Lufft (OTT HydroMet) · Sensor
Ventus / V200A-UMB ultrasonic wind sensor Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 19200
- Parity
- Even
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 0 | 1 | Identification High byte = device subtype, low byte = software version. | UInt16 | - | 1 | R |
| 1 | 1 | Device status A value other than 0 means the configuration storage could not be read or the device hit a serious problem during system start (contact OTT HydroMet with the code). | UInt16 | - | 1 | R |
| 2 | 1 | Sensor status 1 Four 4-bit sensor states: high byte high nibble = temperature buffer, high byte low nibble = temperature, low byte high nibble = air-pressure buffer, low byte low nibble = air pressure. 0 = OK, 1 = OK (alternate code), 2 = UNGLTG_KANAL, 3 = MEAS_ERROR, 4 = INIT_ERROR, 5 = VALUE_OVERFLOW, 6 = BUSY, 7 = other. | UInt16 | - | 1 | R |
| 3 | 1 | Sensor status 2 Same 4-bit coding: wind buffer, wind, then two unused nibbles. | UInt16 | - | 1 | R |
| 9 | 1 | Diagnostic: run time Run time in 10-second steps. | UInt16 | - | 1 | R |
| 10 | 1 | Relative air pressure (actual) Value x 0.1 (scaling factor 10). | Int16 | hPa | 0.1 | R |
| 11 | 1 | Relative air pressure (minimum) Value x 0.1. | Int16 | hPa | 0.1 | R |
| 12 | 1 | Relative air pressure (maximum) Value x 0.1. | Int16 | hPa | 0.1 | R |
| 13 | 1 | Relative air pressure (average) Value x 0.1. | Int16 | hPa | 0.1 | R |
| 14 | 1 | Wind direction (actual) Value x 0.1 degrees. | Int16 | ° | 0.1 | R |
| 15 | 1 | Wind direction (minimum) Value x 0.1 degrees. | Int16 | ° | 0.1 | R |
| 16 | 1 | Wind direction (maximum) Value x 0.1 degrees. | Int16 | ° | 0.1 | R |
| 17 | 1 | Wind direction (vector average) Value x 0.1 degrees. | Int16 | ° | 0.1 | R |
| 18 | 1 | Wind measurement quality Scaling factor 1; the document's scaling column marks the row signed (s), so it is read as a signed 16-bit value. | Int16 | - | 1 | R |
| 19 | 1 | Air temperature (actual) Signed value x 0.1. | Int16 | °C | 0.1 | R |
| 20 | 1 | Air temperature (minimum) Signed value x 0.1. | Int16 | °C | 0.1 | R |
| 21 | 1 | Air temperature (maximum) Signed value x 0.1. | Int16 | °C | 0.1 | R |
| 22 | 1 | Air temperature (average) Signed value x 0.1. | Int16 | °C | 0.1 | R |
| 23 | 1 | Heating temperature, top Signed value x 0.1. | Int16 | °C | 0.1 | R |
| 24 | 1 | Heating temperature, bottom Signed value x 0.1. | Int16 | °C | 0.1 | R |
| 25 | 1 | Wind speed (actual) Value x 0.1 m/s. | Int16 | m/s | 0.1 | R |
| 26 | 1 | Wind speed (minimum) Value x 0.1 m/s. | Int16 | m/s | 0.1 | R |
| 27 | 1 | Wind speed (maximum) Value x 0.1 m/s. | Int16 | m/s | 0.1 | R |
| 28 | 1 | Wind speed (average) Value x 0.1 m/s. | Int16 | m/s | 0.1 | R |
| 29 | 1 | Wind speed (vector average) Scaling factor 1 (the document's only 1:1 wind-speed row). | Int16 | m/s | 1 | R |
| 30 | 1 | Air temperature (actual) Imperial block. Signed value x 0.1. | Int16 | °F | 0.1 | R |
| 31 | 1 | Air temperature (minimum) Imperial block. Signed value x 0.1. | Int16 | °F | 0.1 | R |
| 32 | 1 | Air temperature (maximum) Imperial block. Signed value x 0.1. | Int16 | °F | 0.1 | R |
| 33 | 1 | Air temperature (average) Imperial block. Signed value x 0.1. | Int16 | °F | 0.1 | R |
| 34 | 1 | Heating temperature, top Imperial block. Signed value x 0.1. | Int16 | °F | 0.1 | R |
| 35 | 1 | Heating temperature, bottom Imperial block. Signed value x 0.1. | Int16 | °F | 0.1 | R |
| 36 | 1 | Wind speed (actual) Imperial block. Value x 0.1. | Int16 | mph | 0.1 | R |
| 37 | 1 | Wind speed (minimum) Imperial block. Value x 0.1. | Int16 | mph | 0.1 | R |
| 38 | 1 | Wind speed (maximum) Imperial block. Value x 0.1. | Int16 | mph | 0.1 | R |
| 39 | 1 | Wind speed (average) Imperial block. Value x 0.1. | Int16 | mph | 0.1 | R |
| 40 | 1 | Wind speed (vector average) Imperial block. Value x 0.1. | Int16 | mph | 0.1 | R |
| 41 | 1 | Absolute air pressure (actual) Value x 0.1. | Int16 | hPa | 0.1 | R |
| 42 | 1 | Absolute air pressure (minimum) Value x 0.1. | Int16 | hPa | 0.1 | R |
| 43 | 1 | Absolute air pressure (maximum) Value x 0.1. | Int16 | hPa | 0.1 | R |
| 44 | 1 | Absolute air pressure (average) Value x 0.1. | Int16 | hPa | 0.1 | R |
| 45 | 1 | Wind speed (actual) Value x 0.1. | Int16 | km/h | 0.1 | R |
| 46 | 1 | Wind speed (minimum) Value x 0.1. | Int16 | km/h | 0.1 | R |
| 47 | 1 | Wind speed (maximum) Value x 0.1. | Int16 | km/h | 0.1 | R |
| 48 | 1 | Wind speed (average) Value x 0.1. | Int16 | km/h | 0.1 | R |
| 49 | 1 | Wind speed (vector average) Value x 0.1. | Int16 | km/h | 0.1 | R |
| 50 | 1 | Wind speed (actual) Value x 0.1. | Int16 | kts | 0.1 | R |
| 51 | 1 | Wind speed (minimum) Value x 0.1. | Int16 | kts | 0.1 | R |
| 52 | 1 | Wind speed (maximum) Value x 0.1. | Int16 | kts | 0.1 | R |
| 53 | 1 | Wind speed (average) Value x 0.1. | Int16 | kts | 0.1 | R |
| 54 | 1 | Wind speed (vector average) Value x 0.1. | Int16 | kts | 0.1 | R |
| 55 | 1 | Air density (actual) Scaling factor 1000, unsigned, so the scale factor here is 0.001. | UInt16 | kg/m³ | 0.001 | R |
| 56 | 1 | Wind gust speed Value x 0.1. | Int16 | m/s | 0.1 | R |
| 57 | 1 | Wind gust direction Value x 0.1 degrees. | Int16 | ° | 0.1 | R |
| 58 | 1 | Wind gust speed Value x 0.1. | Int16 | km/h | 0.1 | R |
| 59 | 1 | Wind gust speed Value x 0.1. | Int16 | mph | 0.1 | R |
| 60 | 1 | Wind gust speed Value x 0.1. Registers 61-124 are reserved. | Int16 | kts | 0.1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: OTT HydroMet Fellbach GmbH (Lufft) 'Ventus Ultrasonic Wind Sensor - Operational Manual', document 48.7230-Vent-EN, revision V31 (07/2024), chapter 8.2.1 'Factory settings', chapter 10 'Commissioning for MODBUS format' (10.1-10.8) and the technical specification in chapter 13; hosted by OTT HydroMet's Hach document CDN at https://cdn.hach.com/1XMCM0ZF/at/59sk8hp6b7rv7jcf98g8c5q/Operational_Manual_Ultrasonic_Wind_Sensor_Ventus_final.pdf (SHA-256 25be55f7f1fe31054887901dde4446973ebee15eae729e6ecfea86cc79e86a22). Factory settings from 8.2.1: device ID 1, 19200 baud, data format 8N1. Chapter 10.2 states that selecting MODBUS-RTU preselects 19200 baud and even parity and that the interface can be set to 8E1, 8N1 or 8N2; this seed stores the preselected 19200 8E1 frame with the factory device ID 1 (the Modbus address is the UMB device ID, 10.3). The device also ships in UMB binary protocol, so Modbus must be selected in ConfigTool.NET before the map below is served. Addressing: the register table prints 'Register number' and 'Register address' side by side with address = number - 1, and the measurement values are input registers 0-124 read with function 04, so the seed is zero_based. All values are 16-bit integers scaled to fit one register (the manual deliberately does not use register pairs); the scaling factor column gives the divisor, so the scale factors here are 1/factor. The scaling column also marks each row s (signed) or u (unsigned): s rows are seeded as Int16, and the one u row (air density) as UInt16. 65535 and 32767 mean the value is erroneous or unavailable, and the sensor-status registers 2 and 3 carry the 4-bit status codes. The metric block, the imperial block and the km/h and knots blocks are kept together because each one is a documented row of the same table, although one unit system is enough for a given site. Holding registers 0-2 are the only writable parameters the manual documents; rows 61-124 are reserved.