SMA · Battery inverter

Sunny Tripower Storage X 30/50 (STPS30-20, STPS50-20) and Sunny Island X 30/50 (SI30-20, SI50-20, US variants) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
2
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
302012
Current state of health (5-minute value)
Device or system status tag list; 307 = OK.
UInt32-1R
302332
Accumulated connected power of the PV inverter
UInt32W1R
308452
Current battery state of charge (User SOC)
SOC in relation to the present capacity, without decimal offset. The value is the User SOC: the actual SOC minus the upper and lower charging/discharging limits.
UInt32%1R
330172
Nominal active power WMaxOutRtg
Nominal active power of the grid feed-in, e.g. 50,000 W.
Int32W1R
330192
Nominal active power WMaxInRtg
Nominal active power of the intake, negative, e.g. -50,000 W.
Int32W1R
400182
Quick shut-down of the inverters
Writable tag list: 381 = standby, 1467 = start, 1749 = full stop (AC and DC sides).
UInt32-1RW
400292
General operating status
Tag list: 303 = off, 309 = operation, 569 = switched on (default), 1295 = standby, 1795 = blocked, 16777213 = information not available.
UInt32-1R
401872
Nominal battery capacity
Nominal capacity in watt hours, without decimal offset.
UInt32Wh1R
404722
Nominal grid voltage
e.g. 230 V or 400 V.
UInt32V1RW
411932
Behaviour during failure of external setpoint
Writable tag list: 2506 = keep values (default), 2507 = use fallback values.
UInt32-1RW
411952
Timeout for external setpoint
1 to 1,800 s, default 600 s.
UInt32s1RW
413152
Operating mode of the active power controller
Writable tag list, default 3352: 3352 = open-loop control, 3353 = closed-loop control.
UInt32-1RW
413692
Activation threshold, grid feed-in
Default 5 %.
Int32%0.001RW
413712
Deactivation threshold, grid feed-in
Default 5 %.
Int32%0.001RW
413732
Activation threshold, power consumption
Default 5 %.
Int32%0.001RW
413752
Deactivation threshold, power consumption
Default 5 %.
Int32%0.001RW
440012
Soft start rate P
Range 1 to 10,000, default 1,200 %/min.
UInt32%/min1RW
440132
Soft start P after a grid fault
Writable tag list: 308 = activate, 303 = deactivate.
UInt32-1RW
443812
Nominal active power WMaxOut
Nominal active power of the grid feed-in, e.g. 12,000 W.
Int32W1RW
443832
Nominal active power WMaxIn
Nominal active power of the intake, -60,000 W to 0 W.
Int32W1RW
445052
Limitation of active power
Two decimals, range 0-10,000 = 0-100 %, default 10,000 (100 %). Returns the limitation and is writable.
UInt32%0.01RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: SMA Solar Technology AG "SMA Modbus Interface - Remote Control - Sunny Tripower Storage X / Sunny Island X", technical information SMAModbus-STPS-X-SI-X-TI-en-10, version 1.0, vendor-hosted at https://files.sma.de/downloads/SMAModbus-STPS-X-SI-X-TI-en-10.pdf. Valid for STPS30-20 / STPS50-20 (Sunny Tripower Storage X 30/50), STPS27-US-20 / STPS60-US-20, and SI30-20 / SI50-20 / SI27-US208-20 / SI40-US480-20 / SI60-US480-20 (Sunny Island X 30/50 and US variants). The document defines unit ID 1 = communication product identity, 2 = system, 3 = device; all rows here are from the unit-2 table and the unit-2-and-3 table, so the seed uses unit_id 2, and the default TCP port 502 is stated in section 4. ADR values are decimal wire addresses (addressing zero_based). The document supports Modbus TCP only (no RTU, no UDP). The document states no word order for its 32-bit values; HighFirst follows the SMA profile (32-bit values high word first) and should be checked against a known reading on site. Deliberate omissions: the unit-1 identity rows (30005 serial number, 30051 device category); the unit-3-only table (battery operating status, SOC tag list and the device-level active-power setpoints), which needs a second entry at unit 3; and one row of the unit-2-and-3 table - the active-power limit ('sets the active power limit, e.g. 50,000 W for an STPS 50-20', range 0-60,000 W) - because its address cell is missing in the document and no other table gives the address, so it is not guessed. The battery must be controlled through unit ID 3, not through the system view. SMA product pages: https://www.sma.de/en/products/battery-inverters/sunny-island-x (Sunny Island X) and the SMA Modbus interface page linked here.