HMS Networks (Intesis) · Lighting controller
Intesis Modbus Server - DALI gateway (1 and 2 DALI-channel versions) Modbus register map
Default configuration
- Protocol
- Modbus TCP
- Port
- 502
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 0 | 1 | DALI device 0 - ballast / lamp failure bit fields (ECG15-ECG0) Single-device block: address = 7000 x channel + 100 x short address + signal. This row is channel 0, short address 0, signal 0 and holds the failure bits of DALI ballasts 0-15; other short addresses repeat at +100, the second DALI channel at +7000. | UInt16 | - | 1 | R |
| 1 | 1 | DALI device 0 - ballast / lamp failure bit fields (ECG31-ECG16) Signal 1 of the same block. | UInt16 | - | 1 | R |
| 2 | 1 | DALI device 0 - ballast / lamp failure bit fields (ECG47-ECG32) Signal 2 of the same block. | UInt16 | - | 1 | R |
| 3 | 1 | DALI device 0 - ballast / lamp failure bit fields (ECG63-ECG48) Signal 3 of the same block. | UInt16 | - | 1 | R |
| 4 | 1 | DALI device 0 - update all ECG status 0 = update finished, 1 = trigger update. | UInt16 | - | 1 | RW |
| 5 | 1 | DALI device 0 - ballast status Bit flags: b7 power cycle, b6 missing short address, b5 reset state, b4 fade running, b3 ballast limit error, b2 lamp power on, b1 lamp failure, b0 ballast failure. | UInt16 | - | 1 | R |
| 6 | 1 | DALI device 0 - actual level Actual arc power level of the device, 0-100 %. | UInt16 | % | 1 | R |
| 7 | 1 | DALI device 0 - device type 0 fluorescent, 1 emergency, 2 discharge, 3 halogen, 4 incandescent, 5 digital signal, 6 LED, 7 switching, 8 colour control. | UInt16 | - | 1 | R |
| 8 | 1 | DALI device 0 - physical minimum level 0-100 %. | UInt16 | % | 1 | R |
| 9 | 1 | DALI device 0 - min level 0-100 %. | UInt16 | % | 1 | R |
| 10 | 1 | DALI device 0 - max level 0-100 %. | UInt16 | % | 1 | R |
| 11 | 1 | DALI device 0 - power-on level 0-100 %. | UInt16 | % | 1 | R |
| 12 | 1 | DALI device 0 - system failure level 0-100 %. | UInt16 | % | 1 | R |
| 13 | 1 | DALI device 0 - fade time DALI fade time value, 0-15. | UInt16 | - | 1 | R |
| 14 | 1 | DALI device 0 - fade rate DALI fade rate value, 1-15. | UInt16 | - | 1 | R |
| 15 | 1 | DALI device 0 - arc power level Writable arc power level, 0-100 %. | UInt16 | % | 1 | RW |
| 6400 | 1 | DALI group 0 - arc power level Group block: address = 7000 x line + 20 x group + (6400 + signal). This row is line 0, group 0, signal 6400; other groups repeat at +20, the second line at +7000. Range 0-100 %. | UInt16 | % | 1 | RW |
| 6401 | 1 | DALI group 0 - arc power off / on 0 = off, 1-100 %. | UInt16 | % | 1 | RW |
| 6402 | 1 | DALI group 0 - step down / up 0 = step down, 1 = step up. | UInt16 | - | 1 | RW |
| 6403 | 1 | DALI group 0 - recall min level 1 = recall min level (write-only trigger). | UInt16 | - | 1 | W |
| 6404 | 1 | DALI group 0 - recall max level 1 = recall max level (write-only trigger). | UInt16 | - | 1 | W |
| 6405 | 1 | DALI group 0 - go to scene Scene number, 0-15. | UInt16 | - | 1 | RW |
| 6406 | 1 | DALI group 0 - store current level as scene Scene number, 0-15. | UInt16 | - | 1 | RW |
| 6407 | 1 | DALI group 0 - clear / remove scene Scene number, 0-15. | UInt16 | - | 1 | RW |
| 6408 | 1 | DALI group 0 - set fade time 0-15. | UInt16 | - | 1 | RW |
| 6409 | 1 | DALI group 0 - set fade rate 1-15. | UInt16 | - | 1 | RW |
| 6410 | 1 | DALI group 0 - set min level 0-100 %. | UInt16 | % | 1 | RW |
| 6411 | 1 | DALI group 0 - set max level 0-100 %. | UInt16 | % | 1 | RW |
| 6412 | 1 | DALI group 0 - set power-on level 0-100 %. | UInt16 | % | 1 | RW |
| 6413 | 1 | DALI group 0 - set system-failure level 0-100 %. | UInt16 | % | 1 | RW |
| 6800 | 1 | Broadcast (line 0) - arc power level Broadcast block: address = 7000 x channel + (6800 + signal), i.e. it controls every ballast on the line. This row is line 0, signal 6800; the second line repeats at +7000. Range 0-100 %. | UInt16 | % | 1 | RW |
| 6801 | 1 | Broadcast (line 0) - arc power off / on 0 = off, 1-100 %. | UInt16 | % | 1 | RW |
| 6802 | 1 | Broadcast (line 0) - step down / up 0 = step down, 1 = step up. | UInt16 | - | 1 | RW |
| 6803 | 1 | Broadcast (line 0) - recall min level 1 = recall min level (write-only trigger). | UInt16 | - | 1 | W |
| 6804 | 1 | Broadcast (line 0) - recall max level 1 = recall max level (write-only trigger). | UInt16 | - | 1 | W |
| 6805 | 1 | Broadcast (line 0) - go to scene Scene number, 0-15. | UInt16 | - | 1 | RW |
| 6806 | 1 | Broadcast (line 0) - store current level as scene Scene number, 0-15. | UInt16 | - | 1 | RW |
| 6807 | 1 | Broadcast (line 0) - clear / remove scene Scene number, 0-15. | UInt16 | - | 1 | RW |
| 6808 | 1 | Broadcast (line 0) - set fade time 0-15. | UInt16 | - | 1 | RW |
| 6809 | 1 | Broadcast (line 0) - set fade rate 1-15. | UInt16 | - | 1 | RW |
| 6810 | 1 | Broadcast (line 0) - set min level 0-100 %. | UInt16 | % | 1 | RW |
| 6811 | 1 | Broadcast (line 0) - set max level 0-100 %. | UInt16 | % | 1 | RW |
| 6812 | 1 | Broadcast (line 0) - set power-on level 0-100 %. | UInt16 | % | 1 | RW |
| 6813 | 1 | Broadcast (line 0) - set system-failure level 0-100 %. | UInt16 | % | 1 | RW |
| 6814 | 1 | Broadcast (line 0) - multicontrol Combined DALI command word: 0 off, 1-100 % arc power, 2 step up, 3 step down, 1XX go to scene XX, 2XX store scene XX, 3XX remove scene XX, 1XXX set fade rate, 2XXX set fade time, 3XXX set min level, 4XXX set max level, 5XXX set power-on level, 6XXX set system-failure level. | UInt16 | - | 1 | RW |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: HMS/Intesis 'Intesis Modbus Server - DALI' user manual r1.5 EN, section 3 'Modbus interface' and section 3.4 'Modbus Address Map' - vendor-hosted by HMS Networks (SHA-256 of the copy read: see the seed's own document URL). The map is fixed but expressed as formulas, so this seed carries three complete blocks at their first index instead of every expansion: the single DALI device block for channel 0 / short address 0 (signals 0-15, addresses 7000 x channel + 100 x short address + signal), the DALI group block for line 0 / group 0 (addresses 7000 x line + 20 x group + 6400 + signal) and the broadcast block for line 0 (addresses 7000 x channel + 6800 + signal). The formulas are printed in each block's description, so further devices, groups and the second DALI line can be addressed without another seed. Base: the manual states for every block that 'Modbus address from the formula is expressed in link layer format. This is, first register address is 0', hence zero_based, and it notes that the fixed map only applies when the Modbus Addresses parameter is set to Fixed in Intesis MAPS. Transport: the manual documents Modbus TCP with port 502 as the default TCP port; it says the Modbus slave number 'must be configured' in MAPS and prints no factory value and no relation between the unit identifier and the DALI line, so unit_id 1 is a placeholder to set on site; Modbus RTU exists only on the single-channel version, whose serial frame the manual leaves entirely to configuration ('baud rate can be selected between ... parity ... and stop bits ... can be selected as well', with no factory value printed), so the seed declares the TCP path rather than defaulting a serial frame. All registers are 16-bit signed integers in big-endian order per section 3.1; the seed types them UInt16 because every documented value range (0-100 %, scene 0-15, bit fields) is non-negative.
Related devices
- INMBSDAI001I000 Daikin domestic AC to Modbus RTU gatewayHMS Networks (Intesis)
- INMBSFGL001I000 – Fujitsu domestic and VRF air conditioners to Modbus RTU gatewayHMS Networks (Intesis)
- INMBSMIT001I000 – Mitsubishi Electric AC (Domestic, Mr. Slim, City Multi) to Modbus RTU gatewayHMS Networks (Intesis)
- INMBSPAN001R000 – Panasonic air conditioners (Ecoi, EcoG, PACi) to Modbus RTU gatewayHMS Networks (Intesis)