SMP series pyranometers (SMP3 / SMP6 / SMP10 / SMP12) Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Device type
UInt16-1R
11
Object data model version
UInt16-1R
21
Operational mode
Normal, service, calibration or factory mode.
UInt16-1R
31
Status flags
UInt16-1R
41
Scale factor for sensor data
Sets the number of decimal places of the sensor data registers.
Int16-1R
51
Temperature compensated radiation
Sensor 1 (short wave radiation; net radiation on the SGR). The decimal point is set by the scale factor register 4.
Int16W/m²1R
61
Raw non-linearised radiation
Raw, non-linearised and non-temperature compensated radiation.
Int16W/m²1R
71
Standard deviation of radiation
Standard deviation of the radiation over the last period, in 0.1 W/m2 (value = register / 10).
Int16W/m²0.1R
81
Body temperature
Int16°C0.1R
91
External power voltage
External voltage at the chassis socket in 0.1 V (value = register / 10).
Int16V0.1R
182
ADC counts, radiation sensor
Input voltage of sensor 1 in V (registers 18 MSB and 19 LSB).
Int32-0.01R
222
ADC counts, body temperature sensor
Input voltage of the body temperature sensor in V.
Int32-0.01R
242
ADC counts, power sensor
Input voltage of the power sensor in V.
Int32-0.01R
261
Error code
Most recent / actual error code.
UInt16-1R
271
Protocol error
UInt16-1R
281
Priority 1 error count
UInt16-1R
291
Priority 2 error count
UInt16-1R
301
Restart count
Number of controlled restarts.
UInt16-1R
311
False start count
Number of uncontrolled restarts.
UInt16-1R
321
Sensor on time, MSB
On time in seconds, high word.
UInt16s1R
331
Sensor on time, LSB
On time in seconds, low word.
UInt16s1R
411
Production batch number
Year of production in YY.
UInt16-1R
421
Serial number
UInt16-1R
431
Software version
UInt16-1R
441
Hardware version
UInt16-1R
451
Node ID
Modbus device address on RS-485.
UInt16-1R
100062
Radiation (floating point)
Temperature compensated radiation with the decimal point set by the scale factor (register 4 / holding register 34).
Float32W/m²1R
100082
Standard deviation of radiation (floating point)
Float32W/m²1R
100102
Long wave down radiation (floating point)
SGR only.
Float32W/m²1R
100142
Body temperature (floating point)
Float32K1R
100162
External power voltage (floating point)
Float32V1R
100182
PV panel temperature (floating point)
DustIQ and RT1 only.
Float32K1R
100202
Tilt of the sensor (floating point)
Tilt of the sensor in degrees (manual name FL_TILT).
Float32°1R
100222
Internal relative humidity (floating point)
Internal relative humidity of the instrument in % (manual name FL_RH).
Float32%1R

Notes

RS-485 device: reach it through a Modbus RTU-to-TCP gateway using the factory serial settings above (address 1, 19200 bps, 8 data bits, even parity, 1 stop bit). Source: Kipp & Zonen 'SMP series smart pyranometer' manual SO-KZ-RE-mn-SMP_Series-EN-GL-231130 (30.11.2023), freely downloadable from https://cdn.hach.com/1XMCM0ZF/at/5jt5827v32k5c74ncf4vg8/SO-KZ-RE-mn-SMP_Series-EN-GL-231130.pdf: chapter 15.2 'Input registers overview' (printed pages 36-39) for the integer registers and for the 'Real time floating data points' block starting at PDU address 10000 (page 38), chapter 15.3 for holding register 34, chapter 15.5/15.6 for the 0.1 V / 0.1 degC / 0.1 W/m2 scaling of the integer registers, and chapter 8.1 for the factory communication settings. The PDU addresses in those tables are the wire addresses used here. The instruments do not distinguish holding from input registers, so read-only values are also available with function code 03. Radiation is reported in W/m2 but its number of decimals is set by the scale factor register (input register 4 / holding register 34); the scale factors here assume the common factory scale factor 0. In the cited 2023 edition, registers 15/16 of the integer table are SMP12-only (0.1 ° / 0.1 %), so they are not modelled; the floating-point tilt and humidity values (FL_TILT 10020, FL_RH 10022) are documented for every SMP model and are listed, while the SMP12-only tilt roll/pitch pair (20000/20002) is left out.