KSE series hybrid (energy-storage) inverters Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
30001
PV1 Input Vlot
UInt16V0.1R
30011
PV2 Input Vlot
UInt16V0.1R
30121
PV1 Input Curr
Int16A0.01R
30131
PV2 Input Curr
Int16A0.01R
30241
PV1 Input Power
Int16W1R
30251
PV2 Input Power
Int16W1R
30361
Day Energy (PV)
UInt16kWh0.1R
30372
Month Energy (PV)
4-byte value printed as a high word at 3037 and a low word at 3038, in the 04H input table.
UInt32kWh1R
30392
Year Energy (PV)
4-byte value printed as a high word at 3039 and a low word at 3040, in the 04H input table.
UInt32kWh1R
30412
Total Energy (PV)
4-byte value printed as a high word at 3041 and a low word at 3042, in the 04H input table.
UInt32kWh0.1R
30492
DSP alarm code
4-byte value printed as a high word at 3049 and a low word at 3050, in the 04H input table.
UInt32-1R
30512
DSP error code
4-byte value printed as a high word at 3051 and a low word at 3052, in the 04H input table.
UInt32-1R
30531
BUS Volt
UInt16V0.1R
30541
DCBUS Vlot
UInt16V0.1R
30551
INV radiator temp
Int16°C0.1R
30561
BAT radiator temp
Int16°C0.1R
30571
Inside environment
Int16°C0.1R
30631
BAT Volt
UInt16V0.01R
30641
BAT Current
Int16A0.1R
30651
BAT CHG/DISCHG Power
Int16W1R
30661
BAT_SOC
UInt16%0.1R
30671
BAT_Temp
Int16°C0.1R
30691
BAT_CHG_VOLT
UInt16V0.1R
30701
BAT_CHG_LIMIT_CURR
UInt16A1R
30711
BAT_DISCHG_LIMIT_CURR
UInt16A1R
30971
R Phase Grid Volt
UInt16V0.1R
30981
R Phase Grid Freq
UInt16Hz0.01R
30991
R Phase Meter Curr
Int16A0.001R
31001
R Phase Meter Power
Int16W1R
31011
S Phase Grid Volt
UInt16V0.1R
31021
S Phase Grid Freq
UInt16Hz0.01R
31031
S Phase Meter Curr
Int16A0.001R
31041
S Phase Meter Power
Int16W1R
31051
T Phase Grid Volt
UInt16V0.1R
31061
T Phase Grid Freq
UInt16Hz0.01R
31071
T Phase Meter Curr
Int16A0.001R
31081
T Phase Meter Power
Int16W1R
31091
Day Energy (BUY)
UInt16kWh0.1R
31102
Month Energy (BUY)
4-byte value, high word at 3110, low word at 3111.
UInt32kWh1R
31122
Year Energy (BUY)
4-byte value, high word at 3112, low word at 3113.
UInt32kWh1R
31142
Total Energy (BUY)
4-byte value, high word at 3114, low word at 3115.
UInt32kWh0.1R
31161
Day Energy (SELL)
UInt16kWh0.1R
31172
Month Energy (SELL)
4-byte value, high word at 3117, low word at 3118.
UInt32kWh1R
31192
Year Energy (SELL)
4-byte value, high word at 3119, low word at 3120.
UInt32kWh1R
31212
Total Energy (SELL)
4-byte value printed as a high word at 3121 and a low word at 3122, in the 04H input table.
UInt32kWh0.1R
31231
R-INV_Vlot
UInt16V0.1R
31241
R-INV_Curr
Int16A0.01R
31251
R-INV_Freq
UInt16Hz0.01R
31261
R-INV_Power
Int16W1R
31271
S-INV_Vlot
UInt16V0.1R
31281
S-INV_Curr
Int16A0.01R
31291
S-INV_Freq
UInt16Hz0.01R
31301
S-INV_Power
Int16W1R
31311
T-INV_Vlot
UInt16V0.1R
31321
T-INV_Curr
Int16A0.01R
31331
T-INV_Freq
UInt16Hz0.01R
31341
T-INV_Power
Int16W1R
31351
R-BackUp Volt
UInt16V0.1R
31361
R-BackUp Curr
UInt16A0.01R
31371
R-BackUp Power
UInt16W1R
31381
S-BackUp Volt
UInt16V0.1R
31391
S-BackUp Curr
UInt16A0.01R
31401
S-BackUp Power
UInt16W1R
31411
T-BackUp Volt
UInt16V0.1R
31421
T-BackUp Curr
UInt16A0.01R
31431
T-BackUp Power
UInt16W1R
31441
R-Load Power
UInt16W1R
31451
S-Load Power
UInt16W1R
31461
T-Load Power
Printed only for the three-phase models.
UInt16W1R
31471
Day Energy (LOAD)
UInt16kWh0.1R
31482
Month Energy (LOAD)
4-byte value, high word at 3148, low word at 3149.
UInt32kWh1R
31502
Year Energy ( LOAD)
UInt32kWh1R
31522
Total Energy (LOAD)
4-byte value, high word at 3152, low word at 3153.
UInt32kWh0.1R
31542
On-grid count
4-byte counter, high word at 3154, low word at 3155; the document prints no unit or scale.
UInt32-1R
31561
PV Temperature
Int16°C0.1R
31571
LLC Temperature
Int16°C0.1R
31871
Remote off state
0 = normal, 1 = off state.
UInt16-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

KSTAR 'Hybrid Inverter MODBUS RS485 Communication Protocol V2.9.1' (document SFT-KSE-001 /A/0, issue 2024-07-21, 46 pages, headed Shenzhen Kstar Science & Technology Co.,LTD.) for the KSE hybrid (energy-storage) series. The vendor does not serve it publicly, so the copy read is the vendor file mirrored at https://github.com/user-attachments/files/17555061/KSTAR.Hybrid.Inverter.Modbus.V2.9.1_2024.07.21.pdf, SHA-256 02d9357b8f3571808f9898f0aafee711c798e34d9cef3291d17baeb7cb1754a9, retrieved 2026-11-23 (MIRROR-SOURCED). Frame, section 1.2: RS-485, 1 start bit, 8 data bits, 1 stop bit, no parity, default 9600 bps (2400/4800/9600 selectable), big-endian. Slave addresses 0-32 with 0 broadcast and no factory address printed, so unit 1 is a placeholder. Addressing: the worked frames send register 3000 as 0B B8 and 3200 as 0C 80, so the printed numbers are wire addresses (zero_based); HighFirst follows the document's big-endian statement (0x12345678 sent 12 34 56 78). This is the first tranche of the map, not the whole document: seeded are the rows of the 04H table from 3000 to 3194 whose line prints a byte count and a data type that agree (2 bytes = U16/S16, 4 bytes = U32/S32), each 32-bit row merged only when the following address is start+1. 77 rows, 0 byte/type disagreements, all input registers - the document gives every one of them function 04H, so none belongs in the holding area. Left out: the 04H/06H rows (settings, writable), Reserved rows, the ASCII and time blocks, the state words 3045-3048 whose value tables 3.1.4/3.1.5/3.1.10/3.1.11 do not pair cleanly in the extract, BAT Type 3062 and BAT Health 3075 (no code list, no byte count), and everything from about 3200 up, where the columns change order. Different map from the seeded kstar-ksg1-60k string inverters. No hardware test is claimed.