Precision Digital · Panel meter
ProVu / ProtEX-MAX / Helios meters and controllers (PD6000 family, firmware 4.000 and later) Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 247
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 9600
- Parity
- Even
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 0 | 2 | PV/Rate display value Registers 40001-40002. Includes the decimal point; under range = -99999, over range = 999999, input open = -99999. | Float32 | - | 1 | R |
| 2 | 1 | Alarm and relay status Register 40003. Bits 0-7 = relay 1-8 energized, bits 8-15 = alarm 1-8 active. | UInt16 | - | 1 | R |
| 3 | 1 | Digital inputs and outputs status Register 40004. Bits 0-7 = digital output 1-8 active, bits 8-15 = digital input 1-8 selected. | UInt16 | - | 1 | R |
| 4 | 2 | Maximum display value Registers 40005-40006, since power-up or the last max reset. | Float32 | - | 1 | R |
| 6 | 2 | Minimum display value Registers 40007-40008, since power-up or the last min reset. | Float32 | - | 1 | R |
| 8 | 2 | Total value Registers 40009-40010, since the last total reset; decimal point from 40103. | Float32 | - | 1 | R |
| 10 | 2 | Grand total value Registers 40011-40012, since the last grand-total reset; decimal point from 40104. | Float32 | - | 1 | R |
| 12 | 2 | Total overflow value Registers 40013-40014. | Float32 | - | 1 | R |
| 14 | 2 | Total non-overflow value Registers 40015-40016. | Float32 | - | 1 | R |
| 16 | 2 | Grand total overflow value Registers 40017-40018. | Float32 | - | 1 | R |
| 18 | 2 | Grand total non-overflow value Registers 40019-40020. | Float32 | - | 1 | R |
| 20 | 2 | PV/Rate display value excluding the decimal point Registers 40021-40022, 'Long Hi'/'Long Lo' register pair; read both together with register 40021 first. Scale by the decimal point in 40102. | Int32 | - | 1 | R |
| 22 | 1 | Alarm and relay status (mirror) Register 40023, mirror of 40003. | UInt16 | - | 1 | R |
| 23 | 1 | Digital inputs and outputs status (mirror) Register 40024, mirror of 40004. | UInt16 | - | 1 | R |
| 24 | 2 | Maximum display value excluding the decimal point Registers 40025-40026. | Int32 | - | 1 | R |
| 26 | 2 | Minimum display value excluding the decimal point Registers 40027-40028. | Int32 | - | 1 | R |
| 28 | 2 | Total value excluding the decimal point Registers 40029-40030; decimal point from 40103. | Int32 | - | 1 | R |
| 30 | 2 | Grand total value excluding the decimal point Registers 40031-40032; decimal point from 40104. | Int32 | - | 1 | R |
| 38 | 1 | Start batch Register 40039. Set bit 0 to start the batch process. | UInt16 | - | 1 | W |
| 39 | 1 | Stop batch Register 40040. Write 1 to pause, 1 again to stop; reading returns the batch state: 1 = start, 2 = pause, 4 = stop, 8 = delay. | UInt16 | - | 1 | RW |
| 40 | 1 | Alarm acknowledge Register 40041. One bit per relay; set a bit to acknowledge that relay's alarm. Bits 0-7 mirror bits 8-15. | UInt16 | - | 1 | W |
| 41 | 1 | Reset maximum display value Register 40042. Set bit 0 to reset. | UInt16 | - | 1 | W |
| 42 | 1 | Reset minimum display value Register 40043. Set bit 0 to reset. | UInt16 | - | 1 | W |
| 43 | 1 | Reset max/min display value Register 40044. Set bit 0 to reset both. | UInt16 | - | 1 | W |
| 44 | 1 | Reset total value Register 40045. Set bit 0 to reset. | UInt16 | - | 1 | W |
| 45 | 1 | Reset grand total value Register 40046. Set bit 0 to reset. | UInt16 | - | 1 | W |
| 46 | 1 | Reset batch count value Register 40047. Set bit 0 to reset; the count itself is read at 40152. | UInt16 | - | 1 | W |
| 50 | 1 | Control mode Register 40051. 0 = auto, 1 = manual. Registers 40052-40069 only take effect in manual mode. | UInt16 | - | 1 | RW |
| 51 | 1 | Manual control analog output setting Register 40052. Limits 0 to 23999; the document's unit cell reads 'A', as it does for the analog-output block at 40401 (1 to 23000), which only fits a 4-20 mA output if the value counts thousandths of a milliamp - verify the unit on site. Only effective when 40051 is 1 (manual). | UInt16 | - | 1 | RW |
| 53 | 1 | Manual control relay 1 setting Register 40054(53). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 54 | 1 | Manual control relay 2 setting Register 40055(54). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 55 | 1 | Manual control relay 3 setting Register 40056(55). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 56 | 1 | Manual control relay 4 setting Register 40057(56). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 57 | 1 | Manual control relay 5 setting Register 40058(57). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 58 | 1 | Manual control relay 6 setting Register 40059(58). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 59 | 1 | Manual control relay 7 setting Register 40060(59). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 60 | 1 | Manual control relay 8 setting Register 40061(60). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 61 | 1 | Manual control digital output 1 setting Register 40062(61). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 62 | 1 | Manual control digital output 2 setting Register 40063(62). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 63 | 1 | Manual control digital output 3 setting Register 40064(63). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 64 | 1 | Manual control digital output 4 setting Register 40065(64). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 65 | 1 | Manual control digital output 5 setting Register 40066(65). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 66 | 1 | Manual control digital output 6 setting Register 40067(66). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 67 | 1 | Manual control digital output 7 setting Register 40068(67). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 68 | 1 | Manual control digital output 8 setting Register 40069(68). 0 = off, 1 = on. | UInt16 | - | 1 | RW |
| 100 | 1 | Input selection Register 40101. Input type code, see Table 1 of the document. | UInt16 | - | 1 | RW |
| 101 | 1 | PV/Rate decimal point Register 40102. 0-5 select decimal places (0 = none ... 5 = d.ddddd); 0 = dddd, 1 = dddd.d, 6 = dddd°u and 7 = dddd.du for temperature units. | UInt16 | - | 1 | RW |
| 102 | 1 | Total decimal point Register 40103. 0 to 5 decimal places. | UInt16 | - | 1 | RW |
| 103 | 1 | Grand total decimal point Register 40104. 0 to 5 decimal places. | UInt16 | - | 1 | RW |
| 125 | 1 | Adjust value Register 40126. -500 to 500 = -50.0 to +50.0, applied to temperature inputs only. | Int16 | °C/°F | 0.1 | RW |
| 129 | 1 | Filter setting Register 40130. 0 = no filtering, 2-199 = old + ((new - old)/filter); for pulse input 900 = high speed and 202-250 = low speed (2 to 50 in that mode). | UInt16 | - | 1 | RW |
| 130 | 1 | Bypass setting Register 40131. 2 to 999 = 0.2 to 99.9 % of full scale; no effect when the filter is 0. | UInt16 | % | 0.1 | RW |
| 131 | 1 | Serial address Register 40132. 1 to 247; factory default 247. Takes effect after the next meter reset. | UInt16 | - | 1 | RW |
| 132 | 1 | Serial baud rate Register 40133. 0 = 300, 1 = 600, 2 = 1200, 3 = 2400, 4 = 4800, 5 = 9600, 6 = 19200; factory default 9600 (code 5). Takes effect after the next meter reset. | UInt16 | - | 1 | RW |
| 133 | 1 | Serial transmit delay Register 40134. 0 to 199 ms; factory default 50 ms. | UInt16 | ms | 1 | RW |
| 134 | 1 | Serial parity Register 40135. 0 = none with 1 stop bit, 1 = none with 2 stop bits, 2 = odd, 3 = even; factory default Even with 1 stop bit. | UInt16 | - | 1 | RW |
| 135 | 1 | Serial byte-to-byte timeout Register 40136. 0 to 254 in 1/100 s; the minimum depends on the baud rate (0.01 s for 2400-19200 bps). Factory default 0.10 s. | UInt16 | s | 0.01 | RW |
| 136 | 1 | Function mode Register 40137. 0 = linear, 1 = square root, 2 = exponent, 3 = round horizontal tank. | UInt16 | - | 1 | RW |
| 300 | 1 | Relay 1 mode Register 40301. Operating mode bits, see Table 4 of the document. | UInt16 | - | 1 | RW |
| 301 | 2 | Relay 1 set point Registers 40302-40303. | Float32 | - | 1 | RW |
| 303 | 2 | Relay 1 reset point Registers 40304-40305. | Float32 | - | 1 | RW |
| 305 | 1 | Relay 1 on delay Register 40306. 0 to 1999 in 0.1 s steps. | UInt16 | s | 0.1 | RW |
| 306 | 1 | Relay 1 off delay Register 40307. 0 to 1999 in 0.1 s steps. | UInt16 | s | 0.1 | RW |
| 307 | 2 | Relay 1 sample time Registers 40308-40309. 0 to 59999 in 0.1 s steps. | Float32 | s | 1 | RW |
| 309 | 1 | Relay 2 mode Register 40310. Operating mode bits, see Table 4. | UInt16 | - | 1 | RW |
| 310 | 2 | Relay 2 set point Registers 40311-40312. | Float32 | - | 1 | RW |
| 312 | 2 | Relay 2 reset point Registers 40313-40314. | Float32 | - | 1 | RW |
| 314 | 1 | Relay 2 on delay Register 40315. 0 to 1999 in 0.1 s steps. | UInt16 | s | 0.1 | RW |
| 315 | 1 | Relay 2 off delay Register 40316. 0 to 1999 in 0.1 s steps. | UInt16 | s | 0.1 | RW |
| 316 | 2 | Relay 2 sample time Registers 40317-40318. 0 to 59999 in 0.1 s steps. | Float32 | s | 1 | RW |
| 9900 | 4 | Product identifier Registers 49901-49904. Eight ASCII characters: product/software release, main-board input and input card. | Ascii | - | 1 | R |
| 9904 | 4 | Firmware version (ASCII) Registers 49905-49908. Eight ASCII characters. | Ascii | - | 1 | R |
| 9916 | 1 | Product number Register 49917. Product code, see Table 7 of the document. | UInt16 | - | 1 | R |
| 9917 | 1 | Firmware version Register 49918. Divide by 1000: 2200 = v2.200. | UInt16 | - | 0.001 | R |
| 9997 | 1 | Initialize meter serial communication Register 49998. Write 0xFF00 to apply new serial port parameters. | UInt16 | - | 1 | W |
| 9998 | 1 | Load factory defaults Register 49999. Write 0xFF00 to load the meter's factory defaults. | UInt16 | - | 1 | W |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Sources: Precision Digital 'Modbus Register Tables for PROVU, ProtEX-MAX, and Helios Meters & Controllers' (https://predig.com/files/LIMModbus2.pdf, SHA-256 e6f176942122d9ab21e3718e6ea707870e29eadd5d2524ddcf6a4546e0be5eb8) for the map, and the PD6000 ProVu Instruction Manual LIM6000 (https://predig.com/files/LIM6000.pdf, SHA-256 ed993d60df31bc9ab748ff14323c41951e9c9e1438c773c50d26da3ad46d1f31), 'Factory Defaults & User Settings', for the frame: Slave ID 247, baud rate 9600, parity Even, transmit delay 50 ms. The specification table gives 8 data bits and '1 or 2 stop bits' but not which the factory setting uses, and register 40135 names stop bits only for its two no-parity codes (0 = none/1 stop bit, 1 = none/2 stop bits; 2 = odd, 3 = even), so 1 stop bit with the factory Even parity is this seed's reading of that four-choice menu, not a printed value - verify on site. Register numbers are the printed 4xxxx numbers; Note 1 of the document says the message address is the register number minus one (40100 is sent as 0x0063 = 99), and the table's Address (Hex) column prints that wire address, which this seed stores with zero_based. One document covers the ProVu family and its ProtEX-MAX (PD8-) and Helios (PD2-) siblings, so model rows exist; the seeded rows are shared by every model, plus relay 1/2 and manual override. Every 4x register is mirrored into 3x space and readable with function 04, so the map is seeded once, in the holding area. Data format is IEEE-754 float, highest byte first (byte order 1234), so BigEndian + HighFirst; register pairs print 'Long Hi'/'Long Lo'. Omitted: overflow mirrors 40033-40038, tare 40048-40050, the Modbus-display block 40070-40089, total/display settings 40105-40125, RTD count and low gate 40127-40128, point/exponent/tank/cutoff/batch rows 40138-40160, passwords 40171-40180, dual-scale and function-key rows 40181-40220, relays 3-8 (40319-40372), the 4-20 mA output 40401-40413, remote scaling and PV channel B (41001-46405).