Moxa · Remote I/O
ioLogik E2242 (12 configurable digital I/O + 4 analog inputs) Modbus register map
Default configuration
- Protocol
- Modbus TCP
- Port
- 502
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 0 | 1 | DIO channel 0 output value Coil 0x0000. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x009C). | Binary | - | 1 | RW |
| 1 | 1 | DIO channel 1 output value Coil 0x0001. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x009D). | Binary | - | 1 | RW |
| 2 | 1 | DIO channel 2 output value Coil 0x0002. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x009E). | Binary | - | 1 | RW |
| 3 | 1 | DIO channel 3 output value Coil 0x0003. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x009F). | Binary | - | 1 | RW |
| 4 | 1 | DIO channel 4 output value Coil 0x0004. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A0). | Binary | - | 1 | RW |
| 5 | 1 | DIO channel 5 output value Coil 0x0005. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A1). | Binary | - | 1 | RW |
| 6 | 1 | DIO channel 6 output value Coil 0x0006. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A2). | Binary | - | 1 | RW |
| 7 | 1 | DIO channel 7 output value Coil 0x0007. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A3). | Binary | - | 1 | RW |
| 8 | 1 | DIO channel 8 output value Coil 0x0008. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A4). | Binary | - | 1 | RW |
| 9 | 1 | DIO channel 9 output value Coil 0x0009. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A5). | Binary | - | 1 | RW |
| 10 | 1 | DIO channel 10 output value Coil 0x000A. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A6). | Binary | - | 1 | RW |
| 11 | 1 | DIO channel 11 output value Coil 0x000B. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A7). | Binary | - | 1 | RW |
| 156 | 1 | DIO channel 0 direction Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT. | Binary | - | 1 | RW |
| 157 | 1 | DIO channel 1 direction Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT. | Binary | - | 1 | RW |
| 158 | 1 | DIO channel 2 direction Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT. | Binary | - | 1 | RW |
| 159 | 1 | DIO channel 3 direction Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT. | Binary | - | 1 | RW |
| 160 | 1 | DIO channel 4 direction Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT. | Binary | - | 1 | RW |
| 161 | 1 | DIO channel 5 direction Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT. | Binary | - | 1 | RW |
| 162 | 1 | DIO channel 6 direction Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT. | Binary | - | 1 | RW |
| 163 | 1 | DIO channel 7 direction Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT. | Binary | - | 1 | RW |
| 164 | 1 | DIO channel 8 direction Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT. | Binary | - | 1 | RW |
| 165 | 1 | DIO channel 9 direction Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT. | Binary | - | 1 | RW |
| 166 | 1 | DIO channel 10 direction Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT. | Binary | - | 1 | RW |
| 167 | 1 | DIO channel 11 direction Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT. | Binary | - | 1 | RW |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: Moxa 'ioLogik E2200 Series User Manual' v7.2 (https://moxa.com/getmedia/b6e2827c-9244-446a-babd-d9416dc55765/moxa-iologik-e2200-series-manual-v7.2.pdf, SHA-256 62e957d08fdcb61140b28a45fe54c337a7e5883d181f68251bb2286cf4bd651b), section 'ioLogik E2242 Modbus Mapping' (manual pages 214-232): the 0xxxx read/write coils, 1xxxx read-only coils, 3xxxx read-only registers and 4xxxx read/write registers, each with its reference number and hexadecimal address side by side. The seed stores the hexadecimal (wire) address and declares zero_based. The E2242 has 12 channels that can each be an input or an output (coils 0x009C-0x00A7 choose the direction; the manual states its own per-channel defaults: 0-5 INPUT, 6-11 OUTPUT) plus four analog inputs, so the same channel appears in both the coil and the discrete-input table; the direction coil decides which one is live. Every 32-bit DI counter is printed as a separate high-word and low-word row, so each is one two-register UInt32 row here, high word first. The analog channel value, minimum and maximum registers are seeded unscaled and unit-less because this manual never states their encoding (the input range is selectable in hardware/software at 4x0200-4x0203), and no fixed scale_factor can follow a range that is configured per site - the module's own scaled result, registers 40305-40312 'AI Channel n Scale Value', is printed low-word first and is therefore left out rather than decoded with this seed's HighFirst convention. Omitted on purpose: the DO pulse count, pulse low/high width, power-on and safe value blocks (4x0000-4x0047 and coils 0x000C-0x009B), the AI min/max reset coils, the internal-register working values and the scrambled system-information block (IP address, time, module strings). Unit identifier 1 is a declared placeholder: the ioLogik's Modbus/TCP ID and IP address are set in its web console and the manual prints no factory value for the unit field.