-side MV monitor",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Register 301005(03EC). 0 to 1000 = 0.0 to 100.0 %."
    },
    {
      "address": 1005,
      "count": 1,
      "name": "Cooling-side MV monitor",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Register 301006(03ED). 0 to 1000 = 0.0 to 100.0 %."
    },
    {
      "address": 1006,
      "count": 1,
      "name": "Indicator and status bit field",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 301007(03EE). Bit 0 = ℃ indicator, 1 = ℉, 2 = %, 3 = OUT1, 4 = OUT2, 5 = AT, 6 = SV1, 7 = SV2, 8 = SV3, 9 = AL1, A = AL2, B = MAN, C = DI-1, D = DI-2."
    },
    {
      "address": 1007,
      "count": 1,
      "name": "Heater current value",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Register 301008(03EF). 0.0 to 50.0 (the row's unit cell is empty); the same quantity's setting 400053(0034) 'Heater Current Monitoring' carries the unit A over the range 0.0-50.0 A, so this reading is in the same unit."
    }
  ],
  "holding_registers": [
    {
      "address": 0,
      "count": 1,
      "name": "SV set value",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400001(0000). Between the SV low and high limits; factory default 0."
    },
    {
      "address": 1,
      "count": 1,
      "name": "Heating-side MV (manual control)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400002(0001). 0 to 1000 = 0.0 to 100.0 %; written in manual mode."
    },
    {
      "address": 2,
      "count": 1,
      "name": "Cooling-side MV (manual control)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400003(0002). 0 to 1000 = 0.0 to 100.0 %; written in manual mode."
    },
    {
      "address": 3,
      "count": 1,
      "name": "Auto/manual control",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400004(0003). 0 = AUTO, 1 = MAN. Factory default AUTO."
    },
    {
      "address": 50,
      "count": 1,
      "name": "Control output RUN/STOP",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400051(0032). 0 = RUN, 1 = STOP. Factory default RUN."
    },
    {
      "address": 51,
      "count": 1,
      "name": "Multi-SV number",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400052(0033). 0 = SV-0, 1 = SV-1, 2 = SV-2, 3 = SV-3. Factory default SV-0."
    },
    {
      "address": 52,
      "count": 1,
      "name": "Heater current monitoring setting",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400053(0034). 0 to 500 = 0.0 to 50.0 A (display range)."
    },
    {
      "address": 53,
      "count": 1,
      "name": "Alarm 1 low-limit set value",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400054(0035). Deviation alarm: -full scale to +full scale; absolute-value alarm: within the display range. The table prints one factory default (1550) for the six alarm-limit rows 0x0035-0x0038 and 0x003D-0x003E."
    },
    {
      "address": 54,
      "count": 1,
      "name": "Alarm 1 high-limit set value",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400055(0036). Same range and block default as 0x0035."
    },
    {
      "address": 55,
      "count": 1,
      "name": "Alarm 2 low-limit set value",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400056(0037). Same range and block default as 0x0035."
    },
    {
      "address": 56,
      "count": 1,
      "name": "Alarm 2 high-limit set value",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400057(0038). Same range and block default as 0x0035."
    },
    {
      "address": 57,
      "count": 1,
      "name": "Set value SV-0",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400058(0039). Within the SV low/high limits; factory default 0000."
    },
    {
      "address": 58,
      "count": 1,
      "name": "Set value SV-1",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400059(003A). Within the SV low/high limits; factory default 0000."
    },
    {
      "address": 59,
      "count": 1,
      "name": "Set value SV-2",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400060(003B). Within the SV low/high limits; factory default 0000."
    },
    {
      "address": 60,
      "count": 1,
      "name": "Set value SV-3",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400061(003C). Within the SV low/high limits; factory default 0000."
    },
    {
      "address": 61,
      "count": 1,
      "name": "Alarm 3 low-limit set value",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400062(003D). Same range and block default as 0x0035."
    },
    {
      "address": 62,
      "count": 1,
      "name": "Alarm 3 high-limit set value",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400063(003E). Same range and block default as 0x0035."
    },
    {
      "address": 100,
      "count": 1,
      "name": "Auto-tuning RUN/STOP",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400101(0064). 0 = OFF, 1 = ON. Factory default OFF."
    },
    {
      "address": 101,
      "count": 1,
      "name": "Heating proportional band",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400102(0065). 0.1 to 99.9 in the units of the input (℃, ℉ or %); factory default 1.0. A proportional band of 0 selects ON/OFF control."
    },
    {
      "address": 102,
      "count": 1,
      "name": "Cooling proportional band",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400103(0066). Same scale and limits as the heating proportional band."
    },
    {
      "address": 103,
      "count": 1,
      "name": "Heating integral time",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400104(0067). 0 to 9999 s; factory default 0."
    },
    {
      "address": 104,
      "count": 1,
      "name": "Cooling integral time",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400105(0068). 0 to 9999 s; factory default 0."
    },
    {
      "address": 105,
      "count": 1,
      "name": "Heating derivative time",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400106(0069). 0 to 9999 s; factory default 0."
    },
    {
      "address": 106,
      "count": 1,
      "name": "Cooling derivative time",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400107(006A). 0 to 9999 s; factory default 0."
    },
    {
      "address": 113,
      "count": 1,
      "name": "MV low-limit set value",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400114(0071). 0.0 % up to the high limit; factory default 0.0."
    },
    {
      "address": 114,
      "count": 1,
      "name": "MV high-limit set value",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400115(0072). Low limit + 0.1 % up to 100.0 %; factory default 100.0."
    },
    {
      "address": 150,
      "count": 1,
      "name": "Input type",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400151(0096). Input-type code, see the input specification table of the manual; factory default TC-K1."
    },
    {
      "address": 151,
      "count": 1,
      "name": "Sensor temperature unit",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400152(0097). 0 = ℃, 1 = ℉. Factory default ℃."
    },
    {
      "address": 160,
      "count": 1,
      "name": "SV low-limit set value",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400161(00A0). Input low limit to SV high limit minus one digit; factory default -200."
    },
    {
      "address": 161,
      "count": 1,
      "name": "SV high-limit set value",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400162(00A1). SV low limit plus one digit to the input high limit; factory default 1350."
    },
    {
      "address": 162,
      "count": 1,
      "name": "Control output operation mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400163(00A2). Standard type: 0 = HEAT, 1 = COOL. Heating/cooling type: 2 = H-C. Factory default HEAT (H-C on the heating/cooling models)."
    },
    {
      "address": 163,
      "count": 1,
      "name": "Control type",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400164(00A3). Standard control: 0 = PID, 1 = ON/OFF. Heating/cooling control: 0 = pP, 1 = Pon, 2 = OnP, 3 = OnON. Factory default PID (pP on the heating/cooling models)."
    },
    {
      "address": 170,
      "count": 1,
      "name": "Heating control time",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400171(00AA). 0.1 to 12.0 s for relay/SSR drive output (standard ON/OFF, phase and cycle control); factory default 2.0."
    },
    {
      "address": 171,
      "count": 1,
      "name": "Cooling control time",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400172(00AB). 0.1 to 12.0 s; factory default 2.0."
    },
    {
      "address": 218,
      "count": 1,
      "name": "Communication address",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400219(00DA). 1 to 99; factory default 01."
    },
    {
      "address": 219,
      "count": 1,
      "name": "Communication speed",
      "data_type": "UInt16",
      "units": "bps",
      "scale_factor": 100,
      "offset": 0,
      "access": "RW",
      "description": "Register 400220(00DB). The unit cell reads 'X100 bps' and the set-range cell lists the five speeds under menu positions 0-4 (24, 48, 96, 192, 384), so the register holds the speed in units of 100 bps: 24 = 2400, 48 = 4800, 96 = 9600, 192 = 19200, 384 = 38400 bps. Factory default 96 = 9600 bps."
    },
    {
      "address": 220,
      "count": 1,
      "name": "Communication parity bit",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400221(00DC). 0 = NONE, 1 = EVEN, 2 = ODD. Factory default NONE."
    },
    {
      "address": 221,
      "count": 1,
      "name": "Communication stop bit",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400222(00DD). 0 = 1 stop bit, 1 = 2 stop bits. Factory default 2 stop bits."
    },
    {
      "address": 222,
      "count": 1,
      "name": "Communication response waiting time",
      "data_type": "UInt16",
      "units": "ms",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400223(00DE). 5 to 99 ms; factory default 20 ms."
    },
    {
      "address": 223,
      "count": 1,
      "name": "Communication write",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400224(00DF). 0 = EnA (writing allowed), 1 = DIsA (writing disabled). Factory default EnA."
    },
    {
      "address": 250,
      "count": 1,
      "name": "Multi-SV count",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400251(00FA). 0 = 1 SV, 1 = 2 SVs, 2 = 4 SVs. Factory default 1."
    },
    {
      "address": 251,
      "count": 1,
      "name": "Digital input key function",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400252(00FB). 0 = STOP, 1 = alarm reset, 2 = AT, 3 = OFF. Factory default STOP."
    },
    {
      "address": 252,
      "count": 1,
      "name": "Digital input DI-1 function",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400253(00FC). 0 = OFF, 1 = STOP, 2 = alarm reset, 3 = MAN, 4 = multi-SV. Factory default OFF."
    },
    {
      "address": 253,
      "count": 1,
      "name": "Digital input DI-2 function",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400254(00FD). Same codes as DI-1; factory default OFF."
    },
    {
      "address": 259,
      "count": 1,
      "name": "User level",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400260(0103). 0 = STND, 1 = HIGH. Factory default STND."
    },
    {
      "address": 260,
      "count": 1,
      "name": "Parameter initialization",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400261(0104). 0 = NO, 1 = YES. Factory default NO."
    }
  ],
  "combined_registers": [],
  "notes": "Source: Autonics 'TK Series User Manual for Communication', revision V1.8 (file mct_tkc1_v1_8_1712en_20171218_he_20180221.pdf on the vendor's European site, https://autonics.se/wp-content/uploads/2018/03/mct_tkc1_v1_8_1712en_20171218_he_20180221.pdf, SHA-256 6f48b619e41865ffeaa1551771c3fc9c8adf9d34153f8975de0b432dd41ca59e): chapter 2 'Modbus Mapping Table' for the coils, input status, input registers and the parameter groups 0-3 and 5, which print both the Modicon-style number (400001) and the hexadecimal PDU address (0000). The seed stores the hexadecimal address unchanged and declares zero_based. Factory serial frame from the same parameter 4 group: communication address 01 (400219), speed value 96 = 9600 bps (400220), parity NONE (400221) and 2 stop bits (400222) - all four are printed 'Factory Default' cells, not inferred. The manual prints no data-length parameter at all, so the frame keeps Modbus RTU's 8 data bits (its worked frames carry one byte per register). The PDF's embedded font prints a decimal point as ')' (so the manual's '01)0' is 01.0); the seed states the decimal values an operator sees. Omitted on purpose: the control rows 0x006B-0x0075 (dead/overlap band, manual reset, heating and cooling hysteresis and OFF offsets, ramp up/down change rates, ramp time unit); the analog range and scaling rows 0x0098-0x009F; the auto-tuning-mode and output-configuration rows 0x00A4-0x00A9; the alarm 1/2 block 0x00C8-0x00D6; the analog-transmission and alarm-3 blocks 0x00D7-0x00D9 and 0x00E0-0x00E8 (optional output boards); the manual-mode MV rows 0x00FF-0x0102; the parameter-lock rows 0x0105-0x010A with the password at 0x010B; the 30-word user parameter group 0x012C-0x0149 (meaning set by each parameter); and every 'Reserved' range. The self-describing start/quantity rows are in the input area (input 0x0075-0x007C) and are not seeded either."
}