All devices

HMS Networks (Intesis) · Protocol gateway

INMBSFGL001I000 – Fujitsu domestic and VRF air conditioners to Modbus RTU gateway Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
2

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
AC unit on/off
0 = off, 1 = on.
UInt16-1RW
11
AC unit mode
0 = Auto, 1 = Heat, 2 = Dry, 3 = Fan, 4 = Cool; the available values depend on the indoor unit.
UInt16-1RW
21
AC unit fan speed
0 = Auto, 1 = Quiet, 2 = Low, 3 = Med, 4 = High; the number of speeds is set with DIP switches.
UInt16-1RW
31
AC unit vane position
1 = Position-1 (horizontal), 2 = Position-2 (horizontal), 3 = Position-3 (medium), 4 = Position-4 (vertical), 10 = Swing.
UInt16-1RW
41
AC unit temperature setpoint
-32768 = initialization value; 16..30 °C (raw 160..300 at the factory degC x10 setting), 61..86 °F; 0 = undetermined.
Int16°C0.1RW
51
AC unit temperature reference
18..30 °C; 0 = undetermined; 0x8000 = no temperature sent from the remote controller.
Int16°C0.1R
61
Window contact
0 = closed (default), 1 = open.
UInt16-1RW
71
Gateway disablement
0 = INMBSFGL001I000 enabled (default), 1 = disabled. Stored in non-volatile memory.
UInt16-1RW
81
AC remote control disablement
0 = remote control enabled (default), 1 = disabled. Stored in non-volatile memory.
UInt16-1RW
91
AC unit operation time
0..65535 hours, counts the time the indoor unit is in the 'On' state.
UInt16h1RW
101
AC unit alarm status
0 = no alarm condition, 1 = alarm condition.
UInt16-1R
111
Error code
0 = no error; 65535 (= -1) = communication error between gateway or remote controller and the AC unit; any other value is listed in the manual's error-code table.
UInt16-1R
131
'Open Window' switch-off timeout
0..30 minutes; factory setting 30.
UInt16min1RW
141
Modbus RTU baud rate
2400 / 4800 / 9600 (default) / 19200 / 38400 / 57600 / 76800 / 115200 bps.
UInt16-1R
151
Modbus slave address
1..63.
UInt16-1R
211
Number of fan speeds
3..6 fan speeds.
UInt16-1R
221
Indoor unit ambient temperature from external sensor
-32768 = no external sensor value; otherwise a temperature supplied from the Modbus side.
Int16°C0.1RW
231
AC real temperature setpoint
Current setpoint in the indoor unit; equals register 4 when no external temperature is provided.
Int16°C0.1R
241
Current AC max setpoint
-32768 = initialization value; the range is specific to the indoor unit.
Int16°C0.1R
251
Current AC min setpoint
-32768 = initialization value; the range is specific to the indoor unit.
Int16°C0.1R
261
AC unit horizontal vane position
0 = Auto (default), 1..5 = Position 1..5, 10 = Swing.
UInt16-1RW
311
Window status (feedback)
0 = not active (default), 1 = active (window open).
UInt16-1R
361
External on/off disablement
0 = not active (default), 1 = active.
UInt16-1RW
401
Window contact on/off disablement
0 = the window contact is not disabling on/off, 1 = it is.
UInt16-1R
431
Filter reset
Write 1 to reset the filter sign.
UInt16-1W
441
Filter status
0 = off, 1 = lit.
UInt16-1R
491
Device ID
0x0D00.
UInt16-1R
501
Software version
Gateway firmware version.
UInt16-1R
561
Antifreeze operation
0 = disabled, 1 = enabled.
UInt16-1RW
641
Economy
0 = disabled, 1 = enabled.
UInt16-1RW
651
Input reference temperature
0x8000 = no external sensor value and no virtual temperature applied.
Int16°C0.1R
661
Return path temperature
-32768 = initialization value; the range is specific to the indoor unit.
Int16°C0.1R
971
Block periodic sendings
0 = non-blocked (default), 1 = blocked.
UInt16-1RW
981
Master/slave (gateway role)
0 = slave, 1 = master.
UInt16-1R
991
Reset
Write 1 to reset the gateway.
UInt16-1W

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: HMS Networks / Intesis user manual 'INMBSFGL001I000 Modbus RTU Gateway – Fujitsu Air Conditioning', v1.5 (01/2024), section 4.2 'Modbus Registers' (4.2.1 control and status, 4.2.2 configuration). The gateway is Modbus RTU (RS-485) and exposes its own fixed holding-register map that mirrors the indoor unit; reach it through a Modbus RTU-to-TCP gateway using the factory serial settings above (9600 bps, 8-N-2, Modbus server address 1; the gateway auto-detects 8-N-1 and 8-N-2). All registers are 16-bit unsigned holding registers, big-endian. The addresses in this file are the manual's base-0 'protocol addresses' (the manual also prints a base-1 'PLC address', which is always this address + 1). Temperature registers are signed 16-bit and their magnitude follows the gateway's DIP switches (degC x1, degC x10 or degF), so the 0.1 scale factors below assume the factory default degC x10; with the x1 setting the readings are whole degrees. Register 22 (external reference temperature) only has an effect on the domestic RAC line when the additional communication accessory that enables the gateway link is fitted; on those units the setpoint is still controlled from the remote controller.