Moxa · Remote I/O
ioLogik E1211 Modbus register map
Default configuration
- Protocol
- Modbus TCP
- Port
- 502
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 0 | 1 | Digital output 0 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 1 | 1 | Digital output 1 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 2 | 1 | Digital output 2 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 3 | 1 | Digital output 3 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 4 | 1 | Digital output 4 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 5 | 1 | Digital output 5 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 6 | 1 | Digital output 6 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 7 | 1 | Digital output 7 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 8 | 1 | Digital output 8 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 9 | 1 | Digital output 9 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 10 | 1 | Digital output 10 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 11 | 1 | Digital output 11 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 12 | 1 | Digital output 12 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 13 | 1 | Digital output 13 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 14 | 1 | Digital output 14 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 15 | 1 | Digital output 15 status 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 16 | 1 | Digital output 0 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 17 | 1 | Digital output 1 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 18 | 1 | Digital output 2 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 19 | 1 | Digital output 3 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 20 | 1 | Digital output 4 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 21 | 1 | Digital output 5 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 22 | 1 | Digital output 6 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 23 | 1 | Digital output 7 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 24 | 1 | Digital output 8 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 25 | 1 | Digital output 9 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 26 | 1 | Digital output 10 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 27 | 1 | Digital output 11 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 28 | 1 | Digital output 12 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 29 | 1 | Digital output 13 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 30 | 1 | Digital output 14 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 31 | 1 | Digital output 15 pulse output Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 4128 | 1 | Digital output 0 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4129 | 1 | Digital output 1 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4130 | 1 | Digital output 2 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4131 | 1 | Digital output 3 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4132 | 1 | Digital output 4 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4133 | 1 | Digital output 5 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4134 | 1 | Digital output 6 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4135 | 1 | Digital output 7 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4136 | 1 | Digital output 8 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4137 | 1 | Digital output 9 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4138 | 1 | Digital output 10 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4139 | 1 | Digital output 11 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4140 | 1 | Digital output 12 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4141 | 1 | Digital output 13 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4142 | 1 | Digital output 14 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4143 | 1 | Digital output 15 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4144 | 1 | Watchdog alarm flag clear Write 1 to clear the watchdog alarm. | Binary | - | 1 | RW |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Ethernet remote I/O with a built-in Modbus/TCP server; no gateway needed. Addresses are the manual's decimal start addresses, which are the zero-based wire addresses (the manual also prints the 1-based reference numbers). Each channel occupies one address in the start-address table, so this map lists channels separately. Source: Moxa ioLogik E1200 Series User Manual v16.2, appendix A, 'ioLogik E1211 Modbus Address and Register Map' (16 digital outputs, no digital inputs). The manual types the pulse-count presets as one 16-bit word per channel ('word'), unlike the E1214 where each preset is 32 bits. Unit identifier: the manual states that the Modbus/TCP ID of the ioLogik E1200 is set to 1 by default, so unit_id 1 is used.