Moxa · Remote I/O
ioLogik E1214 Modbus register map
Default configuration
- Protocol
- Modbus TCP
- Port
- 502
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 0 | 1 | Relay output 0 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 1 | 1 | Relay output 1 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 2 | 1 | Relay output 2 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 3 | 1 | Relay output 3 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 4 | 1 | Relay output 4 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 5 | 1 | Relay output 5 0 = off, 1 = on. Write through the coil with function code 05. | Binary | - | 1 | RW |
| 16 | 1 | Relay pulse output 0 Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 17 | 1 | Relay pulse output 1 Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 18 | 1 | Relay pulse output 2 Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 19 | 1 | Relay pulse output 3 Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 20 | 1 | Relay pulse output 4 Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 21 | 1 | Relay pulse output 5 Pulse output start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 256 | 1 | DI counter 0 status Counter start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 257 | 1 | DI counter 1 status Counter start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 258 | 1 | DI counter 2 status Counter start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 259 | 1 | DI counter 3 status Counter start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 260 | 1 | DI counter 4 status Counter start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 261 | 1 | DI counter 5 status Counter start/stop: 0 = stop, 1 = start. | Binary | - | 1 | RW |
| 272 | 1 | DI counter 0 reset Write 1 to reset the counter to its initial value. | Binary | - | 1 | RW |
| 273 | 1 | DI counter 1 reset Write 1 to reset the counter to its initial value. | Binary | - | 1 | RW |
| 274 | 1 | DI counter 2 reset Write 1 to reset the counter to its initial value. | Binary | - | 1 | RW |
| 275 | 1 | DI counter 3 reset Write 1 to reset the counter to its initial value. | Binary | - | 1 | RW |
| 276 | 1 | DI counter 4 reset Write 1 to reset the counter to its initial value. | Binary | - | 1 | RW |
| 277 | 1 | DI counter 5 reset Write 1 to reset the counter to its initial value. | Binary | - | 1 | RW |
| 288 | 1 | DI counter 0 overflow flag clear Write 1 to clear the overflow flag. | Binary | - | 1 | RW |
| 289 | 1 | DI counter 1 overflow flag clear Write 1 to clear the overflow flag. | Binary | - | 1 | RW |
| 290 | 1 | DI counter 2 overflow flag clear Write 1 to clear the overflow flag. | Binary | - | 1 | RW |
| 291 | 1 | DI counter 3 overflow flag clear Write 1 to clear the overflow flag. | Binary | - | 1 | RW |
| 292 | 1 | DI counter 4 overflow flag clear Write 1 to clear the overflow flag. | Binary | - | 1 | RW |
| 293 | 1 | DI counter 5 overflow flag clear Write 1 to clear the overflow flag. | Binary | - | 1 | RW |
| 4128 | 1 | Relay 0 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4129 | 1 | Relay 1 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4130 | 1 | Relay 2 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4131 | 1 | Relay 3 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4132 | 1 | Relay 4 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4133 | 1 | Relay 5 peer-to-peer safe mode flag clear Write 1 to clear the safe mode flag. | Binary | - | 1 | RW |
| 4144 | 1 | Watchdog alarm flag clear Write 1 to clear the watchdog alarm. | Binary | - | 1 | RW |
Notes
Ethernet remote I/O (6 digital inputs, 6 relay outputs) with a built-in Modbus/TCP server; no gateway needed. Addresses are the manual's decimal start addresses, which are zero-based wire addresses (the manual also prints the 1-based reference numbers: coil 0 = 00001, discrete input 0 = 10001, input register 16 = 30017, holding register 32 = 40033). Each channel occupies one address in the start-address table, so this map lists channels separately. Source: Moxa ioLogik E1200 Series User Manual v16.2, appendix A 'ioLogik E1214 Modbus Address and Register Map'. Unit identifier: the manual documents no slave-address setting for the Modbus/TCP server, so 1 is used as the default.