KELLER Pressure · Pressure transmitter

X-Line pressure transmitters (series 33X / 35X / 36X / 39X, Class.Group 5.20 / 5.21 / 5.24) Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
02
CH0, calculated value (float)
Channel CH0 in the format selected by CFG_CH0 (0x0206), e.g. P1-P2, sqrt(P1) or |P1|. IEEE-754 big-endian: HWord at 0x0000, LWord at 0x0001.
Float32-1R
22
P1, pressure of sensor 1 (float)
Pressure of pressure port P1. The document's worked frame reads 0x3F75 0xF07B at 0x0002 = 0.960701 bar.
Float32bar1R
42
P2, pressure of sensor 2 (float)
Pressure of pressure port P2 (differential transmitters). The worked frame reads 0.961042 bar at 0x0004.
Float32bar1R
62
T, temperature (float)
Temperature measured by the transmitter's own temperature sensor.
Float32°C1R
82
TOB1, temperature of sensor P1 (float)
Temperature of the P1 pressure sensor. The worked frame reads 22.719 °C at 0x0008.
Float32°C1R
102
TOB2, temperature of sensor P2 (float)
Temperature of the P2 pressure sensor.
Float32°C1R
161
CH0, calculated value (int16)
Every value of this block is multiplied by 100 in the document, so the scale factor is 0.01.
Int16-0.01R
171
P1, pressure of sensor 1 (int16)
Value x 0.01 bar. The block is limited to +/-327 bar; use the 32-bit block at 0x0022 for a wider range.
Int16bar0.01R
181
P2, pressure of sensor 2 (int16)
Value x 0.01 bar.
Int16bar0.01R
191
T, temperature (int16)
Value x 0.01 °C.
Int16°C0.01R
201
TOB1, temperature of sensor P1 (int16)
Value x 0.01 °C.
Int16°C0.01R
211
TOB2, temperature of sensor P2 (int16)
Value x 0.01 °C.
Int16°C0.01R
322
CH0, calculated value (int32)
Unitless calculated channel; the device stores 10^-5 steps, so the scale factor is 0.00001. HWord at the lower address.
Int32-0.00001R
342
P1, pressure of sensor 1 (int32)
The document stores this block in pascal (10^-5 bar); the seed converts to bar so it matches the other pressure rows.
Int32bar0.00001R
362
P2, pressure of sensor 2 (int32)
Pascal block converted to bar (x 10^-5).
Int32bar0.00001R
382
T, temperature (int32)
Value x 0.01 °C.
Int32°C0.01R
402
TOB1, temperature of sensor P1 (int32)
Value x 0.01 °C.
Int32°C0.01R
422
TOB2, temperature of sensor P2 (int32)
Value x 0.01 °C.
Int32°C0.01R
5121
UART settings
UInt16-1RW
5131
FILTER_bck, factory filter setting
UInt16-1R
5141
Serial number, high bytes
UInt16-1R
5151
Serial number, low bytes
UInt16-1R
5161
CFG_P, active pressure channels
UInt16-1R
5171
CFG_T, active temperature channels
UInt16-1R
5181
CFG_CH0, calculated-channel mode
UInt16-1RW
5211
P-Mode, sensor type and calibration
UInt16-1R
5221
FILT_CTRL, filter control
UInt16-1RW
5231
DAC_CTRL, analogue output control
UInt16-1R
5241
STATUS, device status
UInt16-1R
5251
DEV_ADDR, device (slave) address
UInt16-1RW
5261
Class:Group, device class and group
UInt16-1R
5271
Year:Week, firmware date
UInt16-1R
5291
ConOn, conductivity power (CTD versions)
UInt16-1RW
5311
ConRange, conductivity range (CTD versions)
UInt16-1RW
5321
ConTempCompCoeff, conductivity temperature compensation
UInt16-1RW
5331
ModbusInterFrameTime9k6
UInt16-1RW
5341
ModbusInterFrameTime115k2
UInt16-1RW
8742
Square-root threshold (coefficient 53)
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Version 5.20 and 5.24.
Float32bar1RW
8962
P1 offset (coefficient 64)
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Default 0.0.
Float32bar1RW
8982
P1 gain factor (coefficient 65)
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Default 1.0.
Float32-1RW
9002
P2 offset (coefficient 66)
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Default 0.0.
Float32bar1RW
9022
P2 gain factor (coefficient 67)
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Default 1.0.
Float32-1RW
9042
Analogue output offset (coefficient 68)
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Version 5.20 and 5.24.
Float32bar1RW
9062
Analogue output gain factor (coefficient 69)
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Version 5.20 and 5.24.
Float32-1RW
9082
CH0 offset (coefficient 70)
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Default 0.0, version 5.20 and 5.24.
Float32-1RW
9102
CH0 gain factor (coefficient 71)
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Default 1.0, version 5.20 and 5.24.
Float32-1RW
9122
T offset (coefficient 72)
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Version 5.21 and 5.24.
Float32°C1RW
9162
TOB1 offset (coefficient 74)
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Version 5.21 and 5.24.
Float32°C1RW
9202
TOB2 offset (coefficient 76)
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Version 5.21 and 5.24.
Float32°C1RW
9282
Minimum pressure of sensor P1
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range.
Float32bar1R
9302
Maximum pressure of sensor P1
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range.
Float32bar1R
9322
Minimum pressure of sensor P2
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range.
Float32bar1R
9342
Maximum pressure of sensor P2
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range.
Float32bar1R
9362
Minimum temperature of the temperature sensor
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range.
Float32°C1R
9382
Maximum temperature of the temperature sensor
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range.
Float32°C1R
9402
Minimum temperature of sensor P1
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range.
Float32°C1R
9422
Maximum temperature of sensor P1
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range.
Float32°C1R
9442
Minimum temperature of sensor P2
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range.
Float32°C1R
9462
Maximum temperature of sensor P2
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range.
Float32°C1R
9482
Minimum value of channel CH0
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range.
Float32-1R
9502
Maximum value of channel CH0
IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range.
Float32-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: KELLER Pressure AG 'Communication Protocol - X-Line Pressure Transmitters', version 3.8 (01/2026), vendor-hosted PDF at https://download.keller-pressure.com/api/download/muQjLg2dGMJAbgLYSAHreT/en/latest.pdf (SHA-256 276759928ad1ef8470f164d9c277f85dc87bb929990111a28beeac4d26fc4e31), chapters 2 (physical layer), 4.1 (Modbus basics), 4.4 (register map) and 4.4.3 (configuration range). The document covers the X-Line CLASS 5 devices: GROUP 20 (X1, software 5.20-XX.XX), GROUP 21 (X2, 5.21-XX.XX) and GROUP 24 (X2P, 5.24-XX.XX), i.e. the digital pressure transmitters of series 33X, 35X, 36X and 39X. Factory frame from chapter 4.1: Modbus RTU, 9600 baud, 8 data bits, no parity, 1 stop bit, slave address 1 (chapter 4.1 'Bus Addressing' and register 0x020D 'default 1'). Addressing: the register map prints the wire address - P1 sits at 0x0002 and is read as 0x0002 in the worked frames - so the seed is zero_based. Byte and word order: 32-bit values are IEEE-754 big-endian with the high word at the lower address (the worked frame at 0x0002 returns 0x3F75 0xF07B = 0.960701 bar), hence BigEndian + HighFirst. Not seeded: the 0x0100 float mirror block (its channel/unit column is printed one row out of line in the PDF and it only repeats 0x0000-0x000B), the conductivity coefficients (5.21 CTD versions only), the 0x0207/0x0208 interval/filter registers, the 0x0223 samples-per-second row, the 0x0250-0x0257 ASCII serial number, the analogue-signal (0x03B8-0x03BE), accuracy (0x03D0-0x03DA), conductivity (0x03E0-0x03EC) and samples-per-second (0x03F0-0x03FA) coefficient rows (with the 0x3000-0x301F, 0x3200-0x3217 and 0x4070-0x408F customer and filter tables) and the 0xFF00-0xFF1A write-only zero-point command list (those frames pack a fixed command byte rather than a plain value). P2 and TOB2 only exist on differential models; registers 0x0204/0x0205 report which channels are active. The int32 block is stored in pascal by the device and is scaled to bar here (x 10^-5).