All devices

SMA · Solar plant controller

Data Manager M / Data Manager M Lite / Data Manager L (EDMM-10, EDMM-US-10, EDMM-10.A, EDML-10) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
2
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
301932
UTC system time
UInt32s1R
302012
Current state of health (5-minute value): device status
UInt32-1R
302332
Accumulated connected power of the PV inverter
UInt32W1R
307752
Current PV feed-in active power on all line conductors
Int32W1R
308052
Reactive power on all line conductors
Int32VAr1R
308452
Current battery state of charge
UInt32%1R
312352
Power limitation via digital input
UInt32%0.01R
312372
Setpoint of active power limitation P via analog input
UInt32%0.01R
312392
PV power limitation via communication
UInt32%0.01R
312412
PV power limitation via communication for direct marketing
UInt32%0.01R
312432
Maximum active power setpoint
UInt32%0.01R
312452
Internal PV power limitation
UInt32%0.01R
312492
Active power of system at PCC
Int32W1R
312512
Reactive power of system at PCC
Int32VAr1R
313932
Current battery charge
Sent as NaN when no battery inverter is installed in the system.
UInt32W1R
313952
Current battery discharge
Sent as NaN when no battery inverter is installed in the system.
UInt32W1R
315032
Feed-in of power into grid, line conductor L1 at PCC
Int32W1R
315052
Feed-in of power into grid, line conductor L2 at PCC
Int32W1R
315072
Feed-in of power into grid, line conductor L3 at PCC
Int32W1R
315092
Feed-in of reactive power into grid, line conductor L1 at PCC
Int32VAr1R
315112
Feed-in of reactive power into grid, line conductor L2 at PCC
Int32VAr1R
315132
Feed-in of reactive power into grid, line conductor L3 at PCC
Int32VAr1R
315152
System voltage, line conductor L1 - L2 at PCC
Sent as NaN when no power analyzer is connected.
UInt32V0.01R
315172
System voltage, line conductor L2 - L3 at PCC
Sent as NaN when no power analyzer is connected.
UInt32V0.01R
315192
System voltage, line conductor L3 - L1 at PCC
Sent as NaN when no power analyzer is connected.
UInt32V0.01R
315212
Mean value of grid voltage L-N at PCC
Sent as NaN when no power analyzer is connected.
UInt32V0.01R
315232
Mean value of grid voltage L-L at PCC
Sent as NaN when no power analyzer is connected.
UInt32V0.01R
315252
Displacement power factor at PCC
Sent as NaN when no power analyzer is connected.
Int32-0.01R
315272
Grid frequency at PCC
Sent as NaN when no power analyzer is connected.
UInt32Hz0.01R
315292
System voltage, line conductor L1 at PCC
UInt32V0.01R
315312
System voltage, line conductor L2 at PCC
UInt32V0.01R
315332
System voltage, line conductor L3 at PCC
UInt32V0.01R
315352
System current, line conductor L1 at PCC
Int32A0.001R
315372
System current, line conductor L2 at PCC
Int32A0.001R
315392
System current, line conductor L3 at PCC
Int32A0.001R
315452
Power value of the generating system when all generating units are in operation
UInt32W1R
315472
Available active power of all inverters
UInt32W1R
321852
Internal PV reactive power limitation
Sent as NaN when no internal PV reactive power limitation is set.
Int32%0.01R
321872
Available underexcited reactive power
Int32VAr1R
321892
Available overexcited reactive power
Int32VAr1R
321912
Theoretically available power output
Values marked * require the module-temperature, ambient-temperature and irradiation sensors to be configured and activated in the Data Manager.
UInt32W0.01R
321932
Availability of generating system
Compliant with Pbinst/Pinst per VDE AR-N 4110 (Table C2).
UInt32%1R
321952
External active power limitation
Sent as NaN when the function is disabled.
UInt32%0.01R
321972
Available underexcited reactive power
Int32%0.01R
321992
Available overexcited reactive power
Int32%0.01R
346092
Ambient temperature
Sensor input; requires a sensor configured and activated in the Data Manager.
Int32°C0.1R
346152
Global wind speed (m/s)
UInt32m/s0.01R
346212
PV module temperature
Sensor input; requires a sensor configured and activated in the Data Manager.
Int32°C0.1R
346232
Total irradiation on the external irradiation sensor/pyranometer
Sensor input; requires a sensor configured and activated in the Data Manager.
UInt32W/m²1R
346252
Ambient temperature (°F)
Int32°F0.1R
346272
Ambient temperature (K)
Int32K0.1R
346292
PV module temperature (°F)
Int32°F0.1R
346312
PV module temperature (K)
Int32K0.1R
346332
Global wind speed (km/h)
UInt32km/h0.1R
346352
Global wind speed (mph)
UInt32mph0.1R
346532
Digital input group 1 (status code)
Bit-coded status of the four digital inputs: 311 = open; 2055 = DI1; 2056 = DI1 DI2; 2057 = DI1 DI2 DI3; 2058 = DI1 DI2 DI3 DI4; 2059 = DI1 DI2 DI4; 2060 = DI1 DI3; 2061 = DI1 DI3 DI4; 2062 = DI1 DI4; 2063 = DI2; 2064 = DI2 DI3; 2065 = DI2 DI3 DI4; 2066 = DI2 DI4; 2067 = DI3; 2068 = DI3 DI4; 2069 = DI4.
UInt32-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: SMA Solar Technology AG "SMA Modbus Interface - SMA Data Manager", technical information EDMx-Modbus-TI-en-16, version 1.6, status 2022-03-09, vendor-hosted at https://files.sma.de/downloads/EDMx-Modbus-TI-en-16.pdf. Valid for EDML-10 (Data Manager L), EDMM-10 / EDMM-US-10 (Data Manager M) and EDMM-10.A (Data Manager M Lite). The document describes three unit IDs: 1 = the communication product's identity, 2 = the system (plant) and 3-247 = the managed devices; this seed stores the unit-2 system table and sets unit_id 2, port 502 (section 3.5). ADR values are the decimal wire addresses, so addressing is zero_based. The document lists function codes 0x03 and 0x04 without assigning one to the tables; as in the library's other SMA seeds, the 30xxx measured values are stored as input registers and the 40xxx parameters as holding registers. Word order HighFirst follows the SMA profile (32-bit values high word first). Deliberate omissions: every U64 row (30513 total grid feed-in, 30517 daily grid feed-in, 31397/31401 battery charge/discharge) because the app has no 64-bit integer; the unit-1 identity block (30001-30193) and unit 1's own UTC row; the unit 3-247 device parameters, which belong to the inverter entries; and the EDMM-10.A note that all listed points may answer NaN on the M Lite. Sensor values (34609-34635) require the sensors to be configured and activated in the Data Manager; the PCC voltage, current and power-factor rows require a power analyzer. 30193 UTC system time appears in both the unit-1 and unit-2 tables and is kept once.