SH series hybrid / SG series string inverter Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
1-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
50001
Device type code
Inverter family code; see the adaptive model table in Sungrow's protocol document.
UInt16-1R
50011
Nominal output power
UInt16kW0.1R
50021
Output type
0 = single phase, 1 = three phase 4-wire, 2 = three phase 3-wire.
UInt16-1R
50081
Inside temperature
Int16°C0.1R
50111
MPPT 1 voltage
UInt16V0.1R
50121
MPPT 1 current
UInt16A0.1R
50131
MPPT 2 voltage
UInt16V0.1R
50141
MPPT 2 current
UInt16A0.1R
50151
MPPT 3 voltage
UInt16V0.1R
50161
MPPT 3 current
UInt16A0.1R
50172
Total DC power
UInt32W1R
50191
Line voltage A-B / phase A voltage
Phase voltage on single-phase units, line-to-line voltage on three-phase units set to 3P3L.
UInt16V0.1R
50201
Line voltage B-C / phase B voltage
UInt16V0.1R
50211
Line voltage C-A / phase C voltage
UInt16V0.1R
50332
Reactive power
Int32var1R
50351
Power factor
Positive = leading, negative = lagging.
Int16-0.001R
51151
MPPT 4 voltage
Only on models with four MPP trackers.
UInt16V0.1R
51161
MPPT 4 current
UInt16A0.1R
52142
Battery power
Preferred battery power register; positive = charging.
Int32W1R
52421
Grid frequency (high resolution)
UInt16Hz0.01R
56012
Meter active power
Only valid when the inverter is directly connected to a Sungrow smart energy meter; positive = export.
Int32W1R
56281
BDC rated power
Rated battery converter power; the 100 % reference for the charge/discharge power setting (13052).
UInt16kW0.1R
56311
Battery current
Preferred battery current register.
Int16A0.1R
56391
Battery capacity (high precision)
UInt16kWh0.01R
57262
Total backup power
Int32W1R
130001
Running state
See the running state table in Sungrow's protocol document (standby, running, fault, ...).
UInt16-1R
130011
Power flow status
Encodes where the power currently flows; see the power flow state table.
UInt16-1R
130021
Daily PV generation
UInt16kWh0.1R
130032
Total PV generation
UInt32kWh0.1R
130051
Daily export energy from PV
UInt16kWh0.1R
130062
Total export energy from PV
UInt32kWh0.1R
130082
Load power
Int32W1R
130102
Export power
Power delivered by the inverter to the grid.
Int32W1R
130201
Battery voltage
UInt16V0.1R
130211
Battery current
Signed on SH3.0-6.0RS and SH8.0-10RS; register 5631 is the preferred source.
Int16A0.1R
130221
Battery power
Signed in practice (positive = charging); register 5214-5215 is the preferred source.
Int16W1R
130231
Battery state of charge (SOC)
UInt16%0.1R
130251
Battery temperature
Int16°C0.1R
130261
Daily battery discharge energy
UInt16kWh0.1R
130272
Total battery discharge energy
UInt32kWh0.1R
130311
Phase A current
Only the phases present in the output type are filled.
Int16A0.1R
130321
Phase B current
Int16A0.1R
130331
Phase C current
Int16A0.1R
130342
Total active power
Int32W1R
130361
Daily import energy
UInt16kWh0.1R
130372
Total import energy
UInt32kWh0.1R
130391
Battery capacity
0.1 kWh for lithium batteries, 1 Ah for lead-acid batteries; register 5639 has 0.01 kWh resolution.
UInt16kWh0.1R
130401
Daily charge energy
UInt16kWh0.1R
130412
Total charge energy
UInt32kWh0.1R
130451
Daily export energy
UInt16kWh0.1R
130462
Total export energy
UInt32kWh0.1R
130502
Inverter alarm
Alarm bit field; see the fault code appendix.
UInt32-1R

Notes

Address convention: Sungrow's protocol document numbers registers from 1, and the device expects the number minus one on the wire ("visit all registers by subtracting 1 from the register address"). This file therefore declares one_based addressing and lists Sungrow's register numbers unchanged; a client that works with wire addresses must subtract 1. Read-only running information is served by function code 4 (input registers) and settings by function code 3/6/16 (holding registers); the same register number can therefore appear once in each table (for example 13050 is the inverter alarm when read and the EMS mode when written). Modbus TCP is available through the WiNet-S/WiNet-S2 dongle and, on models with a LAN port, directly on the inverter; the default TCP port is 502 and the default unit ID is 1. Older dongle firmware does not expose all registers (battery power and SOC in particular) - update the dongle firmware first. Registers marked "unavailable" by the device read back as 0xFFFF (U16), 0xFFFFFFFF (U32) or the maximum positive value for signed types, so filter those values. The SG series (string inverters without a battery) uses the same measurement registers but has no battery block, and limits export with registers 5007/5008 instead of the SH ratios at 13087-13090. Source: Sungrow "Communication Protocol of Residential Hybrid Inverter" V1.1.11 (SH series) and the shared running-information registers of the SG series. Battery compatibility: Sungrow's compatibility list (version 3.5, 22.07.2025) pairs the SH hybrid series with Sungrow's own SBR (SBR064-SBR256) and SBH (SBH100-SBH400) packs and, on the SH3.0/6.0RS, SH5.0/10RT and SH15-25T models, with BYD Battery-Box Premium HVS/HVM/HV and Pylontech Powercube/Force H1/H2 - https://ger.sungrowpower.com/upload/file/20250729/EN_FS_Compatibility_Factsheet.pdf.