Daikin Applied · Chiller

Trailblazer AGZ/AMZ, Pathfinder AWS/AWV, ADS, Magnitude WME and Navigator WWV chillers (MicroTech III) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
1-based
Byte order
Big endian
Word order
Low word first
Baud rate
38400
Parity
None
Data bits
8
Stop bits
2

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
81
Chiller ON/OFF
0 = OFF, 1 = ON.
UInt16-1R
11
Chiller Local/Remote
0 = Remote, 1 = Local. Can only be changed on the unit keypad; when Local, the network setpoints are ignored.
UInt16-1R
21
Chiller Enable Output
0 = Disabled, 1 = Enabled.
UInt16-1R
31
Run Enabled
0 = OFF, 1 = Run Allowed. Indicates the chiller can start if operating conditions are met.
UInt16-1R
41
Chiller Capacity Limited
0 = Not Limited, 1 = Limited.
UInt16-1R
51
Alarm Digital Output
0 = No Alarm, 1 = Alarm. Must be polled for alarm notification.
UInt16-1R
61
Evaporator Flow Switch Status
0 = No Flow, 1 = Flow.
UInt16-1R
71
Condenser Flow Switch Status
0 = OFF, 1 = ON.
UInt16-1R
91
Chiller Enable Setpoint
0 = Disable, 1 = Enable, 2 = Null. Ignored when Chiller Local/Remote is Local.
UInt16-1RW
101
Clear Alarms - Network
0 = Normal, 1 = Clear Alarms, 2 = Null. Ignored when Chiller Local/Remote is Local.
UInt16-1RW
111
Chiller Mode Output
1 = Ice, 2 = Cool, 3 = Heat, 4 = Cool/Heat Recovery, 5 = Defrost.
UInt16-1R
121
Active Setpoint
Setpoint the chiller is currently controlling to, after arbitration of the BAS, external and front-panel sources. Transmitted as °F x 10.
Int16°F0.1R
131
Actual Capacity
Percent of maximum capacity currently produced. Transmitted as % x 10.
UInt16%0.1R
141
Active Capacity Limit Output
Lowest of the capacity limits in force. Transmitted as % x 10.
UInt16%0.1R
151
Chiller Status
1 = OFF, 2 = Start, 3 = Run, 4 = Pre Shutdown, 5 = Service.
UInt16-1R
161
Evaporator Entering Fluid Temperature
Fluid entering the evaporator. Transmitted as °F x 10.
Int16°F0.1R
171
Evaporator Leaving Fluid Temperature
Fluid leaving the evaporator. Transmitted as °F x 10.
Int16°F0.1R
181
Evaporator Fluid Flow Rate
Fluid flow through the evaporator (0 to 65,535 GPM).
UInt16GPM1R
191
Condenser Entering Fluid Temperature
Fluid entering the condenser. Transmitted as °F x 10.
Int16°F0.1R
201
Condenser Leaving Fluid Temperature
Fluid leaving the condenser. Transmitted as °F x 10.
Int16°F0.1R
211
Condenser Fluid Flow Rate
Fluid flow through the condenser (0 to 65,535 GPM).
UInt16GPM1R
241
Outdoor Air Temperature
Outdoor air temperature. Transmitted as °F x 10.
Int16°F0.1R
251
Chiller Current
Average chiller current (0 to 10,000 A).
UInt16A1R
271
Total Kilowatts
Total chiller power (0 to 3,500 kW).
UInt16kW1R
341
Chiller Mode Setpoint - Network
0 = Null, 1 = Ice, 2 = Cool, 3 = Heat, 4 = Cool/Heat Recovery. Ignored when Chiller Local/Remote is Local.
UInt16-1RW
351
Cool Setpoint - Network
Cooling leaving-fluid setpoint (24.98 to 60.08 °F). Default 43.88 °F, transmitted as °F x 10.
Int16°F0.1RW
361
Ice Setpoint - Network
Ice-mode leaving-fluid setpoint: 17.6 to 39.2 °F on AWS/AWV/WWV, 15.08 to 38.12 °F on AGZ/AMZ. Default 24.98 °F, transmitted as °F x 10.
Int16°F0.1RW
381
Capacity Limit Setpoint - Network
Maximum capacity the chiller may deliver (0 to 100 %). Default 100 %, transmitted as % x 10.
UInt16%0.1RW
18551
Waterside Economizer Enable Setpoint
0 = Disable, 1 = Enable. Only used on units with the optional waterside economizer and when Chiller Local/Remote is Network.
UInt16-1RW
18541
Waterside Economizer State
0 = Off, 1 = Mech, 2 = Hybrid, 3 = WsEcon. Only on units with the optional waterside economizer.
UInt16-1R
391
Circuit 1 condenser refrigerant pressure
Circuit 1 condenser pressure, transmitted as psi x 10 (0 to 410 psi; 700 psi on R-410A).
UInt16psi0.1R
401
Circuit 1 condenser saturated refrigerant temperature
Circuit 1 saturated condenser temperature, transmitted as °F x 10.
Int16°F0.1R
411
Circuit 1 evaporator refrigerant pressure
Circuit 1 evaporator pressure, transmitted as psi x 10 (-349.97 to 349.97 psi).
Int16psi0.1R
19841
Circuit 1 liquid line refrigerant temperature
Circuit 1 liquid-line temperature, transmitted as °F x 10.
Int16°F0.1R
19901
Circuit 1 suction refrigerant temperature
Refrigerant temperature entering the circuit 1 compressor (-40 to 230 °F).
Int16°F1R
431
Circuit 2 condenser refrigerant pressure
Circuit 2 condenser pressure, transmitted as psi x 10 (0 to 410 psi; 700 psi on R-410A).
UInt16psi0.1R
441
Circuit 2 condenser saturated refrigerant temperature
Circuit 2 saturated condenser temperature, transmitted as °F x 10.
Int16°F0.1R
451
Circuit 2 evaporator refrigerant pressure
Circuit 2 evaporator pressure, transmitted as psi x 10 (-349.97 to 349.97 psi).
Int16psi0.1R
631
Compressor 1 suction refrigerant pressure
Circuit 1 compressor 1 suction pressure, transmitted as psi x 10.
UInt16psi0.1R
651
Compressor 1 suction refrigerant temperature
Refrigerant temperature entering circuit 1 compressor 1, transmitted as °F x 10.
Int16°F0.1R
661
Compressor 1 discharge refrigerant pressure
Circuit 1 compressor 1 discharge pressure, transmitted as psi x 10.
UInt16psi0.1R
681
Compressor 1 discharge refrigerant temperature
Circuit 1 compressor 1 discharge temperature, transmitted as °F x 10.
Int16°F0.1R
691
Compressor 1 percent RLA
Current percent RLA of the circuit 1 compressor 1 motor.
UInt16%1R
701
Compressor 1 current
Average current of the circuit 1 compressor 1 motor (0 to 10,000 A).
UInt16A1R
711
Compressor 1 voltage
Average voltage of the circuit 1 compressor 1 motor (0 to 15,000 V).
UInt16V1R
721
Compressor 1 power
Circuit 1 compressor 1 motor power (0 to 3,500 kW).
UInt16kW1R
731
Compressor 1 starts
Number of times circuit 1 compressor 1 has been started (0 to 65,535).
UInt16starts1R
742
Compressor 1 run hours
Operating hours of circuit 1 compressor 1; two holding registers, low word first (register 74 = 0x863C, 75 = 0x0001 for 99,900 h).
UInt32h1RW
9041
Compressor 1 stator temperature 1
Motor stator sensor 1, transmitted as °F x 10.
Int16°F0.1R
9101
Compressor 1 stator temperature 2
Motor stator sensor 2, transmitted as °F x 10.
Int16°F0.1R
9161
Compressor 1 stator temperature 3
Motor stator sensor 3, transmitted as °F x 10.
Int16°F0.1R
9221
Compressor 1 motor gap temperature
Motor gap temperature, transmitted as °F x 10.
Int16°F0.1R
9281
Compressor 1 motor case temperature
Motor case temperature, transmitted as °F x 10.
Int16°F0.1R
9341
Compressor 1 rotor pump temperature
Rotor pump temperature, transmitted as °F x 10.
Int16°F0.1R
9401
Compressor 1 lift temperature
Lift temperature, transmitted as °F x 10.
Int16°F0.1R
9461
Compressor 1 lift pressure
Lift pressure, transmitted as psi x 10 (0 to 410 psi; 700 psi on R-410A).
UInt16psi0.1R
9701
Compressor 1 unavailable
0 = Available, 1 = Unavailable. AWV units need application code 263220112 or newer.
UInt16-1R
18491
Compressor 1 oil feed pressure
Oil feed pressure, transmitted as psi x 10.
UInt16psi0.1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Daikin Applied "MicroTech Chiller Unit Controller - Protocol Information, Modbus Networks", ED 15121-12, October 2023 (https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/MicroTech%20Chiller%20UC%20Modbus%20Tech%20Sheet%20ED%2015121-12.pdf) and "MicroTech Chiller Unit Controller Modbus Communication Module" IM 969-7, October 2023 (https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/Daikin_Applied_IM_969-7_MT_Chiller_Modbus_Comm_Manual.pdf). Covers the shared MicroTech III chiller map; which points exist depends on the model and options (waterside economizer, number of circuits and compressors). The controller contains only holding registers (4xxxx): ED 15121-12 section "Register Mapping" states that the tables assume 4xxxx addressing and that holding register 40001 is shown as 1, so the numbers here are the supplier's one-based register numbers and the PDU address is one less. All values are 16-bit except the compressor run-hour counters, which span two registers with the low word first (worked example in "Modbus Data Point": 99,900 h at registers 74-75 gives 74 = 0x863C, 75 = 0x0001), hence word_order LowFirst. Rows whose range column carries an x10 mark are transmitted as ten times the engineering value, hence scale_factor 0.1. Serial settings are the communication module's factory values from IM 969-7 Table 3: address 1, 38400 bps, no parity, two stop bits. The unit is reached over RS-485 through a Modbus RTU-to-TCP gateway, so the native interface is RS-485. Circuit 2/3/4 and compressor 2/3 rows that repeat the same pattern were left out to keep the seed on the shared, most-used points; every address in the document is available for extension. Bit-level alarm registers are not modelled.