MidNite Solar · Charge controller
Classic 150 / Classic 200 / Classic 250 / Classic 250KS MPPT charge controllers Modbus register map
Default configuration
- Protocol
- Modbus TCP
- Port
- 502
- Unit ID
- 10
- Addressing
- 1-based
- Byte order
- Big endian
- Word order
- Low word first
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 4101 | 1 | Unit ID PCB revision in the high byte, unit type in the low byte. Unit type values printed by the document: 150 Classic 150, 200 Classic 200, 250 Classic 250, 251 Classic 250KS. | UInt16 | - | 1 | R |
| 4102 | 1 | Software build year | UInt16 | - | 1 | R |
| 4103 | 1 | Software build month and day Month in the high byte, day in the low byte. | UInt16 | - | 1 | R |
| 4104 | 1 | Information flags word 3 Bit field; bit 0x0001 is WhizBangJrCrcGood. | UInt16 | - | 1 | R |
| 4109 | 2 | WhizBang Jr. net amp hours Signed, as the document prints it; low word at 4109, high word at 4110. | Int32 | Ah | 1 | R |
| 4111 | 2 | Unit device ID Low word at 4111, high word at 4112. | UInt32 | - | 1 | R |
| 4113 | 1 | Status roll A 12-bit value that changes once per second in the low 12 bits, with a 4-bit counter in the top 4 bits. | UInt16 | - | 1 | R |
| 4114 | 1 | Restart timer Countdown until the Classic can wake up. | UInt16 | ms | 1 | R |
| 4115 | 1 | Average battery voltage One-second average. | UInt16 | V | 0.1 | R |
| 4116 | 1 | Average PV voltage One-second average. | UInt16 | V | 0.1 | R |
| 4117 | 1 | Displayed battery current One-second average. | UInt16 | A | 0.1 | R |
| 4118 | 1 | Average energy to the battery Reset once per day. | UInt16 | kWh | 0.1 | R |
| 4119 | 1 | Average power to the battery | UInt16 | W | 1 | R |
| 4120 | 1 | Charge stage and state Charge stage in the high byte, state in the low byte. Document stage values: 0 Resting, 3 Absorb, 4 BulkMppt, 5 Float, 6 FloatMppt, 7 Equalize, 10 HyperVoc, 18 EqMppt. | UInt16 | - | 1 | R |
| 4121 | 1 | PV input current One-second average. | UInt16 | A | 0.1 | R |
| 4122 | 1 | Last measured open-circuit PV voltage | UInt16 | V | 0.1 | R |
| 4123 | 1 | Highest input voltage seen | UInt16 | V | 0.1 | R |
| 4124 | 1 | Match point shadow index Present wind power curve step being indexed, 1-16. | UInt16 | - | 1 | R |
| 4125 | 1 | Daily amp hours Reset at 23:59. | UInt16 | Ah | 1 | R |
| 4126 | 2 | Lifetime energy generation Low word at 4126, high word at 4127, as the document's formula shows. | UInt32 | kWh | 1 | R |
| 4128 | 2 | Lifetime amp-hour generation Low word at 4128, high word at 4129. | UInt32 | Ah | 1 | R |
| 4130 | 2 | Information flags words 1 and 2 Low word (InfoFlagsBits) at 4130, InfoFlagsBits2 at 4131; the document's bit table 4130-1 decodes them. | UInt32 | - | 1 | R |
| 4132 | 1 | Battery temperature From the external battery temperature sensor; the document notes 25 °C is reported when none is fitted. | Int16 | °C | 0.1 | R |
| 4133 | 1 | FET temperature | Int16 | °C | 0.1 | R |
| 4134 | 1 | Control PCB temperature | Int16 | °C | 0.1 | R |
| 4135 | 1 | Minutes without power Counts up while there is no power, resets to 0 when there is power. | UInt16 | min | 1 | R |
| 4136 | 1 | Recent-history log interval Minimum 60 seconds, as the document prints. | UInt16 | s | 1 | RW |
| 4137 | 1 | Modbus port number Valid range 0-65535, default 502, as the document prints. | UInt16 | - | 1 | RW |
| 4138 | 1 | Float time today Reset at 23:59. | UInt16 | s | 1 | R |
| 4139 | 1 | Absorb time remaining Readable, seeded read-only: writing it changes how the battery is charged, and the document's disclaimer says a wrong charge setting can damage a battery bank. | UInt16 | s | 1 | R |
| 4141 | 1 | PWM duty command Read-only duty cycle, 0-1023 counts, not percent. | UInt16 | - | 1 | R |
| 4142 | 1 | Reason for the last reset Enum decoded by the document's table 4142-1. | UInt16 | - | 1 | R |
| 4143 | 1 | Equalize time remaining Readable, seeded read-only: writing it changes how the battery is charged, and the document's disclaimer says a wrong charge setting can damage a battery bank. | UInt16 | s | 1 | R |
| 4148 | 1 | Battery output current limit Readable, and seeded read-only: writing it changes how the battery is charged, and the document's own disclaimer says a wrong charge voltage can damage a battery bank. | UInt16 | A | 0.1 | R |
| 4149 | 1 | Absorb set point voltage Readable, and seeded read-only: writing it changes how the battery is charged, and the document's own disclaimer says a wrong charge voltage can damage a battery bank. | UInt16 | V | 0.1 | R |
| 4150 | 1 | Float voltage set point Readable, and seeded read-only: writing it changes how the battery is charged, and the document's own disclaimer says a wrong charge voltage can damage a battery bank. | UInt16 | V | 0.1 | R |
| 4151 | 1 | Equalize voltage set point Readable, and seeded read-only: writing it changes how the battery is charged, and the document's own disclaimer says a wrong charge voltage can damage a battery bank. | UInt16 | V | 0.1 | R |
| 4152 | 1 | Sliding current limit | UInt16 | A | 1 | R |
| 4157 | 1 | Battery temperature compensation per cell The document's conversion is -([4157] / 10) mV per degree C per 2 V cell, in 0.5 mV steps, so the row carries that negative scale: the compensation lowers the charge voltage as the pack warms. | Int16 | mV/°C | -0.1 | R |
| 4162 | 1 | Equalize time Readable, and seeded read-only: writing it changes how the battery is charged, and the document's own disclaimer says a wrong charge voltage can damage a battery bank. | UInt16 | s | 1 | R |
| 4163 | 1 | Equalize interval Readable, and seeded read-only: writing it changes how the battery is charged, and the document's own disclaimer says a wrong charge voltage can damage a battery bank. | UInt16 | days | 1 | R |
| 4166 | 1 | Aux 1 low absolute voltage Readable, seeded read-only with the other MidNite settings: a wrong threshold switches a load at the wrong time. | UInt16 | V | 0.1 | R |
| 4204 | 1 | MPP percent of Voc Readable, seeded read-only: writing it changes how the battery is charged, and the document's disclaimer says a wrong charge setting can damage a battery bank. | UInt16 | % | 1 | R |
| 4240 | 2 | Read-only flags Low word at 4240, high word at 4241. | UInt32 | - | 1 | R |
| 4244 | 1 | Battery voltage regulation set point, temperature compensated | UInt16 | V | 0.1 | R |
| 4245 | 1 | Nominal battery voltage The document prints the valid values as 12 x 1 through 10 (120 V maximum, 250 V for the 250KS). Readable, seeded read-only: it changes the charging regime. | UInt16 | V | 1 | R |
| 4246 | 1 | Absorb ending amps Readable, and seeded read-only: writing it changes how the battery is charged, and the document's own disclaimer says a wrong charge voltage can damage a battery bank. | UInt16 | A | 0.1 | R |
| 4247 | 1 | Absorb ending state of charge Readable, and seeded read-only: writing it changes how the battery is charged, and the document's own disclaimer says a wrong charge voltage can damage a battery bank. | UInt16 | - | 1 | R |
| 4249 | 1 | Rebulk voltage Readable, and seeded read-only: writing it changes how the battery is charged, and the document's disclaimer says a wrong charge voltage can damage a battery bank. | UInt16 | V | 0.1 | R |
| 4250 | 1 | Battery monitor voltage The document prints no conversion or unit for this battery-monitor value (it is marked 'future SOC use'), so no scale is seeded. | UInt16 | - | 1 | R |
| 4251 | 1 | Battery monitor state of charge The document prints no conversion or unit for this battery-monitor value (it is marked 'future SOC use'), so no unit is seeded. | UInt16 | - | 1 | R |
| 4266 | 1 | Raw PV negative current Peak amps read from the A/D converter. The document's conversion cell prints [4266] amps while its note column prints '1 count = 0.1 amp'; the two disagree, so the conversion cell is followed here and the conflict recorded. | UInt16 | A | 1 | R |
| 4271 | 1 | Restart timer (latest) | UInt16 | ms | 1 | R |
| 4272 | 1 | Battery current Peak amps. | UInt16 | A | 0.1 | R |
| 4275 | 1 | Reason for resting Reason number, as printed. | UInt16 | - | 1 | R |
| 4276 | 1 | Output battery voltage Peak volts. The document's conversion cell cites register 4376 here while the register column prints 4276; the seed keeps 4276 and the 0.1 V scale, which is what the neighbouring battery-voltage rows use. | UInt16 | V | 0.1 | R |
| 4277 | 1 | Input PV voltage Peak volts. The document's conversion cell cites register 4377 while the register column prints 4277; the seed keeps 4277 and the 0.1 V scale, as for 4276. | UInt16 | V | 0.1 | R |
| 4283 | 1 | MPP voltage target | UInt16 | V | 0.1 | R |
| 4286 | 1 | Low watts threshold Readable, seeded read-only: writing it changes how the battery is charged, and the document's disclaimer says a wrong charge setting can damage a battery bank. The document's conversion cell cites register 4284 for this row while the register column prints 4286; the seed keeps 4286. | UInt16 | W | 1 | R |
| 4326 | 1 | Modbus address Valid range 0-255; the document prints the default as 10. | UInt16 | - | 1 | RW |
| 4365 | 2 | WhizBang Jr. positive amp hours Low word at 4365, high word at 4366. | UInt32 | Ah | 1 | R |
| 4367 | 2 | WhizBang Jr. negative amp hours Signed, as the document prints it; low word at 4367, high word at 4368. | Int32 | Ah | 1 | R |
| 4369 | 2 | WhizBang Jr. net amp hours Signed, as the document prints it; low word at 4369, high word at 4370. | Int32 | Ah | 1 | R |
| 4371 | 1 | WhizBang Jr. current The document lists 4371 as one register, scaled and rounded, signed to +-3276.7 A, so the row is a signed 16-bit value in 0.1 A units; 4372 is a different register (WhizBang CRC and temperature). | Int16 | A | 0.1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: MidNite Solar "MODBUS Network Spec.", vendor map at midnitesolar.com/firmware/classic_register_map_Rev-C5-December-8-2013.pdf (read 2026-11-23, SHA-256 08d2ca806bc95e982320648a1a0d721f8a2911e29f9223b894b4253a95f159c6); the file says Rev C5, the page headers say Rev C.4, Dec 9, 2013. Covers Classic 150/200/250/250KS per its unit-type table (150, 200, 250, 251 = 250KS); it prints no Lite code, so none is claimed. Addressing: the document says the map starts at register 4101 while the packet sends 4100, so the seed is one_based. Unit 10 is cited: register 4326 prints "Default address = 10". Transport: the Ethernet port carries Modbus over TCP/IP (MAC and Ethernet config registers, a TCP/IP advertise flag) and register 4137 prints the port, range 0-65535, default 502; RS-232 is 19.2K 8N1. Word order is LowFirst: every 32-bit row prints its low word first, (([4110] << 16) + [4109]) and likewise 4111/4112, 4126/4127, 4128/4129, 4130/4131, 4240/4241 and 4365-4370. The map has no signedness column: temperatures 4132-4134 are Int16 (a battery sensor reads below zero) and the WhizBang amp-hour rows are Int32 where the notes say (signed). Seeded: telemetry 4101-4135 and 4138-4152, battery-monitor and MPPT rows 4244-4251, 4266, 4271-4277, 4283 and 4286, and WhizBang 4365-4371. WRITES: only 4136 (log interval), 4137 (Modbus port) and 4326 (Modbus address). Every row that changes charging is present but READ-ONLY (4139, 4143, 4148-4151, 4157, 4162, 4163, 4166, 4204, 4245-4247, 4249, 4286), because the disclaimer says no write protection is enforced and a wrong charge voltage can damage a battery bank. Not seeded: calibration, reserved and internal blocks (including the resting references 4294/4295, printed with no conversion), wind and hydro tables, aux-relay blocks, log-selection rows, TCP counters and MAC words. Three conversion cells cite the wrong register (4276/4277 print 4376/4377, 4286 prints 4284); the register column is kept and the typo recorded on those rows.