All devices

ebm-papst · Fan controller

EC fans with integrated Modbus (product range, identification 0x0011) register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Identification
D000. 0x0011 identifies the ebm-papst product range at specification version 6.2.
Hex-1R
11
Maximum number of bytes per telegram
D001. Contrary to the general Modbus specification the maximum telegram length is 80 bytes.
UInt16bytes1R
31
Bus controller software version
D003. Software version of the bus controller (LSB; the MSB is always 0).
UInt16-1R
51
Commutation controller software version
D005. Software version of the commutation controller (LSB; the MSB is always 0).
UInt16-1R
161
Current speed
D010. Speed-referenced: 64000 = maximum speed (holding 281 / D119); the display is limited to 1.02 x maximum speed (0xFFF0).
UInt16-1R
171
Motor status (errors)
D011. Bit 0 PHA (phase failure / line undervoltage), 1 TFE (output stage overheating), 2 SKF (master/slave communication error), 3 FB (fan bad), 4 TFM (motor overheating), 5 HLL (Hall sensor error), 6 BLK (motor blocked), 8 n_Limit (speed limit exceeded), 10 RL_Cal (rotor position calibration error), 12 UzLow (DC-link undervoltage).
Binary-1R
181
Warning
D012. Bit 0 I_Limit, 1 L_high, 2 P_Limit, 3 TE_high, 4 TM_high, 5 TEI_high, 6 UzLow, 7 Brems, 8 RL_Cal, 9 n_Low, 10 Kabelbr. (open circuit at the set value input), 12 UzHigh, 14 UeHigh, 15 LRF (shedding active).
Binary-1R
241
Current direction of rotation
D018. 0 = counter-clockwise, 1 = clockwise.
UInt16-1R
251
Current modulation level
D019. 65536 = 100 %.
UInt16%0.00152587890625R
261
Current set value
D01A. In speed control mode 64000 = maximum speed (D119); in open-loop control mode 65536 = 100 %; in sensor control mode referenced to the sensor characteristic curve.
UInt16-1R
271
Sensor actual value
D01B. Actual value of the external sensor selected by the source sensor value (D147), 65536 = 10 V at the analog input.
UInt16-1R
281
Enable/Disable input state
D01C. 0 = enable off (motor stop), 1 = enable on (motor start permitted).
UInt16-1R
291
Current parameter set
D01D. 0 = parameter set 1, 1 = parameter set 2.
UInt16-1R
301
Current controller function
D01E. 0 = positive (heating), 1 = negative (cooling).
UInt16-1R
391
Current power
D027. The numerical value corresponds directly to the current power in W; no reference values are needed.
UInt16W1R
401
Current set value source
D028. 0 = analog input Ain1, 1 = RS485 (setpoint D001), 2 = analog input Ain2, 3 = PWM input PWMin3, 255 = fail-safe set value.
UInt16-1R
751
MEMS sensor status
D04B. Bit 0 test run interval elapsed, 1 XE_Err (communication break to the MEMS sensor), 2 more than 5 ranges detected, 4 limit (vibration velocity limit exceeded), 5 Ausbl (operating set value masked out).
Binary-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: ebm-papst "MODBUS parameter specification for 'ebm-papst product range'" V6.2, document en-US_MODBUS_6_2_Auszug.docx, dated 6 March 2019 (the vendor excerpt: parameters for ebm-papst internal use are marked "Reserved"). Copy read: ebmpapst.se/sv/dat/site_common/upload/MODBUS_Series_V6.2_Excerpt.pdf, SHA-256 37fd6ac881db850be68694a964603e16a96c067c7c0994246f17891c39c55baa. Covers every fan of the product range whose electronics answer identification 0x0011 (e.g. RadiPac and HyBlade EC fans with integrated Modbus). Factory frame, from 2.44.3 ("leave the interface settings on the default values") and the parity table 2.44.2: 19200 bit/s, 8 data bits, even parity, 1 stop bit. Fan address: 1.3.6 states "All ex works fans have the same address 1" (range 1...247, 0 = broadcast) - 19200 8E1 at unit 1. Register addresses: the document prints them as D000...D1AA; the seed stores the decimal value of those hex numbers (D100 = 0x0100 = 256), and the worked frames in 1.3 send the address as-is and 1.1 documents the RTU byte structure, so the seed is zero_based. Several rows of the 2.1 overview print the address one row out of line with the parameter's own section - 2.1 puts transmission speed and parity at D148/D149 where 2.44.1 and 2.44.2 print D149/D14A - so the seed stores the per-section address. Scale factors come from the printed codings: current modulation level and the 0-10 V remote control value are word/65536 x 100 %, the modulation-level limits and set-points are word/256 x 100 %, and the absolute power row is already in W. Omitted: DC-link voltage and current (D013/D014), the three temperatures (D015...D017), the energy counter (D029), the mirrored blocks (input D100...D10F, holding D380...D39F and D480...D49F), the software-name rows (D002/D004) and every parameter the excerpt marks "Reserved". Registers whose write authorization is ebm-papst only are listed with access R and say so.