All devices

HMS Networks (Intesis) · Lighting controller

Intesis Modbus Server - DALI gateway (1 and 2 DALI-channel versions) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
01
DALI device 0 - ballast / lamp failure bit fields (ECG15-ECG0)
Single-device block: address = 7000 x channel + 100 x short address + signal. This row is channel 0, short address 0, signal 0 and holds the failure bits of DALI ballasts 0-15; other short addresses repeat at +100, the second DALI channel at +7000.
UInt16-1R
11
DALI device 0 - ballast / lamp failure bit fields (ECG31-ECG16)
Signal 1 of the same block.
UInt16-1R
21
DALI device 0 - ballast / lamp failure bit fields (ECG47-ECG32)
Signal 2 of the same block.
UInt16-1R
31
DALI device 0 - ballast / lamp failure bit fields (ECG63-ECG48)
Signal 3 of the same block.
UInt16-1R
41
DALI device 0 - update all ECG status
0 = update finished, 1 = trigger update.
UInt16-1RW
51
DALI device 0 - ballast status
Bit flags: b7 power cycle, b6 missing short address, b5 reset state, b4 fade running, b3 ballast limit error, b2 lamp power on, b1 lamp failure, b0 ballast failure.
UInt16-1R
61
DALI device 0 - actual level
Actual arc power level of the device, 0-100 %.
UInt16%1R
71
DALI device 0 - device type
0 fluorescent, 1 emergency, 2 discharge, 3 halogen, 4 incandescent, 5 digital signal, 6 LED, 7 switching, 8 colour control.
UInt16-1R
81
DALI device 0 - physical minimum level
0-100 %.
UInt16%1R
91
DALI device 0 - min level
0-100 %.
UInt16%1R
101
DALI device 0 - max level
0-100 %.
UInt16%1R
111
DALI device 0 - power-on level
0-100 %.
UInt16%1R
121
DALI device 0 - system failure level
0-100 %.
UInt16%1R
131
DALI device 0 - fade time
DALI fade time value, 0-15.
UInt16-1R
141
DALI device 0 - fade rate
DALI fade rate value, 1-15.
UInt16-1R
151
DALI device 0 - arc power level
Writable arc power level, 0-100 %.
UInt16%1RW
64001
DALI group 0 - arc power level
Group block: address = 7000 x line + 20 x group + (6400 + signal). This row is line 0, group 0, signal 6400; other groups repeat at +20, the second line at +7000. Range 0-100 %.
UInt16%1RW
64011
DALI group 0 - arc power off / on
0 = off, 1-100 %.
UInt16%1RW
64021
DALI group 0 - step down / up
0 = step down, 1 = step up.
UInt16-1RW
64031
DALI group 0 - recall min level
1 = recall min level (write-only trigger).
UInt16-1W
64041
DALI group 0 - recall max level
1 = recall max level (write-only trigger).
UInt16-1W
64051
DALI group 0 - go to scene
Scene number, 0-15.
UInt16-1RW
64061
DALI group 0 - store current level as scene
Scene number, 0-15.
UInt16-1RW
64071
DALI group 0 - clear / remove scene
Scene number, 0-15.
UInt16-1RW
64081
DALI group 0 - set fade time
0-15.
UInt16-1RW
64091
DALI group 0 - set fade rate
1-15.
UInt16-1RW
64101
DALI group 0 - set min level
0-100 %.
UInt16%1RW
64111
DALI group 0 - set max level
0-100 %.
UInt16%1RW
64121
DALI group 0 - set power-on level
0-100 %.
UInt16%1RW
64131
DALI group 0 - set system-failure level
0-100 %.
UInt16%1RW
68001
Broadcast (line 0) - arc power level
Broadcast block: address = 7000 x channel + (6800 + signal), i.e. it controls every ballast on the line. This row is line 0, signal 6800; the second line repeats at +7000. Range 0-100 %.
UInt16%1RW
68011
Broadcast (line 0) - arc power off / on
0 = off, 1-100 %.
UInt16%1RW
68021
Broadcast (line 0) - step down / up
0 = step down, 1 = step up.
UInt16-1RW
68031
Broadcast (line 0) - recall min level
1 = recall min level (write-only trigger).
UInt16-1W
68041
Broadcast (line 0) - recall max level
1 = recall max level (write-only trigger).
UInt16-1W
68051
Broadcast (line 0) - go to scene
Scene number, 0-15.
UInt16-1RW
68061
Broadcast (line 0) - store current level as scene
Scene number, 0-15.
UInt16-1RW
68071
Broadcast (line 0) - clear / remove scene
Scene number, 0-15.
UInt16-1RW
68081
Broadcast (line 0) - set fade time
0-15.
UInt16-1RW
68091
Broadcast (line 0) - set fade rate
1-15.
UInt16-1RW
68101
Broadcast (line 0) - set min level
0-100 %.
UInt16%1RW
68111
Broadcast (line 0) - set max level
0-100 %.
UInt16%1RW
68121
Broadcast (line 0) - set power-on level
0-100 %.
UInt16%1RW
68131
Broadcast (line 0) - set system-failure level
0-100 %.
UInt16%1RW
68141
Broadcast (line 0) - multicontrol
Combined DALI command word: 0 off, 1-100 % arc power, 2 step up, 3 step down, 1XX go to scene XX, 2XX store scene XX, 3XX remove scene XX, 1XXX set fade rate, 2XXX set fade time, 3XXX set min level, 4XXX set max level, 5XXX set power-on level, 6XXX set system-failure level.
UInt16-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: HMS/Intesis 'Intesis Modbus Server - DALI' user manual r1.5 EN, section 3 'Modbus interface' and section 3.4 'Modbus Address Map' - vendor-hosted by HMS Networks (SHA-256 of the copy read: see the seed's own document URL). The map is fixed but expressed as formulas, so this seed carries three complete blocks at their first index instead of every expansion: the single DALI device block for channel 0 / short address 0 (signals 0-15, addresses 7000 x channel + 100 x short address + signal), the DALI group block for line 0 / group 0 (addresses 7000 x line + 20 x group + 6400 + signal) and the broadcast block for line 0 (addresses 7000 x channel + 6800 + signal). The formulas are printed in each block's description, so further devices, groups and the second DALI line can be addressed without another seed. Base: the manual states for every block that 'Modbus address from the formula is expressed in link layer format. This is, first register address is 0', hence zero_based, and it notes that the fixed map only applies when the Modbus Addresses parameter is set to Fixed in Intesis MAPS. Transport: the manual documents Modbus TCP with port 502 as the default TCP port; it says the Modbus slave number 'must be configured' in MAPS and prints no factory value and no relation between the unit identifier and the DALI line, so unit_id 1 is a placeholder to set on site; Modbus RTU exists only on the single-channel version, whose serial frame the manual leaves entirely to configuration ('baud rate can be selected between ... parity ... and stop bits ... can be selected as well', with no factory value printed), so the seed declares the TCP path rather than defaulting a serial frame. All registers are 16-bit signed integers in big-endian order per section 3.1; the seed types them UInt16 because every documented value range (0-100 %, scene 0-15, bit fields) is non-negative.