ioLogik E1211 Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
01
Digital output 0 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
11
Digital output 1 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
21
Digital output 2 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
31
Digital output 3 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
41
Digital output 4 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
51
Digital output 5 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
61
Digital output 6 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
71
Digital output 7 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
81
Digital output 8 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
91
Digital output 9 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
101
Digital output 10 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
111
Digital output 11 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
121
Digital output 12 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
131
Digital output 13 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
141
Digital output 14 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
151
Digital output 15 status
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
161
Digital output 0 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
171
Digital output 1 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
181
Digital output 2 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
191
Digital output 3 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
201
Digital output 4 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
211
Digital output 5 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
221
Digital output 6 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
231
Digital output 7 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
241
Digital output 8 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
251
Digital output 9 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
261
Digital output 10 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
271
Digital output 11 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
281
Digital output 12 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
291
Digital output 13 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
301
Digital output 14 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
311
Digital output 15 pulse output
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
41281
Digital output 0 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41291
Digital output 1 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41301
Digital output 2 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41311
Digital output 3 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41321
Digital output 4 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41331
Digital output 5 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41341
Digital output 6 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41351
Digital output 7 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41361
Digital output 8 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41371
Digital output 9 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41381
Digital output 10 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41391
Digital output 11 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41401
Digital output 12 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41411
Digital output 13 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41421
Digital output 14 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41431
Digital output 15 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41441
Watchdog alarm flag clear
Write 1 to clear the watchdog alarm.
Binary-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Ethernet remote I/O with a built-in Modbus/TCP server; no gateway needed. Addresses are the manual's decimal start addresses, which are the zero-based wire addresses (the manual also prints the 1-based reference numbers). Each channel occupies one address in the start-address table, so this map lists channels separately. Source: Moxa ioLogik E1200 Series User Manual v16.2, appendix A, 'ioLogik E1211 Modbus Address and Register Map' (16 digital outputs, no digital inputs). The manual types the pulse-count presets as one 16-bit word per channel ('word'), unlike the E1214 where each preset is 32 bits. Unit identifier: the manual states that the Modbus/TCP ID of the ioLogik E1200 is set to 1 by default, so unit_id 1 is used.