All devices

Janitza · Power analyzer

UMG 604 / UMG 604-PRO Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
190002
Voltage L1-N
Phase-to-neutral voltage, phase L1 (_G_ULN[0]).
Float32V1R
190022
Voltage L2-N
Float32V1R
190042
Voltage L3-N
Float32V1R
190062
Voltage L1-L2
Float32V1R
190082
Voltage L2-L3
Float32V1R
190102
Voltage L3-L1
Float32V1R
190122
Current L1
Float32A1R
190142
Current L2
Float32A1R
190162
Current L3
Float32A1R
190182
Neutral conductor current
Vector sum of the three phase currents (_G_I_SUM3).
Float32A1R
190202
Real power L1
Float32W1R
190222
Real power L2
Float32W1R
190242
Real power L3
Float32W1R
190262
Real power, sum L1-L3
Psum3 = P1 + P2 + P3.
Float32W1R
190282
Apparent power L1
Float32VA1R
190302
Apparent power L2
Float32VA1R
190322
Apparent power L3
Float32VA1R
190342
Apparent power, sum L1-L3
Float32VA1R
190362
Reactive power L1
Fundamental component.
Float32var1R
190382
Reactive power L2
Float32var1R
190402
Reactive power L3
Float32var1R
190422
Reactive power, sum L1-L3
Qsum3 = Q1 + Q2 + Q3 (fundamental component).
Float32var1R
190442
Cos phi L1
Displacement power factor of phase L1 (fundamental component).
Float32-1R
190462
Cos phi L2
Float32-1R
190482
Cos phi L3
Float32-1R
190502
Measured frequency
Float32Hz1R
190522
Rotating field
1 = right, 0 = none, -1 = left.
Float32-1R
190602
Real energy, sum L1-L3
Signed total real energy of all phases.
Float32Wh1R
190682
Real energy, sum L1-L3, consumed (rate 1)
Active energy drawn from the supply, tariff 1.
Float32Wh1R
190762
Real energy, sum L1-L3, delivered
Active energy fed back into the supply.
Float32Wh1R
190842
Apparent energy, sum L1-L3
Float32VAh1R
190922
Reactive energy, sum L1-L3
Fundamental component.
Float32varh1R
191102
THD voltage L1-N
Total harmonic distortion, phase-to-neutral voltage L1.
Float32%1R
191122
THD voltage L2-N
Float32%1R
191142
THD voltage L3-N
Float32%1R
191162
THD current L1
Float32%1R
191182
THD current L2
Float32%1R
191202
THD current L3
Float32%1R
196302
Average voltage L-N
(ULN1 + ULN2 + ULN3) / 3.
Float32V1R
196322
Average voltage L-L
(UL1-L2 + UL2-L3 + UL3-L1) / 3.
Float32V1R
196342
Average current
(IL1 + IL2 + IL3) / 3.
Float32A1R
196362
Total power factor
Average power factor (PF1 + PF2 + PF3) / 3.
Float32-1R
99731
Digital output 1 state
Digital output 1 (_DIGOUT_STAT[0]). Readable and writable.
Int16-1RW
99741
Digital output 2 state
Digital output 2 (_DIGOUT_STAT[1]). Readable and writable.
Int16-1RW
99751
Digital input 1 state
Int16-1R
99761
Digital input 2 state
Int16-1R
101762
Serial number
UInt32-1R
101782
Production number
UInt32-1R

Combined registers

  • Real energy, consumed minus delivered (calculated)Holding registers 19068 - Holding registers 19076 (Wh)Net metering value built from the two tariff-1 counters.

Notes

Addresses are the Modbus addresses in Janitza's UMG 604-PRO address list (document 1.033.026.f, firmware from 5.028) and are used as wire addresses. All measurement values in the 19000 range are IEEE 754 single precision (Float32) and are read with function code 03; the values are refreshed every 200 ms. Energy counters are single precision Floats in Wh/varh/VAh and are not rescaled by a transformer factor, so apply the CT/VT ratio yourself if the device is set up with instrument transformers. The length of the list is deliberately limited to the frequently used measurements: harmonics 3 to 63, min/max values, load profiles and the configuration registers in the 10000 range (nominal values, transformer ratios, Modbus settings) are documented in the same address list. Digital outputs are writable; everything else listed here is read-only.