ProVu / ProtEX-MAX / Helios meters and controllers (PD6000 family, firmware 4.000 and later) Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
247
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
Even
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
02
PV/Rate display value
Registers 40001-40002. Includes the decimal point; under range = -99999, over range = 999999, input open = -99999.
Float32-1R
21
Alarm and relay status
Register 40003. Bits 0-7 = relay 1-8 energized, bits 8-15 = alarm 1-8 active.
UInt16-1R
31
Digital inputs and outputs status
Register 40004. Bits 0-7 = digital output 1-8 active, bits 8-15 = digital input 1-8 selected.
UInt16-1R
42
Maximum display value
Registers 40005-40006, since power-up or the last max reset.
Float32-1R
62
Minimum display value
Registers 40007-40008, since power-up or the last min reset.
Float32-1R
82
Total value
Registers 40009-40010, since the last total reset; decimal point from 40103.
Float32-1R
102
Grand total value
Registers 40011-40012, since the last grand-total reset; decimal point from 40104.
Float32-1R
122
Total overflow value
Registers 40013-40014.
Float32-1R
142
Total non-overflow value
Registers 40015-40016.
Float32-1R
162
Grand total overflow value
Registers 40017-40018.
Float32-1R
182
Grand total non-overflow value
Registers 40019-40020.
Float32-1R
202
PV/Rate display value excluding the decimal point
Registers 40021-40022, 'Long Hi'/'Long Lo' register pair; read both together with register 40021 first. Scale by the decimal point in 40102.
Int32-1R
221
Alarm and relay status (mirror)
Register 40023, mirror of 40003.
UInt16-1R
231
Digital inputs and outputs status (mirror)
Register 40024, mirror of 40004.
UInt16-1R
242
Maximum display value excluding the decimal point
Registers 40025-40026.
Int32-1R
262
Minimum display value excluding the decimal point
Registers 40027-40028.
Int32-1R
282
Total value excluding the decimal point
Registers 40029-40030; decimal point from 40103.
Int32-1R
302
Grand total value excluding the decimal point
Registers 40031-40032; decimal point from 40104.
Int32-1R
381
Start batch
Register 40039. Set bit 0 to start the batch process.
UInt16-1W
391
Stop batch
Register 40040. Write 1 to pause, 1 again to stop; reading returns the batch state: 1 = start, 2 = pause, 4 = stop, 8 = delay.
UInt16-1RW
401
Alarm acknowledge
Register 40041. One bit per relay; set a bit to acknowledge that relay's alarm. Bits 0-7 mirror bits 8-15.
UInt16-1W
411
Reset maximum display value
Register 40042. Set bit 0 to reset.
UInt16-1W
421
Reset minimum display value
Register 40043. Set bit 0 to reset.
UInt16-1W
431
Reset max/min display value
Register 40044. Set bit 0 to reset both.
UInt16-1W
441
Reset total value
Register 40045. Set bit 0 to reset.
UInt16-1W
451
Reset grand total value
Register 40046. Set bit 0 to reset.
UInt16-1W
461
Reset batch count value
Register 40047. Set bit 0 to reset; the count itself is read at 40152.
UInt16-1W
501
Control mode
Register 40051. 0 = auto, 1 = manual. Registers 40052-40069 only take effect in manual mode.
UInt16-1RW
511
Manual control analog output setting
Register 40052. Limits 0 to 23999; the document's unit cell reads 'A', as it does for the analog-output block at 40401 (1 to 23000), which only fits a 4-20 mA output if the value counts thousandths of a milliamp - verify the unit on site. Only effective when 40051 is 1 (manual).
UInt16-1RW
531
Manual control relay 1 setting
Register 40054(53). 0 = off, 1 = on.
UInt16-1RW
541
Manual control relay 2 setting
Register 40055(54). 0 = off, 1 = on.
UInt16-1RW
551
Manual control relay 3 setting
Register 40056(55). 0 = off, 1 = on.
UInt16-1RW
561
Manual control relay 4 setting
Register 40057(56). 0 = off, 1 = on.
UInt16-1RW
571
Manual control relay 5 setting
Register 40058(57). 0 = off, 1 = on.
UInt16-1RW
581
Manual control relay 6 setting
Register 40059(58). 0 = off, 1 = on.
UInt16-1RW
591
Manual control relay 7 setting
Register 40060(59). 0 = off, 1 = on.
UInt16-1RW
601
Manual control relay 8 setting
Register 40061(60). 0 = off, 1 = on.
UInt16-1RW
611
Manual control digital output 1 setting
Register 40062(61). 0 = off, 1 = on.
UInt16-1RW
621
Manual control digital output 2 setting
Register 40063(62). 0 = off, 1 = on.
UInt16-1RW
631
Manual control digital output 3 setting
Register 40064(63). 0 = off, 1 = on.
UInt16-1RW
641
Manual control digital output 4 setting
Register 40065(64). 0 = off, 1 = on.
UInt16-1RW
651
Manual control digital output 5 setting
Register 40066(65). 0 = off, 1 = on.
UInt16-1RW
661
Manual control digital output 6 setting
Register 40067(66). 0 = off, 1 = on.
UInt16-1RW
671
Manual control digital output 7 setting
Register 40068(67). 0 = off, 1 = on.
UInt16-1RW
681
Manual control digital output 8 setting
Register 40069(68). 0 = off, 1 = on.
UInt16-1RW
1001
Input selection
Register 40101. Input type code, see Table 1 of the document.
UInt16-1RW
1011
PV/Rate decimal point
Register 40102. 0-5 select decimal places (0 = none ... 5 = d.ddddd); 0 = dddd, 1 = dddd.d, 6 = dddd°u and 7 = dddd.du for temperature units.
UInt16-1RW
1021
Total decimal point
Register 40103. 0 to 5 decimal places.
UInt16-1RW
1031
Grand total decimal point
Register 40104. 0 to 5 decimal places.
UInt16-1RW
1251
Adjust value
Register 40126. -500 to 500 = -50.0 to +50.0, applied to temperature inputs only.
Int16°C/°F0.1RW
1291
Filter setting
Register 40130. 0 = no filtering, 2-199 = old + ((new - old)/filter); for pulse input 900 = high speed and 202-250 = low speed (2 to 50 in that mode).
UInt16-1RW
1301
Bypass setting
Register 40131. 2 to 999 = 0.2 to 99.9 % of full scale; no effect when the filter is 0.
UInt16%0.1RW
1311
Serial address
Register 40132. 1 to 247; factory default 247. Takes effect after the next meter reset.
UInt16-1RW
1321
Serial baud rate
Register 40133. 0 = 300, 1 = 600, 2 = 1200, 3 = 2400, 4 = 4800, 5 = 9600, 6 = 19200; factory default 9600 (code 5). Takes effect after the next meter reset.
UInt16-1RW
1331
Serial transmit delay
Register 40134. 0 to 199 ms; factory default 50 ms.
UInt16ms1RW
1341
Serial parity
Register 40135. 0 = none with 1 stop bit, 1 = none with 2 stop bits, 2 = odd, 3 = even; factory default Even with 1 stop bit.
UInt16-1RW
1351
Serial byte-to-byte timeout
Register 40136. 0 to 254 in 1/100 s; the minimum depends on the baud rate (0.01 s for 2400-19200 bps). Factory default 0.10 s.
UInt16s0.01RW
1361
Function mode
Register 40137. 0 = linear, 1 = square root, 2 = exponent, 3 = round horizontal tank.
UInt16-1RW
3001
Relay 1 mode
Register 40301. Operating mode bits, see Table 4 of the document.
UInt16-1RW
3012
Relay 1 set point
Registers 40302-40303.
Float32-1RW
3032
Relay 1 reset point
Registers 40304-40305.
Float32-1RW
3051
Relay 1 on delay
Register 40306. 0 to 1999 in 0.1 s steps.
UInt16s0.1RW
3061
Relay 1 off delay
Register 40307. 0 to 1999 in 0.1 s steps.
UInt16s0.1RW
3072
Relay 1 sample time
Registers 40308-40309. 0 to 59999 in 0.1 s steps.
Float32s1RW
3091
Relay 2 mode
Register 40310. Operating mode bits, see Table 4.
UInt16-1RW
3102
Relay 2 set point
Registers 40311-40312.
Float32-1RW
3122
Relay 2 reset point
Registers 40313-40314.
Float32-1RW
3141
Relay 2 on delay
Register 40315. 0 to 1999 in 0.1 s steps.
UInt16s0.1RW
3151
Relay 2 off delay
Register 40316. 0 to 1999 in 0.1 s steps.
UInt16s0.1RW
3162
Relay 2 sample time
Registers 40317-40318. 0 to 59999 in 0.1 s steps.
Float32s1RW
99004
Product identifier
Registers 49901-49904. Eight ASCII characters: product/software release, main-board input and input card.
Ascii-1R
99044
Firmware version (ASCII)
Registers 49905-49908. Eight ASCII characters.
Ascii-1R
99161
Product number
Register 49917. Product code, see Table 7 of the document.
UInt16-1R
99171
Firmware version
Register 49918. Divide by 1000: 2200 = v2.200.
UInt16-0.001R
99971
Initialize meter serial communication
Register 49998. Write 0xFF00 to apply new serial port parameters.
UInt16-1W
99981
Load factory defaults
Register 49999. Write 0xFF00 to load the meter's factory defaults.
UInt16-1W

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Sources: Precision Digital 'Modbus Register Tables for PROVU, ProtEX-MAX, and Helios Meters & Controllers' (https://predig.com/files/LIMModbus2.pdf, SHA-256 e6f176942122d9ab21e3718e6ea707870e29eadd5d2524ddcf6a4546e0be5eb8) for the map, and the PD6000 ProVu Instruction Manual LIM6000 (https://predig.com/files/LIM6000.pdf, SHA-256 ed993d60df31bc9ab748ff14323c41951e9c9e1438c773c50d26da3ad46d1f31), 'Factory Defaults & User Settings', for the frame: Slave ID 247, baud rate 9600, parity Even, transmit delay 50 ms. The specification table gives 8 data bits and '1 or 2 stop bits' but not which the factory setting uses, and register 40135 names stop bits only for its two no-parity codes (0 = none/1 stop bit, 1 = none/2 stop bits; 2 = odd, 3 = even), so 1 stop bit with the factory Even parity is this seed's reading of that four-choice menu, not a printed value - verify on site. Register numbers are the printed 4xxxx numbers; Note 1 of the document says the message address is the register number minus one (40100 is sent as 0x0063 = 99), and the table's Address (Hex) column prints that wire address, which this seed stores with zero_based. One document covers the ProVu family and its ProtEX-MAX (PD8-) and Helios (PD2-) siblings, so model rows exist; the seeded rows are shared by every model, plus relay 1/2 and manual override. Every 4x register is mirrored into 3x space and readable with function 04, so the map is seeded once, in the holding area. Data format is IEEE-754 float, highest byte first (byte order 1234), so BigEndian + HighFirst; register pairs print 'Long Hi'/'Long Lo'. Omitted: overflow mirrors 40033-40038, tare 40048-40050, the Modbus-display block 40070-40089, total/display settings 40105-40125, RTD count and low gate 40127-40128, point/exponent/tank/cutoff/batch rows 40138-40160, passwords 40171-40180, dual-scale and function-key rows 40181-40220, relays 3-8 (40319-40372), the 4-20 mA output 40401-40413, remote scaling and PV channel B (41001-46405).