All devices

EKO Instruments · Sensor

MS-80S pyranometer (Modbus RTU variant of the MS-80 series) Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Model number
U16 model number; the MS-80S reports 0x0110.
UInt16-1R
11
Fixed value 0
The document prints a fixed value of 0 in this register.
UInt16-1R
22
Solar irradiance, temperature- and linearity-compensated
Comp.Irr: irradiance after temperature and linearity compensation (F32, two registers, high word first). Updated about every 110 ms.
Float32W/m²1R
82
Sensor temperature (Pt100)
Pt100 sensor temperature of the pyranometer body (F32).
Float32°C1R
142
X-axis tilt angle
X-axis component of the tilt angle (F32). Updated about every 110 ms.
Float32°1R
162
Y-axis tilt angle
Y-axis component of the tilt angle (F32).
Float32°1R
182
Solar irradiance before correction
Raw.Irr: irradiance before the temperature/linearity correction (F32).
Float32W/m²1R
202
Sensor output voltage
ADmV: the raw sensor output voltage in mV (F32).
Float32mV1R
222
Internal temperature
Temperature measured by the internal temperature sensor (F32).
Float32°C1R
242
Internal humidity
Relative humidity measured by the internal humidity sensor (F32).
Float32%RH1R
262
Alerts for internal humidity of the pyranometer
U32 alert word: normal = 0, an abnormality in the internal humidity is reported as 1.
UInt32-1R
961
Company name (characters 0,1)
One 16-bit register holding the first two characters of the four-character company name, 'EK'.
Ascii-1R
971
Company name (characters 2,3)
One 16-bit register holding characters 3 and 4 of the company name, 'O' followed by the 0x20 padding character.
Ascii-1R
981
Firmware version
U16 firmware version number.
UInt16-1R
991
Hardware version
U16 hardware version number.
UInt16-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: EKO INSTRUMENTS 'INSTRUCTION MANUAL - Pyranometer MS-80/80S/80U', Ver. 8 (file dated 2023-10-13), chapter 4 'About RS485 Modbus RTU connection [MS-80S]', Table 5-10, Appendix A-4 'Communication Specifications (Modbus RTU)' (Tables A4-1 to A4-3), A-6 to A-10 (register maps and details) and A-9 'MS-80S Setting Report'; vendor-hosted PDF at https://eko-instruments.com/wp-content/uploads/2024/08/ms-80_80s_80u_manual20231013v8.pdf (SHA-256 159e0df960d3165ab463a224812569b267679470cbc43b0cef5b4844e20f1035). Factory serial settings: Modbus RTU is the default interface and the default communication setting is 19200 bps with even parity (Table A4-3 setting 10, marked default; Table 5-10 prints 'Baud rate 19200, Parity Even'); the stop bit follows parity (one with parity, two without) and the word is always 8 data bits, so the frame is 19200 8E1. Unit ID: Table 5-10 gives the factory address as the last two digits of the serial number (100 when they are '00'), while the example report in A-9 prints address 1; the seed stores 1 as a verify-on-site placeholder: set the unit ID from address register 101. Addressing: A-6 states that the register map starts from address 0 and A4-3 confirms addresses start from 0, so the seed is zero_based. Word order: Table A4-8 shows a 32-bit value as 0x1234 (MSW) at address n and 0x5678 (LSW) at n+1, so BigEndian + HighFirst. The device does not distinguish holding from input register addresses (A4-2): measurements are listed as input registers and settings as holding registers, but either function code reaches both. Not seeded: the coils (only 'Reboot' at coil 1 and 'Save' at coil 3 are documented, both write-only, which this schema's coil area cannot express), the analog-output scaling rows from register 131 on (Table A4-15's decimal column drifts against its description column there), the calibration history block (200-219) and the M/SMP/SRD register types that register 103 can select.