Janitza · Power analyzer

UMG 96RM-E Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
190002
Voltage L1-N
Float32V1R
190022
Voltage L2-N
Float32V1R
190042
Voltage L3-N
Float32V1R
190062
Voltage L1-L2
Float32V1R
190082
Voltage L2-L3
Float32V1R
190102
Voltage L3-L1
Float32V1R
190122
Current I L1
Float32A1R
190142
Current I L2
Float32A1R
190162
Current I L3
Float32A1R
190182
Vector sum current IN (I1+I2+I3)
Float32A1R
190202
Real power P1 L1N
Float32W1R
190222
Real power P2 L2N
Float32W1R
190242
Real power P3 L3N
Float32W1R
190262
Real power sum Psum3
Float32W1R
190282
Apparent power S1 L1N
Float32VA1R
190302
Apparent power S2 L2N
Float32VA1R
190322
Apparent power S3 L3N
Float32VA1R
190342
Apparent power sum Ssum3
Float32VA1R
190362
Fundamental reactive power Q1 L1N
Float32var1R
190382
Fundamental reactive power Q2 L2N
Float32var1R
190402
Fundamental reactive power Q3 L3N
Float32var1R
190422
Fundamental reactive power sum Qsum3
Float32var1R
190442
cos phi UL1 IL1 (fundamental)
Float32-1R
190462
cos phi UL2 IL2 (fundamental)
Float32-1R
190482
cos phi UL3 IL3 (fundamental)
Float32-1R
190502
Measured frequency
Float32Hz1R
190522
Rotation field
1 = right, 0 = none, -1 = left.
Float32-1R
190542
Real energy L1
Float32Wh1R
190562
Real energy L2
Float32Wh1R
190582
Real energy L3
Float32Wh1R
190602
Real energy L1..L3
Float32Wh1R
190622
Real energy L1, consumed
Float32Wh1R
190642
Real energy L2, consumed
Float32Wh1R
190662
Real energy L3, consumed
Float32Wh1R
190682
Real energy L1..L3, consumed
Float32Wh1R
190702
Real energy L1, delivered
Float32Wh1R
190722
Real energy L2, delivered
Float32Wh1R
190742
Real energy L3, delivered
Float32Wh1R
190762
Real energy L1..L3, delivered
Float32Wh1R
190782
Apparent energy L1
Float32VAh1R
190802
Apparent energy L2
Float32VAh1R
190822
Apparent energy L3
Float32VAh1R
190842
Apparent energy L1..L3
Float32VAh1R
190862
Reactive energy L1
Float32varh1R
190882
Reactive energy L2
Float32varh1R
190902
Reactive energy L3
Float32varh1R
190922
Reactive energy L1..L3
Float32varh1R
190942
Reactive energy inductive L1
Float32varh1R
190962
Reactive energy inductive L2
Float32varh1R
190982
Reactive energy inductive L3
Float32varh1R
191002
Reactive energy inductive L1..L3
Float32varh1R
191022
Reactive energy capacitive L1
Float32varh1R
191042
Reactive energy capacitive L2
Float32varh1R
191062
Reactive energy capacitive L3
Float32varh1R
191082
Reactive energy capacitive L1..L3
Float32varh1R
191102
THD voltage L1-N
Float32%1R
191122
THD voltage L2-N
Float32%1R
191142
THD voltage L3-N
Float32%1R
191162
THD current L1
Float32%1R
191182
THD current L2
Float32%1R
191202
THD current L3
Float32%1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

The UMG 96RM-E has its own Ethernet interface, so it is read directly over Modbus TCP (port 502, slave address 1 by default). Every row is the "Frequently required readings" block of Janitza's "UMG 96RM-E - Modbus-address list and Formulary", document 1.040.085.8.o (07/2025, from firmware 3.01 / hardware release 104), published at https://assets.janitza.com/ce18jq9ih0x6/b80ca06dda38d37f864115/703a1d1d3014935a5c3327ed6b978d37/janitza-mal-umg96rme-en.pdf ; the addresses are used as wire addresses (the list itself says the Little-Endian variant is the same address + 32768, so this is the Big-Endian, high-byte-first layout). All values are IEEE-754 single precision floats read with function code 03 and refreshed every 200 ms. Float and integer measured values already include the set current/voltage transformer factors; the short (16-bit) block does not. The list is deliberately limited to the frequently used measurements plus THD: harmonics 2-63, minimum/maximum/mean values, drag indicators, limit-value monitoring, logos and the 10000/10002 configuration registers (transformer ratios, nominal values, Modbus settings) are documented in the same address list. Everything listed here is read-only.