Ventus / V200A-UMB ultrasonic wind sensor Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Identification
High byte = device subtype, low byte = software version.
UInt16-1R
11
Device status
A value other than 0 means the configuration storage could not be read or the device hit a serious problem during system start (contact OTT HydroMet with the code).
UInt16-1R
21
Sensor status 1
Four 4-bit sensor states: high byte high nibble = temperature buffer, high byte low nibble = temperature, low byte high nibble = air-pressure buffer, low byte low nibble = air pressure. 0 = OK, 1 = OK (alternate code), 2 = UNGLTG_KANAL, 3 = MEAS_ERROR, 4 = INIT_ERROR, 5 = VALUE_OVERFLOW, 6 = BUSY, 7 = other.
UInt16-1R
31
Sensor status 2
Same 4-bit coding: wind buffer, wind, then two unused nibbles.
UInt16-1R
91
Diagnostic: run time
Run time in 10-second steps.
UInt16-1R
101
Relative air pressure (actual)
Value x 0.1 (scaling factor 10).
Int16hPa0.1R
111
Relative air pressure (minimum)
Value x 0.1.
Int16hPa0.1R
121
Relative air pressure (maximum)
Value x 0.1.
Int16hPa0.1R
131
Relative air pressure (average)
Value x 0.1.
Int16hPa0.1R
141
Wind direction (actual)
Value x 0.1 degrees.
Int16°0.1R
151
Wind direction (minimum)
Value x 0.1 degrees.
Int16°0.1R
161
Wind direction (maximum)
Value x 0.1 degrees.
Int16°0.1R
171
Wind direction (vector average)
Value x 0.1 degrees.
Int16°0.1R
181
Wind measurement quality
Scaling factor 1; the document's scaling column marks the row signed (s), so it is read as a signed 16-bit value.
Int16-1R
191
Air temperature (actual)
Signed value x 0.1.
Int16°C0.1R
201
Air temperature (minimum)
Signed value x 0.1.
Int16°C0.1R
211
Air temperature (maximum)
Signed value x 0.1.
Int16°C0.1R
221
Air temperature (average)
Signed value x 0.1.
Int16°C0.1R
231
Heating temperature, top
Signed value x 0.1.
Int16°C0.1R
241
Heating temperature, bottom
Signed value x 0.1.
Int16°C0.1R
251
Wind speed (actual)
Value x 0.1 m/s.
Int16m/s0.1R
261
Wind speed (minimum)
Value x 0.1 m/s.
Int16m/s0.1R
271
Wind speed (maximum)
Value x 0.1 m/s.
Int16m/s0.1R
281
Wind speed (average)
Value x 0.1 m/s.
Int16m/s0.1R
291
Wind speed (vector average)
Scaling factor 1 (the document's only 1:1 wind-speed row).
Int16m/s1R
301
Air temperature (actual)
Imperial block. Signed value x 0.1.
Int16°F0.1R
311
Air temperature (minimum)
Imperial block. Signed value x 0.1.
Int16°F0.1R
321
Air temperature (maximum)
Imperial block. Signed value x 0.1.
Int16°F0.1R
331
Air temperature (average)
Imperial block. Signed value x 0.1.
Int16°F0.1R
341
Heating temperature, top
Imperial block. Signed value x 0.1.
Int16°F0.1R
351
Heating temperature, bottom
Imperial block. Signed value x 0.1.
Int16°F0.1R
361
Wind speed (actual)
Imperial block. Value x 0.1.
Int16mph0.1R
371
Wind speed (minimum)
Imperial block. Value x 0.1.
Int16mph0.1R
381
Wind speed (maximum)
Imperial block. Value x 0.1.
Int16mph0.1R
391
Wind speed (average)
Imperial block. Value x 0.1.
Int16mph0.1R
401
Wind speed (vector average)
Imperial block. Value x 0.1.
Int16mph0.1R
411
Absolute air pressure (actual)
Value x 0.1.
Int16hPa0.1R
421
Absolute air pressure (minimum)
Value x 0.1.
Int16hPa0.1R
431
Absolute air pressure (maximum)
Value x 0.1.
Int16hPa0.1R
441
Absolute air pressure (average)
Value x 0.1.
Int16hPa0.1R
451
Wind speed (actual)
Value x 0.1.
Int16km/h0.1R
461
Wind speed (minimum)
Value x 0.1.
Int16km/h0.1R
471
Wind speed (maximum)
Value x 0.1.
Int16km/h0.1R
481
Wind speed (average)
Value x 0.1.
Int16km/h0.1R
491
Wind speed (vector average)
Value x 0.1.
Int16km/h0.1R
501
Wind speed (actual)
Value x 0.1.
Int16kts0.1R
511
Wind speed (minimum)
Value x 0.1.
Int16kts0.1R
521
Wind speed (maximum)
Value x 0.1.
Int16kts0.1R
531
Wind speed (average)
Value x 0.1.
Int16kts0.1R
541
Wind speed (vector average)
Value x 0.1.
Int16kts0.1R
551
Air density (actual)
Scaling factor 1000, unsigned, so the scale factor here is 0.001.
UInt16kg/m³0.001R
561
Wind gust speed
Value x 0.1.
Int16m/s0.1R
571
Wind gust direction
Value x 0.1 degrees.
Int16°0.1R
581
Wind gust speed
Value x 0.1.
Int16km/h0.1R
591
Wind gust speed
Value x 0.1.
Int16mph0.1R
601
Wind gust speed
Value x 0.1. Registers 61-124 are reserved.
Int16kts0.1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: OTT HydroMet Fellbach GmbH (Lufft) 'Ventus Ultrasonic Wind Sensor - Operational Manual', document 48.7230-Vent-EN, revision V31 (07/2024), chapter 8.2.1 'Factory settings', chapter 10 'Commissioning for MODBUS format' (10.1-10.8) and the technical specification in chapter 13; hosted by OTT HydroMet's Hach document CDN at https://cdn.hach.com/1XMCM0ZF/at/59sk8hp6b7rv7jcf98g8c5q/Operational_Manual_Ultrasonic_Wind_Sensor_Ventus_final.pdf (SHA-256 25be55f7f1fe31054887901dde4446973ebee15eae729e6ecfea86cc79e86a22). Factory settings from 8.2.1: device ID 1, 19200 baud, data format 8N1. Chapter 10.2 states that selecting MODBUS-RTU preselects 19200 baud and even parity and that the interface can be set to 8E1, 8N1 or 8N2; this seed stores the preselected 19200 8E1 frame with the factory device ID 1 (the Modbus address is the UMB device ID, 10.3). The device also ships in UMB binary protocol, so Modbus must be selected in ConfigTool.NET before the map below is served. Addressing: the register table prints 'Register number' and 'Register address' side by side with address = number - 1, and the measurement values are input registers 0-124 read with function 04, so the seed is zero_based. All values are 16-bit integers scaled to fit one register (the manual deliberately does not use register pairs); the scaling factor column gives the divisor, so the scale factors here are 1/factor. The scaling column also marks each row s (signed) or u (unsigned): s rows are seeded as Int16, and the one u row (air density) as UInt16. 65535 and 32767 mean the value is erroneous or unavailable, and the sensor-status registers 2 and 3 carry the 4-bit status codes. The metric block, the imperial block and the km/h and knots blocks are kept together because each one is a documented row of the same table, although one unit system is enough for a given site. Holding registers 0-2 are the only writable parameters the manual documents; rows 61-124 are reserved.