All devices

Moxa · Remote I/O

ioLogik E2242 (12 configurable digital I/O + 4 analog inputs) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
01
DIO channel 0 output value
Coil 0x0000. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x009C).
Binary-1RW
11
DIO channel 1 output value
Coil 0x0001. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x009D).
Binary-1RW
21
DIO channel 2 output value
Coil 0x0002. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x009E).
Binary-1RW
31
DIO channel 3 output value
Coil 0x0003. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x009F).
Binary-1RW
41
DIO channel 4 output value
Coil 0x0004. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A0).
Binary-1RW
51
DIO channel 5 output value
Coil 0x0005. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A1).
Binary-1RW
61
DIO channel 6 output value
Coil 0x0006. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A2).
Binary-1RW
71
DIO channel 7 output value
Coil 0x0007. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A3).
Binary-1RW
81
DIO channel 8 output value
Coil 0x0008. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A4).
Binary-1RW
91
DIO channel 9 output value
Coil 0x0009. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A5).
Binary-1RW
101
DIO channel 10 output value
Coil 0x000A. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A6).
Binary-1RW
111
DIO channel 11 output value
Coil 0x000B. 0 = off, 1 = on; effective when the channel is configured as an output (see the direction coil 0x00A7).
Binary-1RW
1561
DIO channel 0 direction
Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT.
Binary-1RW
1571
DIO channel 1 direction
Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT.
Binary-1RW
1581
DIO channel 2 direction
Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT.
Binary-1RW
1591
DIO channel 3 direction
Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT.
Binary-1RW
1601
DIO channel 4 direction
Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT.
Binary-1RW
1611
DIO channel 5 direction
Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT.
Binary-1RW
1621
DIO channel 6 direction
Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT.
Binary-1RW
1631
DIO channel 7 direction
Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT.
Binary-1RW
1641
DIO channel 8 direction
Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT.
Binary-1RW
1651
DIO channel 9 direction
Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT.
Binary-1RW
1661
DIO channel 10 direction
Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT.
Binary-1RW
1671
DIO channel 11 direction
Coil 0x009C-0x00A7. 1 = OUTPUT, 0 = INPUT. The manual prints the defaults per channel: channels 0-5 INPUT, channels 6-11 OUTPUT.
Binary-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Moxa 'ioLogik E2200 Series User Manual' v7.2 (https://moxa.com/getmedia/b6e2827c-9244-446a-babd-d9416dc55765/moxa-iologik-e2200-series-manual-v7.2.pdf, SHA-256 62e957d08fdcb61140b28a45fe54c337a7e5883d181f68251bb2286cf4bd651b), section 'ioLogik E2242 Modbus Mapping' (manual pages 214-232): the 0xxxx read/write coils, 1xxxx read-only coils, 3xxxx read-only registers and 4xxxx read/write registers, each with its reference number and hexadecimal address side by side. The seed stores the hexadecimal (wire) address and declares zero_based. The E2242 has 12 channels that can each be an input or an output (coils 0x009C-0x00A7 choose the direction; the manual states its own per-channel defaults: 0-5 INPUT, 6-11 OUTPUT) plus four analog inputs, so the same channel appears in both the coil and the discrete-input table; the direction coil decides which one is live. Every 32-bit DI counter is printed as a separate high-word and low-word row, so each is one two-register UInt32 row here, high word first. The analog channel value, minimum and maximum registers are seeded unscaled and unit-less because this manual never states their encoding (the input range is selectable in hardware/software at 4x0200-4x0203), and no fixed scale_factor can follow a range that is configured per site - the module's own scaled result, registers 40305-40312 'AI Channel n Scale Value', is printed low-word first and is therefore left out rather than decoded with this seed's HighFirst convention. Omitted on purpose: the DO pulse count, pulse low/high width, power-on and safe value blocks (4x0000-4x0047 and coils 0x000C-0x009B), the AI min/max reset coils, the internal-register working values and the scrambled system-information block (IP address, time, module strings). Unit identifier 1 is a declared placeholder: the ioLogik's Modbus/TCP ID and IP address are set in its web console and the manual prints no factory value for the unit field.