ECblue BASIC-MODBUS EC fans and motors Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
247
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Firmware version
i0. Firmware version of the ECblue electronics, printed as xx.xx (range 0.00 - 655.35), so the raw word is divided by 100.
UInt16-0.01R
11
Product code 1 (controller code)
i1. Controller code of the device.
UInt16-1R
21
Parameter set ID
i2. Identifier of the loaded parameter set.
UInt16-1R
91
Parameter set index
i9. Index of the loaded parameter set.
UInt16-1R
101
Operation condition 1
i10. Bit-coded operating state of the fan.
Binary-1R
111
Operation condition 2
i11. Bit-coded operating state of the fan (from firmware 14).
Binary-1R
121
Error status
i12. Bit-coded error status; selected entries are copied into i29/i30 by PIN codes 7500...7509.
Binary-1R
131
Error status 2
i13. Second, bit-coded error word.
Binary-1R
141
Speed
i14. Actual speed in 1/min.
UInt16rpm1R
151
Motor current
i15. Actual motor current in 0.01 A steps.
UInt16A0.01R
201
DC-link voltage
i20. DC-link voltage in 1 V steps.
UInt16V1R
211
Line voltage
i21. Supply voltage (peak value) in 1 V steps.
UInt16V1R
221
IGBT temperature
i22. IGBT temperature; 200 = 20.0 degC.
Int16degC0.1R
231
Temperature inside the electronics
i23. Ambient temperature of the electronics inside the housing; 200 = 20.0 degC.
Int16degC0.1R
241
MCU temperature
i24. Chip temperature; 200 = 20.0 degC.
Int16degC0.1R
261
E1 input
i26. Raw value at the analogue input E1: 0...32767 = 0...10 V or 0...100 % PWM.
UInt16-1R
271
Control (modulation level)
i27. Fan level of the speed controller: 0...32767 = 0...100 %.
UInt16%0.0030518509475997192R
291
MSW of the selected event-log entry
i29. Most significant word; format as error status i13.
Binary-1R
301
LSW of the selected event-log entry
i30. Least significant word; format as error status i12.
Binary-1R
311
Event-log entry number
i31. Item of the selected event-log entry (7500 = most recent fault).
UInt16-1R
321
Power factor
i32. cos(phi) at the inverter output; the document prints the raw range 0...65535 only.
UInt16-1R
331
Motor input power
i33. Motor input power in watts.
UInt16W1R
401
Reactor temperature
i40. Temperature at the input reactor; 200 = 20.0 degC.
Int16degC0.1R
451
Motor voltage
i45. Effective motor voltage; 2000 = 200.0 V.
UInt16V0.1R
471
Motor current, phase U
i47. Maximum value of the current in phase U; 2000 = 2.00 A.
UInt16A0.01R
481
Motor current, phase V
i48. Maximum value of the current in phase V; 2000 = 2.00 A.
UInt16A0.01R
491
Inquiry PIN protection level
i49. Active write-authorization level 0...3 (see h16 bits 9:8).
UInt16-1R
501
Remaining lifetime
i50. Remaining lifetime of the electronics in hours.
UInt16h1R
551
Motor installation position
i55. 0 = vertical installation (motor shaft horizontal), 1 = horizontal installation (motor shaft vertical).
UInt16-1R
591
Vibration velocity, X axis (1st order)
i59. Vibration velocity in mm/s x 100 (0...655.35 mm/s).
UInt16mm/s0.01R
601
Vibration velocity, Y axis (1st order)
i60. Vibration velocity in mm/s x 100 (0...655.35 mm/s).
UInt16mm/s0.01R
611
Vibration velocity, Z axis (1st order)
i61. Vibration velocity in mm/s x 100 (0...655.35 mm/s).
UInt16mm/s0.01R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: ZIEHL-ABEGG "Description MODBUS Communication ECblue BASIC-MODBUS", L-BAL-E311-GB 1934 Index 001, software version ECblue firmware from 1.00, marked "Preliminary edition"; copy read is the vendor PDF mirrored at ivprodukt.com/file/3141, SHA-256 a1d33d7c2bb31d89ae4c756693a51fb312c5c7e67dc72444322a6e3c9e615fbe. The interface is Modbus RTU over RS-485 (2160EC / 2160 series EC fans and motors with ECblue BASIC electronics). Factory frame: holding register h3 documents bus address default 247, baud rate default 19200 bit/s and COM mode default 8E1 (8 data bits, even parity, 1 stop bit), and section 4 (emergency scenario) repeats "Baudrate: 19200 / Parity: 8E1" for the recovery defaults - so the seed declares 19200 8E1 at unit 247. Setting another address/frame is done by writing h3 and then a reset (PIN 2143 or power cycle); section 4's MODBUS Recovery Function answers on address 254, which is not the factory address. 3.2 states the application data start at MODBUS register address 0 in both areas, and the table's h/i numbers are used as the wire address, so the seed is zero_based; holding registers use FC 3/6/16 and input registers FC 4. Omitted by scope: the 6-register unique device signature i3...i8, the operating-hours and air-flow counters printed as separate 16-bit words (i38/i39, i42/i43), holding h37 (Fan Bad), the antiblock rows h50...h55, the vibration and lifetime thresholds h60...h71 and h80...h84, and the type-specific factory registers h20...h24 and h26...h29. Registers that need PIN protection level 1 or 2 stay writable in the seed but carry the level in the description.