Trane · Chiller

Ascend ACRB air-cooled chiller (Symbio 800 controls) Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
1-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
112
Active chilled water setpoint
Chilled water setpoint the chiller is currently controlling to, after arbitration between BAS, external and front-panel sources.
Float32°F1R
132
Evaporator entering water temperature
Water temperature entering the evaporator (return from the cooling load).
Float32°F1R
152
Evaporator leaving water temperature
Water temperature leaving the evaporator (supply to the cooling load).
Float32°F1R
172
Calculated chiller capacity
Cooling capacity the chiller is currently delivering, in tons of refrigeration.
Float32ton1R
192
Active demand limit setpoint
Demand limit the chiller is currently applying.
Float32%1R
212
Unit power consumption
Electrical input power of the whole chiller.
Float32kW1R
252
Outdoor air temperature
Ambient temperature at the unit.
Float32°F1R
272
Evaporator refrigerant pressure, circuit 1
Refrigerant pressure in the evaporator of circuit 1.
Float32psi1R
292
Condenser refrigerant pressure, circuit 1
Refrigerant pressure in the condenser of circuit 1.
Float32psi1R
312
Differential refrigerant pressure, circuit 1
Difference between discharge and suction pressure on circuit 1.
Float32psi1R
332
Evaporator saturated refrigerant temperature, circuit 1
Saturated refrigerant temperature in the evaporator of circuit 1.
Float32°F1R
352
Condenser saturated refrigerant temperature, circuit 1
Saturated refrigerant temperature in the condenser of circuit 1.
Float32°F1R
372
Evaporator refrigerant pressure, circuit 2
Refrigerant pressure in the evaporator of circuit 2.
Float32psi1R
392
Condenser refrigerant pressure, circuit 2
Refrigerant pressure in the condenser of circuit 2.
Float32psi1R
412
Differential refrigerant pressure, circuit 2
Difference between discharge and suction pressure on circuit 2.
Float32psi1R
432
Evaporator saturated refrigerant temperature, circuit 2
Saturated refrigerant temperature in the evaporator of circuit 2.
Float32°F1R
452
Condenser saturated refrigerant temperature, circuit 2
Saturated refrigerant temperature in the condenser of circuit 2.
Float32°F1R
472
Refrigerant discharge temperature, compressor 1A
Discharge gas temperature of compressor 1A.
Float32°F1R
492
Oil pressure, compressor 1A
Oil pressure on the high-pressure side of compressor 1A.
Float32psi1R
512
Refrigerant discharge temperature, compressor 2A
Discharge gas temperature of compressor 2A.
Float32°F1R
532
Oil pressure, compressor 2A
Oil pressure on the high-pressure side of compressor 2A.
Float32psi1R
552
Air flow percentage, circuit 1
Approximate air flow through circuit 1.
Float32%1R
572
Air flow percentage, circuit 2
Approximate air flow through circuit 2.
Float32%1R
592
Starts, compressor 1A
Number of starts of compressor 1A.
Float32-1R
612
Run time, compressor 1A
Accumulated run time of compressor 1A.
Float32h1R
632
Compressor 1A speed status
Percentage of available speed currently used by compressor 1A.
Float32%1R
692
Drive motor current U, compressor 1A (RLA)
Line 1 current at the compressor 1A drive, as a percentage of rated load amps.
Float32%1R
712
Drive motor current V, compressor 1A (RLA)
Line 2 current at the compressor 1A drive, as a percentage of rated load amps.
Float32%1R
732
Drive motor current W, compressor 1A (RLA)
Line 3 current at the compressor 1A drive, as a percentage of rated load amps.
Float32%1R
932
Drive output power, circuit 1
Power delivered by the compressor drive of circuit 1.
Float32kW1R
1112
Starts, compressor 2A
Number of starts of compressor 2A.
Float32-1R
1132
Run time, compressor 2A
Accumulated run time of compressor 2A.
Float32h1R
1732
Energy consumption, lifetime
Total electrical energy consumed by the unit since commissioning.
Float32kWh1R
1812
Active cool/heat setpoint temperature
Active setpoint for the current mode (cooling or heating).
Float32°F1R
20101
Running mode
1 = Chiller off, 2 = Chiller in start mode, 3 = Chiller in run mode, 4 = Chiller in pre-shutdown mode, 5 = Chiller in service mode.
UInt16-1R
20111
Operating mode
1 = Cool, 2 = Heat, 3 = Ice making, 4 = Free cooling.
UInt16-1R
20121
Chiller setpoint source
1 = BAS, 2 = External, 3 = Front panel.
UInt16-1R
30101
Run enable
0 = Run not enabled, 1 = Run enabled.
Int16-1R
30111
Local setpoint control
0 = Remote control, 1 = Local control.
Int16-1R
30131
Chiller running state
0 = Off, 1 = On.
Int16-1R
30151
Evaporator water pump command
0 = Off, 1 = On. Request from the chiller to run the evaporator water pump.
Int16-1R
30161
Evaporator water flow status
1 = Flow, 0 = No flow (the chiller may refuse to start).
Int16-1R
30181
Emergency stop
0 = Auto, 1 = Emergency stop, manual reset required.
Int16-1R
30191
Diagnostic present
1 = In alarm, 0 = Normal.
Int16-1R
30201
Diagnostic shutdown present
1 = Chiller is shut down by a diagnostic, 0 = Normal.
Int16-1R
30211
Diagnostic: manual reset required
1 = A diagnostic requiring manual reset is active, 0 = Normal.
Int16-1R
30251
Diagnostic present: critical
1 = Critical-category diagnostic present, 0 = Normal.
Int16-1R
30261
Diagnostic present: service required
1 = Service-required diagnostic present, 0 = Normal.
Int16-1R
30271
Running status, compressor 1A
0 = Off, 1 = Running.
Int16-1R
30281
Running status, compressor 2A
0 = Off, 1 = Running.
Int16-1R
30291
Free cooling active
0 = Inactive, 1 = Active.
Int16-1R
30301
External auto/stop
State of the hard-wired auto/stop input: 0 = Stop, 1 = Auto.
Int16-1R
30321
Noise reduction request active
0 = Off, 1 = On.
Int16-1R

Notes

This is the Modbus points list for Ascend ACRB 150-300 ton chillers with Symbio 800 controls (Trane integration guide BAS-SVP045B-EN). Larger ACRB 350-500 ton units use a different set of register numbers with the same object names, so check the points list for your unit size. Symbio 800 serves Modbus TCP on Ethernet port 1 once the system protocol is set to Modbus TCP in the controller; the rotary address applies only to Modbus RTU, so the unit identifier is not used for TCP and 1 is sent here. Addresses are the register numbers from the Trane points list without their Modicon area prefix (input register 30011 is listed as 11, holding register 40010 as 10), one-based, so the wire address is the number minus one; Float32 values occupy two registers and are transmitted big-endian, high word first. Values are US units (degrees Fahrenheit, psi, tons of refrigeration). Port 2 of the controller is reserved for the TD7 display.