ZIEHL-ABEGG · Fan controller
ECblue BASIC-MODBUS EC fans and motors Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 247
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 19200
- Parity
- Even
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 0 | 1 | Firmware version i0. Firmware version of the ECblue electronics, printed as xx.xx (range 0.00 - 655.35), so the raw word is divided by 100. | UInt16 | - | 0.01 | R |
| 1 | 1 | Product code 1 (controller code) i1. Controller code of the device. | UInt16 | - | 1 | R |
| 2 | 1 | Parameter set ID i2. Identifier of the loaded parameter set. | UInt16 | - | 1 | R |
| 9 | 1 | Parameter set index i9. Index of the loaded parameter set. | UInt16 | - | 1 | R |
| 10 | 1 | Operation condition 1 i10. Bit-coded operating state of the fan. | Binary | - | 1 | R |
| 11 | 1 | Operation condition 2 i11. Bit-coded operating state of the fan (from firmware 14). | Binary | - | 1 | R |
| 12 | 1 | Error status i12. Bit-coded error status; selected entries are copied into i29/i30 by PIN codes 7500...7509. | Binary | - | 1 | R |
| 13 | 1 | Error status 2 i13. Second, bit-coded error word. | Binary | - | 1 | R |
| 14 | 1 | Speed i14. Actual speed in 1/min. | UInt16 | rpm | 1 | R |
| 15 | 1 | Motor current i15. Actual motor current in 0.01 A steps. | UInt16 | A | 0.01 | R |
| 20 | 1 | DC-link voltage i20. DC-link voltage in 1 V steps. | UInt16 | V | 1 | R |
| 21 | 1 | Line voltage i21. Supply voltage (peak value) in 1 V steps. | UInt16 | V | 1 | R |
| 22 | 1 | IGBT temperature i22. IGBT temperature; 200 = 20.0 degC. | Int16 | degC | 0.1 | R |
| 23 | 1 | Temperature inside the electronics i23. Ambient temperature of the electronics inside the housing; 200 = 20.0 degC. | Int16 | degC | 0.1 | R |
| 24 | 1 | MCU temperature i24. Chip temperature; 200 = 20.0 degC. | Int16 | degC | 0.1 | R |
| 26 | 1 | E1 input i26. Raw value at the analogue input E1: 0...32767 = 0...10 V or 0...100 % PWM. | UInt16 | - | 1 | R |
| 27 | 1 | Control (modulation level) i27. Fan level of the speed controller: 0...32767 = 0...100 %. | UInt16 | % | 0.0030518509475997192 | R |
| 29 | 1 | MSW of the selected event-log entry i29. Most significant word; format as error status i13. | Binary | - | 1 | R |
| 30 | 1 | LSW of the selected event-log entry i30. Least significant word; format as error status i12. | Binary | - | 1 | R |
| 31 | 1 | Event-log entry number i31. Item of the selected event-log entry (7500 = most recent fault). | UInt16 | - | 1 | R |
| 32 | 1 | Power factor i32. cos(phi) at the inverter output; the document prints the raw range 0...65535 only. | UInt16 | - | 1 | R |
| 33 | 1 | Motor input power i33. Motor input power in watts. | UInt16 | W | 1 | R |
| 40 | 1 | Reactor temperature i40. Temperature at the input reactor; 200 = 20.0 degC. | Int16 | degC | 0.1 | R |
| 45 | 1 | Motor voltage i45. Effective motor voltage; 2000 = 200.0 V. | UInt16 | V | 0.1 | R |
| 47 | 1 | Motor current, phase U i47. Maximum value of the current in phase U; 2000 = 2.00 A. | UInt16 | A | 0.01 | R |
| 48 | 1 | Motor current, phase V i48. Maximum value of the current in phase V; 2000 = 2.00 A. | UInt16 | A | 0.01 | R |
| 49 | 1 | Inquiry PIN protection level i49. Active write-authorization level 0...3 (see h16 bits 9:8). | UInt16 | - | 1 | R |
| 50 | 1 | Remaining lifetime i50. Remaining lifetime of the electronics in hours. | UInt16 | h | 1 | R |
| 55 | 1 | Motor installation position i55. 0 = vertical installation (motor shaft horizontal), 1 = horizontal installation (motor shaft vertical). | UInt16 | - | 1 | R |
| 59 | 1 | Vibration velocity, X axis (1st order) i59. Vibration velocity in mm/s x 100 (0...655.35 mm/s). | UInt16 | mm/s | 0.01 | R |
| 60 | 1 | Vibration velocity, Y axis (1st order) i60. Vibration velocity in mm/s x 100 (0...655.35 mm/s). | UInt16 | mm/s | 0.01 | R |
| 61 | 1 | Vibration velocity, Z axis (1st order) i61. Vibration velocity in mm/s x 100 (0...655.35 mm/s). | UInt16 | mm/s | 0.01 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: ZIEHL-ABEGG "Description MODBUS Communication ECblue BASIC-MODBUS", L-BAL-E311-GB 1934 Index 001, software version ECblue firmware from 1.00, marked "Preliminary edition"; copy read is the vendor PDF mirrored at ivprodukt.com/file/3141, SHA-256 a1d33d7c2bb31d89ae4c756693a51fb312c5c7e67dc72444322a6e3c9e615fbe. The interface is Modbus RTU over RS-485 (2160EC / 2160 series EC fans and motors with ECblue BASIC electronics). Factory frame: holding register h3 documents bus address default 247, baud rate default 19200 bit/s and COM mode default 8E1 (8 data bits, even parity, 1 stop bit), and section 4 (emergency scenario) repeats "Baudrate: 19200 / Parity: 8E1" for the recovery defaults - so the seed declares 19200 8E1 at unit 247. Setting another address/frame is done by writing h3 and then a reset (PIN 2143 or power cycle); section 4's MODBUS Recovery Function answers on address 254, which is not the factory address. 3.2 states the application data start at MODBUS register address 0 in both areas, and the table's h/i numbers are used as the wire address, so the seed is zero_based; holding registers use FC 3/6/16 and input registers FC 4. Omitted by scope: the 6-register unique device signature i3...i8, the operating-hours and air-flow counters printed as separate 16-bit words (i38/i39, i42/i43), holding h37 (Fan Bad), the antiblock rows h50...h55, the vibration and lifetime thresholds h60...h71 and h80...h84, and the type-specific factory registers h20...h24 and h26...h29. Registers that need PIN protection level 1 or 2 stay writable in the seed but carry the level in the description.