EKO Instruments · Sensor
MS-80S pyranometer (Modbus RTU variant of the MS-80 series) Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 19200
- Parity
- Even
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 0 | 1 | Model number U16 model number; the MS-80S reports 0x0110. | UInt16 | - | 1 | R |
| 1 | 1 | Fixed value 0 The document prints a fixed value of 0 in this register. | UInt16 | - | 1 | R |
| 2 | 2 | Solar irradiance, temperature- and linearity-compensated Comp.Irr: irradiance after temperature and linearity compensation (F32, two registers, high word first). Updated about every 110 ms. | Float32 | W/m² | 1 | R |
| 8 | 2 | Sensor temperature (Pt100) Pt100 sensor temperature of the pyranometer body (F32). | Float32 | °C | 1 | R |
| 14 | 2 | X-axis tilt angle X-axis component of the tilt angle (F32). Updated about every 110 ms. | Float32 | ° | 1 | R |
| 16 | 2 | Y-axis tilt angle Y-axis component of the tilt angle (F32). | Float32 | ° | 1 | R |
| 18 | 2 | Solar irradiance before correction Raw.Irr: irradiance before the temperature/linearity correction (F32). | Float32 | W/m² | 1 | R |
| 20 | 2 | Sensor output voltage ADmV: the raw sensor output voltage in mV (F32). | Float32 | mV | 1 | R |
| 22 | 2 | Internal temperature Temperature measured by the internal temperature sensor (F32). | Float32 | °C | 1 | R |
| 24 | 2 | Internal humidity Relative humidity measured by the internal humidity sensor (F32). | Float32 | %RH | 1 | R |
| 26 | 2 | Alerts for internal humidity of the pyranometer U32 alert word: normal = 0, an abnormality in the internal humidity is reported as 1. | UInt32 | - | 1 | R |
| 96 | 1 | Company name (characters 0,1) One 16-bit register holding the first two characters of the four-character company name, 'EK'. | Ascii | - | 1 | R |
| 97 | 1 | Company name (characters 2,3) One 16-bit register holding characters 3 and 4 of the company name, 'O' followed by the 0x20 padding character. | Ascii | - | 1 | R |
| 98 | 1 | Firmware version U16 firmware version number. | UInt16 | - | 1 | R |
| 99 | 1 | Hardware version U16 hardware version number. | UInt16 | - | 1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: EKO INSTRUMENTS 'INSTRUCTION MANUAL - Pyranometer MS-80/80S/80U', Ver. 8 (file dated 2023-10-13), chapter 4 'About RS485 Modbus RTU connection [MS-80S]', Table 5-10, Appendix A-4 'Communication Specifications (Modbus RTU)' (Tables A4-1 to A4-3), A-6 to A-10 (register maps and details) and A-9 'MS-80S Setting Report'; vendor-hosted PDF at https://eko-instruments.com/wp-content/uploads/2024/08/ms-80_80s_80u_manual20231013v8.pdf (SHA-256 159e0df960d3165ab463a224812569b267679470cbc43b0cef5b4844e20f1035). Factory serial settings: Modbus RTU is the default interface and the default communication setting is 19200 bps with even parity (Table A4-3 setting 10, marked default; Table 5-10 prints 'Baud rate 19200, Parity Even'); the stop bit follows parity (one with parity, two without) and the word is always 8 data bits, so the frame is 19200 8E1. Unit ID: Table 5-10 gives the factory address as the last two digits of the serial number (100 when they are '00'), while the example report in A-9 prints address 1; the seed stores 1 as a verify-on-site placeholder: set the unit ID from address register 101. Addressing: A-6 states that the register map starts from address 0 and A4-3 confirms addresses start from 0, so the seed is zero_based. Word order: Table A4-8 shows a 32-bit value as 0x1234 (MSW) at address n and 0x5678 (LSW) at n+1, so BigEndian + HighFirst. The device does not distinguish holding from input register addresses (A4-2): measurements are listed as input registers and settings as holding registers, but either function code reaches both. Not seeded: the coils (only 'Reboot' at coil 1 and 'Save' at coil 3 are documented, both write-only, which this schema's coil area cannot express), the analog-output scaling rows from register 131 on (Table A4-15's decimal column drifts against its description column there), the calibration history block (200-219) and the M/SMP/SRD register types that register 103 can select.