PF4 / PF5 differential pressure, humidity and temperature transmitter Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
None
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
310002
Humidity
Current humidity value, 32-bit IEEE-754 float in two registers (part 1 at 31000, part 2 at 31001). The worked frame in section 2.4.5.1 reads registers 31'001-31'006 and returns 0x41F370A3 = 30.43 %RH here. Only present when an HC2 probe is connected.
Float32%RH1R
310022
Temperature
Current temperature value (two registers, high word first). The worked frame returns 0x41BA0000 = 23.25. The unit follows the unit selection in holding register 41'001 (address 41'000): 0 = °C, 1 = °F.
Float32-1R
310042
Differential pressure
Current differential pressure value (two registers). The worked frame returns 0x3D80E9A2 = 0.0629. The unit follows the differential-pressure unit register 41'002 (address 41'001): 0 = Pa, 1 = inH2O, 2 = mpsi, 3 = mbar, 4 = mmHg, 5 = mmH2O, 6 = Torr, 7 = g/cm2.
Float32-1R
310062
Calculation value
Current value of the selected calculation (two registers). The calculation is chosen in holding register 40'001 (address 40'000): 0 = dew point, 1 = frost point, 2 = wet bulb temperature, 3 = enthalpy, 4 = vapour concentration, 5 = specific humidity, 6 = mixing ratio, 7 = saturation vapour concentration, 8 = vapour partial pressure, 9 = vapour saturation pressure.
Float32-1R
310082
Analog input value
Current analog input value (two registers). The input type is set in holding register 40'002 (address 40'001): 0 = voltage 0...10 V, 1 = current 0...24 mA.
Float32-1R
310102
Flow
Current flow value (two registers). Only present when the flow option is activated; the unit follows the flow-unit selection (0 = m/s, 1 = km/h, 2 = ft/s, 3 = mph).
Float32-1R
310122
Volume flow
Current volume flow value (two registers). Only present when the flow option is activated; the unit follows the volume-flow selection (m3/h, m3/min, l/min, l/s, cfm, cfs).
Float32-1R
310142
Ambient pressure
Current ambient pressure value (two registers). The unit follows the ambient-pressure unit register 41'003 (address 41'002): 0 = hPa, 1 = inHg, 2 = psi.
Float32-1R
310162
Internal temperature
Current internal temperature of the transmitter (two registers).
Float32-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Rotronic 'Modbus Manual for PF4/5 - Differential Pressure Transmitter', document E-M-PF4_PF5-Modbus_V1.2 ((c) 2021), vendor-hosted PDF at https://www.rotronic.com/pub/media/productattachments/files/E-M-PF4_PF5-V1.2_Modbus_Manual.pdf (SHA-256 70d19545b7b6fddad0e1bc40826c91e234bcb30e89f17fba030cda199aa02fad), sections 1.1.1.1 (Modbus RTU), 2.4.2 'Current Values: Float Values', 2.4.4 'Explanation of Flags', 2.4.5.1 (worked read of 31'001-31'006), 2.5.1 'Value Type' and 2.5.2 'Value Unit'. Factory frame from section 1.1.1.1: Modbus RTU over RS-485, 19200 baud, 8 data bits, no parity, 1 stop bit, and the parameters 'cannot be changed'. The Modbus address is always the RS485 network address + 1 (section 1.1.1.1 and the Device Specific Settings chapter); the RS485 device number is selectable 0...63 and no factory value is printed, so this seed stores unit 1 (RS485 address 0) as a stated placeholder - set it to the unit's own address before polling a shared bus. Addressing: the register tables print the register number and the protocol (wire) address side by side, the worked frame reads 0x7918 = 31000 for register 31'001, and the manual states that Modbus registers are addressed starting at zero, so the seed is zero_based. Word order: the worked read returns humidity 0x41F3 0x70A3 and temperature 0x41BA 0x0000, high word first (BigEndian + HighFirst); 44'114 can change the operation mode from its 'word swap' default, so verify it on site. Only the measurement block is seeded: the device-data block (30'001-31'000) and the holding-register chapters print register numbers, protocol addresses and names as separate text streams, so rows cannot be paired reliably, and the 16-bit block (32'001-32'009) is the same values multiplied by scaling factors that live in those unpairable holding registers. Units are not fixed: every measurement except humidity follows the unit selection registers listed in each row's description, so no engineering unit is claimed for them here.