  "spec_version": 1,
  "slug": "keller-x-line-pressure-transmitters",
  "manufacturer": "KELLER Pressure",
  "model": "X-Line pressure transmitters (series 33X / 35X / 36X / 39X, Class.Group 5.20 / 5.21 / 5.24)",
  "category": "Pressure transmitter",
  "supplier_url": "https://keller-pressure.com/en/downloads",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 9600,
      "parity": "None",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [],
  "holding_registers": [
    {
      "address": 0,
      "count": 2,
      "name": "CH0, calculated value (float)",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Channel CH0 in the format selected by CFG_CH0 (0x0206), e.g. P1-P2, sqrt(P1) or |P1|. IEEE-754 big-endian: HWord at 0x0000, LWord at 0x0001."
    },
    {
      "address": 2,
      "count": 2,
      "name": "P1, pressure of sensor 1 (float)",
      "data_type": "Float32",
      "units": "bar",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Pressure of pressure port P1. The document's worked frame reads 0x3F75 0xF07B at 0x0002 = 0.960701 bar."
    },
    {
      "address": 4,
      "count": 2,
      "name": "P2, pressure of sensor 2 (float)",
      "data_type": "Float32",
      "units": "bar",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Pressure of pressure port P2 (differential transmitters). The worked frame reads 0.961042 bar at 0x0004."
    },
    {
      "address": 6,
      "count": 2,
      "name": "T, temperature (float)",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Temperature measured by the transmitter's own temperature sensor."
    },
    {
      "address": 8,
      "count": 2,
      "name": "TOB1, temperature of sensor P1 (float)",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Temperature of the P1 pressure sensor. The worked frame reads 22.719 °C at 0x0008."
    },
    {
      "address": 10,
      "count": 2,
      "name": "TOB2, temperature of sensor P2 (float)",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Temperature of the P2 pressure sensor."
    },
    {
      "address": 16,
      "count": 1,
      "name": "CH0, calculated value (int16)",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Every value of this block is multiplied by 100 in the document, so the scale factor is 0.01."
    },
    {
      "address": 17,
      "count": 1,
      "name": "P1, pressure of sensor 1 (int16)",
      "data_type": "Int16",
      "units": "bar",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Value x 0.01 bar. The block is limited to +/-327 bar; use the 32-bit block at 0x0022 for a wider range."
    },
    {
      "address": 18,
      "count": 1,
      "name": "P2, pressure of sensor 2 (int16)",
      "data_type": "Int16",
      "units": "bar",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Value x 0.01 bar."
    },
    {
      "address": 19,
      "count": 1,
      "name": "T, temperature (int16)",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Value x 0.01 °C."
    },
    {
      "address": 20,
      "count": 1,
      "name": "TOB1, temperature of sensor P1 (int16)",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Value x 0.01 °C."
    },
    {
      "address": 21,
      "count": 1,
      "name": "TOB2, temperature of sensor P2 (int16)",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Value x 0.01 °C."
    },
    {
      "address": 32,
      "count": 2,
      "name": "CH0, calculated value (int32)",
      "data_type": "Int32",
      "units": "",
      "scale_factor": 0.00001,
      "offset": 0,
      "access": "R",
      "description": "Unitless calculated channel; the device stores 10^-5 steps, so the scale factor is 0.00001. HWord at the lower address."
    },
    {
      "address": 34,
      "count": 2,
      "name": "P1, pressure of sensor 1 (int32)",
      "data_type": "Int32",
      "units": "bar",
      "scale_factor": 0.00001,
      "offset": 0,
      "access": "R",
      "description": "The document stores this block in pascal (10^-5 bar); the seed converts to bar so it matches the other pressure rows."
    },
    {
      "address": 36,
      "count": 2,
      "name": "P2, pressure of sensor 2 (int32)",
      "data_type": "Int32",
      "units": "bar",
      "scale_factor": 0.00001,
      "offset": 0,
      "access": "R",
      "description": "Pascal block converted to bar (x 10^-5)."
    },
    {
      "address": 38,
      "count": 2,
      "name": "T, temperature (int32)",
      "data_type": "Int32",
      "units": "°C",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Value x 0.01 °C."
    },
    {
      "address": 40,
      "count": 2,
      "name": "TOB1, temperature of sensor P1 (int32)",
      "data_type": "Int32",
      "units": "°C",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Value x 0.01 °C."
    },
    {
      "address": 42,
      "count": 2,
      "name": "TOB2, temperature of sensor P2 (int32)",
      "data_type": "Int32",
      "units": "°C",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Value x 0.01 °C."
    },
    {
      "address": 512,
      "count": 1,
      "name": "UART settings",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW"
    },
    {
      "address": 513,
      "count": 1,
      "name": "FILTER_bck, factory filter setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 514,
      "count": 1,
      "name": "Serial number, high bytes",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 515,
      "count": 1,
      "name": "Serial number, low bytes",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 516,
      "count": 1,
      "name": "CFG_P, active pressure channels",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 517,
      "count": 1,
      "name": "CFG_T, active temperature channels",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 518,
      "count": 1,
      "name": "CFG_CH0, calculated-channel mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW"
    },
    {
      "address": 521,
      "count": 1,
      "name": "P-Mode, sensor type and calibration",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 522,
      "count": 1,
      "name": "FILT_CTRL, filter control",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW"
    },
    {
      "address": 523,
      "count": 1,
      "name": "DAC_CTRL, analogue output control",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 524,
      "count": 1,
      "name": "STATUS, device status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 525,
      "count": 1,
      "name": "DEV_ADDR, device (slave) address",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW"
    },
    {
      "address": 526,
      "count": 1,
      "name": "Class:Group, device class and group",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 527,
      "count": 1,
      "name": "Year:Week, firmware date",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 529,
      "count": 1,
      "name": "ConOn, conductivity power (CTD versions)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW"
    },
    {
      "address": 531,
      "count": 1,
      "name": "ConRange, conductivity range (CTD versions)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW"
    },
    {
      "address": 532,
      "count": 1,
      "name": "ConTempCompCoeff, conductivity temperature compensation",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW"
    },
    {
      "address": 533,
      "count": 1,
      "name": "ModbusInterFrameTime9k6",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW"
    },
    {
      "address": 534,
      "count": 1,
      "name": "ModbusInterFrameTime115k2",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW"
    },
    {
      "address": 874,
      "count": 2,
      "name": "Square-root threshold (coefficient 53)",
      "data_type": "Float32",
      "units": "bar",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Version 5.20 and 5.24."
    },
    {
      "address": 896,
      "count": 2,
      "name": "P1 offset (coefficient 64)",
      "data_type": "Float32",
      "units": "bar",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Default 0.0."
    },
    {
      "address": 898,
      "count": 2,
      "name": "P1 gain factor (coefficient 65)",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Default 1.0."
    },
    {
      "address": 900,
      "count": 2,
      "name": "P2 offset (coefficient 66)",
      "data_type": "Float32",
      "units": "bar",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Default 0.0."
    },
    {
      "address": 902,
      "count": 2,
      "name": "P2 gain factor (coefficient 67)",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Default 1.0."
    },
    {
      "address": 904,
      "count": 2,
      "name": "Analogue output offset (coefficient 68)",
      "data_type": "Float32",
      "units": "bar",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Version 5.20 and 5.24."
    },
    {
      "address": 906,
      "count": 2,
      "name": "Analogue output gain factor (coefficient 69)",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Version 5.20 and 5.24."
    },
    {
      "address": 908,
      "count": 2,
      "name": "CH0 offset (coefficient 70)",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Default 0.0, version 5.20 and 5.24."
    },
    {
      "address": 910,
      "count": 2,
      "name": "CH0 gain factor (coefficient 71)",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Default 1.0, version 5.20 and 5.24."
    },
    {
      "address": 912,
      "count": 2,
      "name": "T offset (coefficient 72)",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Version 5.21 and 5.24."
    },
    {
      "address": 916,
      "count": 2,
      "name": "TOB1 offset (coefficient 74)",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Version 5.21 and 5.24."
    },
    {
      "address": 920,
      "count": 2,
      "name": "TOB2 offset (coefficient 76)",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Writing coefficients needs function 16 with more than one register. Version 5.21 and 5.24."
    },
    {
      "address": 928,
      "count": 2,
      "name": "Minimum pressure of sensor P1",
      "data_type": "Float32",
      "units": "bar",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range."
    },
    {
      "address": 930,
      "count": 2,
      "name": "Maximum pressure of sensor P1",
      "data_type": "Float32",
      "units": "bar",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range."
    },
    {
      "address": 932,
      "count": 2,
      "name": "Minimum pressure of sensor P2",
      "data_type": "Float32",
      "units": "bar",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range."
    },
    {
      "address": 934,
      "count": 2,
      "name": "Maximum pressure of sensor P2",
      "data_type": "Float32",
      "units": "bar",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range."
    },
    {
      "address": 936,
      "count": 2,
      "name": "Minimum temperature of the temperature sensor",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range."
    },
    {
      "address": 938,
      "count": 2,
      "name": "Maximum temperature of the temperature sensor",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range."
    },
    {
      "address": 940,
      "count": 2,
      "name": "Minimum temperature of sensor P1",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range."
    },
    {
      "address": 942,
      "count": 2,
      "name": "Maximum temperature of sensor P1",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range."
    },
    {
      "address": 944,
      "count": 2,
      "name": "Minimum temperature of sensor P2",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range."
    },
    {
      "address": 946,
      "count": 2,
      "name": "Maximum temperature of sensor P2",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range."
    },
    {
      "address": 948,
      "count": 2,
      "name": "Minimum value of channel CH0",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range."
    },
    {
      "address": 950,
      "count": 2,
      "name": "Maximum value of channel CH0",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IEEE-754 float, two registers with the high word first; reading coefficients requires an even number of registers. Read-only measurement range."
    }
  ],
  "combined_registers": [],
  "notes": "Source: KELLER Pressure AG 'Communication Protocol - X-Line Pressure Transmitters', version 3.8 (01/2026), vendor-hosted PDF at https://download.keller-pressure.com/api/download/muQjLg2dGMJAbgLYSAHreT/en/latest.pdf (SHA-256 276759928ad1ef8470f164d9c277f85dc87bb929990111a28beeac4d26fc4e31), chapters 2 (physical layer), 4.1 (Modbus basics), 4.4 (register map) and 4.4.3 (configuration range). The document covers the X-Line CLASS 5 devices: GROUP 20 (X1, software 5.20-XX.XX), GROUP 21 (X2, 5.21-XX.XX) and GROUP 24 (X2P, 5.24-XX.XX), i.e. the digital pressure transmitters of series 33X, 35X, 36X and 39X. Factory frame from chapter 4.1: Modbus RTU, 9600 baud, 8 data bits, no parity, 1 stop bit, slave address 1 (chapter 4.1 'Bus Addressing' and register 0x020D 'default 1'). Addressing: the register map prints the wire address - P1 sits at 0x0002 and is read as 0x0002 in the worked frames - so the seed is zero_based. Byte and word order: 32-bit values are IEEE-754 big-endian with the high word at the lower address (the worked frame at 0x0002 returns 0x3F75 0xF07B = 0.960701 bar), hence BigEndian + HighFirst. Not seeded: the 0x0100 float mirror block (its channel/unit column is printed one row out of line in the PDF and it only repeats 0x0000-0x000B), the conductivity coefficients (5.21 CTD versions only), the 0x0207/0x0208 interval/filter registers, the 0x0223 samples-per-second row, the 0x0250-0x0257 ASCII serial number, the analogue-signal (0x03B8-0x03BE), accuracy (0x03D0-0x03DA), conductivity (0x03E0-0x03EC) and samples-per-second (0x03F0-0x03FA) coefficient rows (with the 0x3000-0x301F, 0x3200-0x3217 and 0x4070-0x408F customer and filter tables) and the 0xFF00-0xFF1A write-only zero-point command list (those frames pack a fixed command byte rather than a plain value). P2 and TOB2 only exist on differential models; registers 0x0204/0x0205 report which channels are active. The int32 block is stored in pascal by the device and is scaled to bar here (x 10^-5)."
}