SolaX Power · Solar inverter

X3-MIC / X3-PRO G2 (three-phase string) Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
10281
AC voltage R
UInt16V0.1R
10291
AC voltage S
UInt16V0.1R
10301
AC voltage T
UInt16V0.1R
10341
AC current R
UInt16A0.1R
10351
AC current S
UInt16A0.1R
10361
AC current T
UInt16A0.1R
10381
AC active power (Pac)
UInt16W1R
10592
Total yield
UInt32kWh0.1R
10832
Grid power
Positive means export to the grid, negative means import.
Int32W1R
10872
Total energy consumed from grid
UInt32kWh0.01R

Notes

Register map from the evcc template https://raw.githubusercontent.com/evcc-io/evcc/master/templates/definition/meter/solax-g2.yaml (SolaX X3-MIC G2, X3-PRO G2 and the rebadged Qcells Q.VOLT P5T-X/P17T-X). RS-485 device with 9600 8N1 factory settings and slave address 1; the PocketLAN/PocketWiFi dongle serves the same map as Modbus TCP on port 502. All entries are input registers. Grid power is signed: positive means export to the grid.