ioLogik E2262 (8 thermocouple inputs + 4 digital outputs) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
321
TC enable channel 0
<RW> 0 = Disable, 1 = Enable (coil reference 00033).
Binary-1RW
331
TC enable channel 1
<RW> 0 = Disable, 1 = Enable (coil reference 00034).
Binary-1RW
341
TC enable channel 2
<RW> 0 = Disable, 1 = Enable (coil reference 00035).
Binary-1RW
351
TC enable channel 3
<RW> 0 = Disable, 1 = Enable (coil reference 00036).
Binary-1RW
361
TC enable channel 4
<RW> 0 = Disable, 1 = Enable (coil reference 00037).
Binary-1RW
371
TC enable channel 5
<RW> 0 = Disable, 1 = Enable (coil reference 00038).
Binary-1RW
381
TC enable channel 6
<RW> 0 = Disable, 1 = Enable (coil reference 00039).
Binary-1RW
391
TC enable channel 7
<RW> 0 = Disable, 1 = Enable (coil reference 00040).
Binary-1RW
401
DO status channel 0
<RW> 0 = OFF, 1 = ON (coil reference 00041).
Binary-1RW
411
DO status channel 1
<RW> 0 = OFF, 1 = ON (coil reference 00042).
Binary-1RW
421
DO status channel 2
<RW> 0 = OFF, 1 = ON (coil reference 00043).
Binary-1RW
431
DO status channel 3
<RW> 0 = OFF, 1 = ON (coil reference 00044).
Binary-1RW
441
DO power-on status channel 0
<RW> 0 = OFF, 1 = ON (coil reference 00045).
Binary-1RW
451
DO power-on status channel 1
<RW> 0 = OFF, 1 = ON (coil reference 00046).
Binary-1RW
461
DO power-on status channel 2
<RW> 0 = OFF, 1 = ON (coil reference 00047).
Binary-1RW
471
DO power-on status channel 3
<RW> 0 = OFF, 1 = ON (coil reference 00048).
Binary-1RW
481
DO safe status channel 0
<RW> 0 = OFF, 1 = ON (coil reference 00049).
Binary-1RW
491
DO safe status channel 1
<RW> 0 = OFF, 1 = ON (coil reference 00050).
Binary-1RW
501
DO safe status channel 2
<RW> 0 = OFF, 1 = ON (coil reference 00051).
Binary-1RW
511
DO safe status channel 3
<RW> 0 = OFF, 1 = ON (coil reference 00052).
Binary-1RW
521
DO pulse output status channel 0
<RW> 0 = Stop, 1 = Start (coil reference 00053).
Binary-1RW
531
DO pulse output status channel 1
<RW> 0 = Stop, 1 = Start (coil reference 00054).
Binary-1RW
541
DO pulse output status channel 2
<RW> 0 = Stop, 1 = Start (coil reference 00055).
Binary-1RW
551
DO pulse output status channel 3
<RW> 0 = Stop, 1 = Start (coil reference 00056).
Binary-1RW
561
DO power-on pulse output status channel 0
<RW> 0 = Stop, 1 = Start (coil reference 00057).
Binary-1RW
571
DO power-on pulse output status channel 1
<RW> 0 = Stop, 1 = Start (coil reference 00058).
Binary-1RW
581
DO power-on pulse output status channel 2
<RW> 0 = Stop, 1 = Start (coil reference 00059).
Binary-1RW
591
DO power-on pulse output status channel 3
<RW> 0 = Stop, 1 = Start (coil reference 00060).
Binary-1RW
601
DO safe-mode pulse output status channel 0
<RW> 0 = Stop, 1 = Start (coil reference 00061).
Binary-1RW
611
DO safe-mode pulse output status channel 1
<RW> 0 = Stop, 1 = Start (coil reference 00062).
Binary-1RW
621
DO safe-mode pulse output status channel 2
<RW> 0 = Stop, 1 = Start (coil reference 00063).
Binary-1RW
631
DO safe-mode pulse output status channel 3
<RW> 0 = Stop, 1 = Start (coil reference 00064).
Binary-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Ethernet remote I/O with a built-in Modbus/TCP server, so no gateway is needed. Source: Moxa "ioLogik E2200 Series User Manual" v7.2, section "ioLogik E2262 Modbus Mapping" (manual pages 235-239): 0xxxx read/write coils, 3xxxx read-only registers (function 04) and 4xxxx read/write registers (functions 03/06/16). The mapping table prints the reference number and the hexadecimal address side by side; this seed stores the hex address with zero-based addressing. Every 32-bit value in the 3xxxx block is printed as separate high-word and low-word rows, so each value is one two-register row here, high word first. The table gives the unit of the TC values as "0.1 (Celsius, Fahrenheit) or 0.0001 (mV)": it follows the channel's engineering unit register (40029-40044), which this seed lists, and the value rows are scaled 0.1 with degC as the default unit. The write-only per-channel reset coils (00001-00032, marked <W>) are left out because the coil area of this format carries read or read/write entries only. Unit identifier 1: it is the ioLogik's default Modbus/TCP ID in the shipped configuration and is set in the web console if a site uses another value. Left out of the 4xxxx block, because the manual's own chapter stops at the engineering-unit registers here: the TC sensor-type registers (40045-40060), the reset minimum/maximum registers (40061-40092), the word mirrors of the DO status and TC enable bits (40093-40124) and the internal Click&Go registers (40313-40360); the sensor-type enumeration (0 = J, 1 = K ... 20 = AVG, 21 = DIF) is the one setting a site normally needs to change, so confirm it in the ioLogik web console.