ioLogik E1214 Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
01
Relay output 0
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
11
Relay output 1
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
21
Relay output 2
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
31
Relay output 3
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
41
Relay output 4
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
51
Relay output 5
0 = off, 1 = on. Write through the coil with function code 05.
Binary-1RW
161
Relay pulse output 0
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
171
Relay pulse output 1
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
181
Relay pulse output 2
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
191
Relay pulse output 3
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
201
Relay pulse output 4
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
211
Relay pulse output 5
Pulse output start/stop: 0 = stop, 1 = start.
Binary-1RW
2561
DI counter 0 status
Counter start/stop: 0 = stop, 1 = start.
Binary-1RW
2571
DI counter 1 status
Counter start/stop: 0 = stop, 1 = start.
Binary-1RW
2581
DI counter 2 status
Counter start/stop: 0 = stop, 1 = start.
Binary-1RW
2591
DI counter 3 status
Counter start/stop: 0 = stop, 1 = start.
Binary-1RW
2601
DI counter 4 status
Counter start/stop: 0 = stop, 1 = start.
Binary-1RW
2611
DI counter 5 status
Counter start/stop: 0 = stop, 1 = start.
Binary-1RW
2721
DI counter 0 reset
Write 1 to reset the counter to its initial value.
Binary-1RW
2731
DI counter 1 reset
Write 1 to reset the counter to its initial value.
Binary-1RW
2741
DI counter 2 reset
Write 1 to reset the counter to its initial value.
Binary-1RW
2751
DI counter 3 reset
Write 1 to reset the counter to its initial value.
Binary-1RW
2761
DI counter 4 reset
Write 1 to reset the counter to its initial value.
Binary-1RW
2771
DI counter 5 reset
Write 1 to reset the counter to its initial value.
Binary-1RW
2881
DI counter 0 overflow flag clear
Write 1 to clear the overflow flag.
Binary-1RW
2891
DI counter 1 overflow flag clear
Write 1 to clear the overflow flag.
Binary-1RW
2901
DI counter 2 overflow flag clear
Write 1 to clear the overflow flag.
Binary-1RW
2911
DI counter 3 overflow flag clear
Write 1 to clear the overflow flag.
Binary-1RW
2921
DI counter 4 overflow flag clear
Write 1 to clear the overflow flag.
Binary-1RW
2931
DI counter 5 overflow flag clear
Write 1 to clear the overflow flag.
Binary-1RW
41281
Relay 0 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41291
Relay 1 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41301
Relay 2 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41311
Relay 3 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41321
Relay 4 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41331
Relay 5 peer-to-peer safe mode flag clear
Write 1 to clear the safe mode flag.
Binary-1RW
41441
Watchdog alarm flag clear
Write 1 to clear the watchdog alarm.
Binary-1RW

Notes

Ethernet remote I/O (6 digital inputs, 6 relay outputs) with a built-in Modbus/TCP server; no gateway needed. Addresses are the manual's decimal start addresses, which are zero-based wire addresses (the manual also prints the 1-based reference numbers: coil 0 = 00001, discrete input 0 = 10001, input register 16 = 30017, holding register 32 = 40033). Each channel occupies one address in the start-address table, so this map lists channels separately. Source: Moxa ioLogik E1200 Series User Manual v16.2, appendix A 'ioLogik E1214 Modbus Address and Register Map'. Unit identifier: the manual documents no slave-address setting for the Modbus/TCP server, so 1 is used as the default.