  "spec_version": 1,
  "slug": "precision-digital-pd6000-prov",
  "manufacturer": "Precision Digital",
  "model": "ProVu / ProtEX-MAX / Helios meters and controllers (PD6000 family, firmware 4.000 and later)",
  "category": "Panel meter",
  "supplier_url": "https://www.predig.com/family/pd6000",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 247,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 9600,
      "parity": "Even",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [],
  "holding_registers": [
    {
      "address": 0,
      "count": 2,
      "name": "PV/Rate display value",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 40001-40002. Includes the decimal point; under range = -99999, over range = 999999, input open = -99999."
    },
    {
      "address": 2,
      "count": 1,
      "name": "Alarm and relay status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 40003. Bits 0-7 = relay 1-8 energized, bits 8-15 = alarm 1-8 active."
    },
    {
      "address": 3,
      "count": 1,
      "name": "Digital inputs and outputs status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 40004. Bits 0-7 = digital output 1-8 active, bits 8-15 = digital input 1-8 selected."
    },
    {
      "address": 4,
      "count": 2,
      "name": "Maximum display value",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 40005-40006, since power-up or the last max reset."
    },
    {
      "address": 6,
      "count": 2,
      "name": "Minimum display value",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 40007-40008, since power-up or the last min reset."
    },
    {
      "address": 8,
      "count": 2,
      "name": "Total value",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 40009-40010, since the last total reset; decimal point from 40103."
    },
    {
      "address": 10,
      "count": 2,
      "name": "Grand total value",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 40011-40012, since the last grand-total reset; decimal point from 40104."
    },
    {
      "address": 12,
      "count": 2,
      "name": "Total overflow value",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 40013-40014."
    },
    {
      "address": 14,
      "count": 2,
      "name": "Total non-overflow value",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 40015-40016."
    },
    {
      "address": 16,
      "count": 2,
      "name": "Grand total overflow value",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 40017-40018."
    },
    {
      "address": 18,
      "count": 2,
      "name": "Grand total non-overflow value",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 40019-40020."
    },
    {
      "address": 20,
      "count": 2,
      "name": "PV/Rate display value excluding the decimal point",
      "data_type": "Int32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 40021-40022, 'Long Hi'/'Long Lo' register pair; read both together with register 40021 first. Scale by the decimal point in 40102."
    },
    {
      "address": 22,
      "count": 1,
      "name": "Alarm and relay status (mirror)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 40023, mirror of 40003."
    },
    {
      "address": 23,
      "count": 1,
      "name": "Digital inputs and outputs status (mirror)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 40024, mirror of 40004."
    },
    {
      "address": 24,
      "count": 2,
      "name": "Maximum display value excluding the decimal point",
      "data_type": "Int32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 40025-40026."
    },
    {
      "address": 26,
      "count": 2,
      "name": "Minimum display value excluding the decimal point",
      "data_type": "Int32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 40027-40028."
    },
    {
      "address": 28,
      "count": 2,
      "name": "Total value excluding the decimal point",
      "data_type": "Int32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 40029-40030; decimal point from 40103."
    },
    {
      "address": 30,
      "count": 2,
      "name": "Grand total value excluding the decimal point",
      "data_type": "Int32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 40031-40032; decimal point from 40104."
    },
    {
      "address": 38,
      "count": 1,
      "name": "Start batch",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "W",
      "description": "Register 40039. Set bit 0 to start the batch process."
    },
    {
      "address": 39,
      "count": 1,
      "name": "Stop batch",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40040. Write 1 to pause, 1 again to stop; reading returns the batch state: 1 = start, 2 = pause, 4 = stop, 8 = delay."
    },
    {
      "address": 40,
      "count": 1,
      "name": "Alarm acknowledge",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "W",
      "description": "Register 40041. One bit per relay; set a bit to acknowledge that relay's alarm. Bits 0-7 mirror bits 8-15."
    },
    {
      "address": 41,
      "count": 1,
      "name": "Reset maximum display value",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "W",
      "description": "Register 40042. Set bit 0 to reset."
    },
    {
      "address": 42,
      "count": 1,
      "name": "Reset minimum display value",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "W",
      "description": "Register 40043. Set bit 0 to reset."
    },
    {
      "address": 43,
      "count": 1,
      "name": "Reset max/min display value",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "W",
      "description": "Register 40044. Set bit 0 to reset both."
    },
    {
      "address": 44,
      "count": 1,
      "name": "Reset total value",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "W",
      "description": "Register 40045. Set bit 0 to reset."
    },
    {
      "address": 45,
      "count": 1,
      "name": "Reset grand total value",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "W",
      "description": "Register 40046. Set bit 0 to reset."
    },
    {
      "address": 46,
      "count": 1,
      "name": "Reset batch count value",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "W",
      "description": "Register 40047. Set bit 0 to reset; the count itself is read at 40152."
    },
    {
      "address": 50,
      "count": 1,
      "name": "Control mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40051. 0 = auto, 1 = manual. Registers 40052-40069 only take effect in manual mode."
    },
    {
      "address": 51,
      "count": 1,
      "name": "Manual control analog output setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40052. Limits 0 to 23999; the document's unit cell reads 'A', as it does for the analog-output block at 40401 (1 to 23000), which only fits a 4-20 mA output if the value counts thousandths of a milliamp - verify the unit on site. Only effective when 40051 is 1 (manual)."
    },
    {
      "address": 53,
      "count": 1,
      "name": "Manual control relay 1 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40054(53). 0 = off, 1 = on."
    },
    {
      "address": 54,
      "count": 1,
      "name": "Manual control relay 2 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40055(54). 0 = off, 1 = on."
    },
    {
      "address": 55,
      "count": 1,
      "name": "Manual control relay 3 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40056(55). 0 = off, 1 = on."
    },
    {
      "address": 56,
      "count": 1,
      "name": "Manual control relay 4 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40057(56). 0 = off, 1 = on."
    },
    {
      "address": 57,
      "count": 1,
      "name": "Manual control relay 5 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40058(57). 0 = off, 1 = on."
    },
    {
      "address": 58,
      "count": 1,
      "name": "Manual control relay 6 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40059(58). 0 = off, 1 = on."
    },
    {
      "address": 59,
      "count": 1,
      "name": "Manual control relay 7 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40060(59). 0 = off, 1 = on."
    },
    {
      "address": 60,
      "count": 1,
      "name": "Manual control relay 8 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40061(60). 0 = off, 1 = on."
    },
    {
      "address": 61,
      "count": 1,
      "name": "Manual control digital output 1 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40062(61). 0 = off, 1 = on."
    },
    {
      "address": 62,
      "count": 1,
      "name": "Manual control digital output 2 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40063(62). 0 = off, 1 = on."
    },
    {
      "address": 63,
      "count": 1,
      "name": "Manual control digital output 3 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40064(63). 0 = off, 1 = on."
    },
    {
      "address": 64,
      "count": 1,
      "name": "Manual control digital output 4 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40065(64). 0 = off, 1 = on."
    },
    {
      "address": 65,
      "count": 1,
      "name": "Manual control digital output 5 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40066(65). 0 = off, 1 = on."
    },
    {
      "address": 66,
      "count": 1,
      "name": "Manual control digital output 6 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40067(66). 0 = off, 1 = on."
    },
    {
      "address": 67,
      "count": 1,
      "name": "Manual control digital output 7 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40068(67). 0 = off, 1 = on."
    },
    {
      "address": 68,
      "count": 1,
      "name": "Manual control digital output 8 setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40069(68). 0 = off, 1 = on."
    },
    {
      "address": 100,
      "count": 1,
      "name": "Input selection",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40101. Input type code, see Table 1 of the document."
    },
    {
      "address": 101,
      "count": 1,
      "name": "PV/Rate decimal point",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40102. 0-5 select decimal places (0 = none ... 5 = d.ddddd); 0 = dddd, 1 = dddd.d, 6 = dddd°u and 7 = dddd.du for temperature units."
    },
    {
      "address": 102,
      "count": 1,
      "name": "Total decimal point",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40103. 0 to 5 decimal places."
    },
    {
      "address": 103,
      "count": 1,
      "name": "Grand total decimal point",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40104. 0 to 5 decimal places."
    },
    {
      "address": 125,
      "count": 1,
      "name": "Adjust value",
      "data_type": "Int16",
      "units": "°C/°F",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40126. -500 to 500 = -50.0 to +50.0, applied to temperature inputs only."
    },
    {
      "address": 129,
      "count": 1,
      "name": "Filter setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40130. 0 = no filtering, 2-199 = old + ((new - old)/filter); for pulse input 900 = high speed and 202-250 = low speed (2 to 50 in that mode)."
    },
    {
      "address": 130,
      "count": 1,
      "name": "Bypass setting",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40131. 2 to 999 = 0.2 to 99.9 % of full scale; no effect when the filter is 0."
    },
    {
      "address": 131,
      "count": 1,
      "name": "Serial address",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40132. 1 to 247; factory default 247. Takes effect after the next meter reset."
    },
    {
      "address": 132,
      "count": 1,
      "name": "Serial baud rate",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40133. 0 = 300, 1 = 600, 2 = 1200, 3 = 2400, 4 = 4800, 5 = 9600, 6 = 19200; factory default 9600 (code 5). Takes effect after the next meter reset."
    },
    {
      "address": 133,
      "count": 1,
      "name": "Serial transmit delay",
      "data_type": "UInt16",
      "units": "ms",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40134. 0 to 199 ms; factory default 50 ms."
    },
    {
      "address": 134,
      "count": 1,
      "name": "Serial parity",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40135. 0 = none with 1 stop bit, 1 = none with 2 stop bits, 2 = odd, 3 = even; factory default Even with 1 stop bit."
    },
    {
      "address": 135,
      "count": 1,
      "name": "Serial byte-to-byte timeout",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "RW",
      "description": "Register 40136. 0 to 254 in 1/100 s; the minimum depends on the baud rate (0.01 s for 2400-19200 bps). Factory default 0.10 s."
    },
    {
      "address": 136,
      "count": 1,
      "name": "Function mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40137. 0 = linear, 1 = square root, 2 = exponent, 3 = round horizontal tank."
    },
    {
      "address": 300,
      "count": 1,
      "name": "Relay 1 mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40301. Operating mode bits, see Table 4 of the document."
    },
    {
      "address": 301,
      "count": 2,
      "name": "Relay 1 set point",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Registers 40302-40303."
    },
    {
      "address": 303,
      "count": 2,
      "name": "Relay 1 reset point",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Registers 40304-40305."
    },
    {
      "address": 305,
      "count": 1,
      "name": "Relay 1 on delay",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40306. 0 to 1999 in 0.1 s steps."
    },
    {
      "address": 306,
      "count": 1,
      "name": "Relay 1 off delay",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40307. 0 to 1999 in 0.1 s steps."
    },
    {
      "address": 307,
      "count": 2,
      "name": "Relay 1 sample time",
      "data_type": "Float32",
      "units": "s",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Registers 40308-40309. 0 to 59999 in 0.1 s steps."
    },
    {
      "address": 309,
      "count": 1,
      "name": "Relay 2 mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40310. Operating mode bits, see Table 4."
    },
    {
      "address": 310,
      "count": 2,
      "name": "Relay 2 set point",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Registers 40311-40312."
    },
    {
      "address": 312,
      "count": 2,
      "name": "Relay 2 reset point",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Registers 40313-40314."
    },
    {
      "address": 314,
      "count": 1,
      "name": "Relay 2 on delay",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40315. 0 to 1999 in 0.1 s steps."
    },
    {
      "address": 315,
      "count": 1,
      "name": "Relay 2 off delay",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "Register 40316. 0 to 1999 in 0.1 s steps."
    },
    {
      "address": 316,
      "count": 2,
      "name": "Relay 2 sample time",
      "data_type": "Float32",
      "units": "s",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Registers 40317-40318. 0 to 59999 in 0.1 s steps."
    },
    {
      "address": 9900,
      "count": 4,
      "name": "Product identifier",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 49901-49904. Eight ASCII characters: product/software release, main-board input and input card."
    },
    {
      "address": 9904,
      "count": 4,
      "name": "Firmware version (ASCII)",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Registers 49905-49908. Eight ASCII characters."
    },
    {
      "address": 9916,
      "count": 1,
      "name": "Product number",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 49917. Product code, see Table 7 of the document."
    },
    {
      "address": 9917,
      "count": 1,
      "name": "Firmware version",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Register 49918. Divide by 1000: 2200 = v2.200."
    },
    {
      "address": 9997,
      "count": 1,
      "name": "Initialize meter serial communication",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "W",
      "description": "Register 49998. Write 0xFF00 to apply new serial port parameters."
    },
    {
      "address": 9998,
      "count": 1,
      "name": "Load factory defaults",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "W",
      "description": "Register 49999. Write 0xFF00 to load the meter's factory defaults."
    }
  ],
  "combined_registers": [],
  "notes": "Sources: Precision Digital 'Modbus Register Tables for PROVU, ProtEX-MAX, and Helios Meters & Controllers' (https://predig.com/files/LIMModbus2.pdf, SHA-256 e6f176942122d9ab21e3718e6ea707870e29eadd5d2524ddcf6a4546e0be5eb8) for the map, and the PD6000 ProVu Instruction Manual LIM6000 (https://predig.com/files/LIM6000.pdf, SHA-256 ed993d60df31bc9ab748ff14323c41951e9c9e1438c773c50d26da3ad46d1f31), 'Factory Defaults & User Settings', for the frame: Slave ID 247, baud rate 9600, parity Even, transmit delay 50 ms. The specification table gives 8 data bits and '1 or 2 stop bits' but not which the factory setting uses, and register 40135 names stop bits only for its two no-parity codes (0 = none/1 stop bit, 1 = none/2 stop bits; 2 = odd, 3 = even), so 1 stop bit with the factory Even parity is this seed's reading of that four-choice menu, not a printed value - verify on site. Register numbers are the printed 4xxxx numbers; Note 1 of the document says the message address is the register number minus one (40100 is sent as 0x0063 = 99), and the table's Address (Hex) column prints that wire address, which this seed stores with zero_based. One document covers the ProVu family and its ProtEX-MAX (PD8-) and Helios (PD2-) siblings, so model rows exist; the seeded rows are shared by every model, plus relay 1/2 and manual override. Every 4x register is mirrored into 3x space and readable with function 04, so the map is seeded once, in the holding area. Data format is IEEE-754 float, highest byte first (byte order 1234), so BigEndian + HighFirst; register pairs print 'Long Hi'/'Long Lo'. Omitted: overflow mirrors 40033-40038, tare 40048-40050, the Modbus-display block 40070-40089, total/display settings 40105-40125, RTD count and low gate 40127-40128, point/exponent/tank/cutoff/batch rows 40138-40160, passwords 40171-40180, dual-scale and function-key rows 40181-40220, relays 3-8 (40319-40372), the 4-20 mA output 40401-40413, remote scaling and PV channel B (41001-46405)."
}