SmartLink PLC / SmartLink Plus battery gateway (MG LFP battery bank Modbus TCP interface) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
123
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
1002
Product ID
SmartLink PLC = 0x520D0001
UInt32-1R
10210
Product name
20 characters ending with '\0'
Ascii-1R
1302
Serial number
Shown in hex format
UInt32-1R
1321
Hardware type
SmartLink PLC = 21005
UInt16-1R
1331
Smartlink PLC application firmware version
MAJOR=value >> 10; MINOR=value;
UInt16-1R
1341
SmartLink MX application firmware version
MAJOR=value >> 10; MINOR=value;
UInt16-1R
2241
Battery capacity
System capacity of the active systems.
UInt16-1R
2351
Combined control state
See Register 235 details
UInt16-1R
2592
Voltage
Int32V0.001R
2611
Current
Int16A0.1R
2621
Temperature
Int16°C0.1R
2661
State-Of-Charge (SOC)
UInt16%0.1R
2681
Minimum cell temperature
Range: -3276.8 to 3276.7
Int16°C0.1R
2691
Maximum cell temperature
Range: -3276.8 to 3276.7
Int16°C0.1R
2701
Minimum cell voltage
Range: 0 to 655.35
UInt16V0.01R
2711
Maximum cell voltage
Range: 0 to 655.35
UInt16V0.01R
3051
Battery limit charge voltage
UInt16V0.1R
3061
Battery limit charge current
UInt16A0.1R
3071
Battery limit discharge voltage
UInt16V0.1R
3081
Battery limit discharge current
UInt16A0.1R
4002
Hist.Cumulative AH
Not implemented yet.
Int32Ah0.1R
4022
Hist.Lowest Voltage
Not implemented yet.
Int32V0.01R
4042
Hist.Highest Voltage
Not implemented yet.
Int32V0.01R
4062
Hist.KWH out
Not implemented yet.
UInt32kWh0.01R
4082
Hist.KWH in
Not implemented yet.
UInt32kWh0.01R
4101
Hist.Highest temperature
Range: -3276.8 to 3276.7 | Not implemented yet.
Int16°C0.1R
4111
Hist.Lowest temperature
Range: -3276.8 to 3276.7 | Not implemented yet.
Int16°C0.1R
4121
Hist.Lowest cell Voltage
Range: 0 to 655.35 | Not implemented yet.
UInt16V0.01R
4131
Hist.Highest cell Voltage
Range: 0 to 655.35 | Not implemented yet.
UInt16V0.01R
5001
Alive counter
Range: 0 to 65535 | Increases every second. Note that invalid value is part of counter
UInt16-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: MG Energy Systems knowledge base, "Modbus TCP" application note with the "Modbus TCP/IP register list", revision V1.9, dated 15/04/2026 (SmartLink PLC version 1.7 or higher), vendor-hosted at https://docs.mgenergysystems.eu/application-notes/modbus-tcp. The page carries two register tables: the SmartLink Plus/PLC table (unit ID 123, the gateway that aggregates MG LFP batteries on the CAN bus) and a second table for the BMS units behind it, which answer on unit IDs 1-9 at the same input-register addresses. This seed is the SmartLink PLC map at unit ID 123, so only the first table is seeded; the connected-BMS values are the same addresses on a different unit ID. The SmartLink table's input registers are read-only and read with function code 04; its only holding register is 1000, the start/stop/reset command, read with 03 and written with 06. The document lists function codes 3, 4 and 6 and prints no port, so the seed uses the Modbus TCP default 502 with the document's default IP 192.168.1.10. The resolution column is the scale factor (0.001, 0.1, 0.01, 1), which is what the seed stores; the document's invalid-value convention (0xFFFF / 0x7FFF / 0x80000000) is recorded in the descriptions where it states one. Not seeded: every row the document types uint8 (one register: counters, module counts, state bytes and the 240-245 combine settings) or uint64 (four registers: the packed status, warning and failure bit words at 200/204/208/230 and the SmartLink PLC state at 150), because this schema has no 8-bit or 64-bit integer type; their bit-level detail is in the document's per-register detail sections. The "Product name" row is seeded as ASCII (10 registers, 20 characters) because the document types it char array(20).